← All reports
PDF Excel ReqIF

Nuclear Reactor Protection System

System Requirements Specification (SyRS) — ISO/IEC/IEEE 15289 — Specification | IEEE 29148 §6.2–6.4
Generated 2026-03-27 — UHT Journal / universalhex.org

Referenced Standards

StandardTitle
IEC 60584
IEC 60747-5-5
IEC 60751
IEC 61513 Nuclear power plants — Instrumentation and control important to safety
IEEE 1115
IEEE 242
IEEE 317
IEEE 323
IEEE 338
IEEE 344
IEEE 384
IEEE 450
IEEE 485
IEEE 603
IEEE 603-2018
IEEE 7-4.3.2
IEEE 946

Acronyms & Abbreviations

AcronymExpansion
ARC Architecture Decisions
CCCS Completeness, Consistency, Correctness, Stability
EARS Easy Approach to Requirements Syntax
IFC Interface Requirements
STK Stakeholder Requirements
SUB Subsystem Requirements
SYS System Requirements
UHT Universal Hex Taxonomy
VER Verification Plan

Stakeholder Requirements (STK)

RefRequirementV&VTags
STK-NEEDS-001 The Nuclear Reactor Protection System SHALL comply with NRC 10 CFR 50.55a, IEEE 603-2018, and IEC 61513 as the governing regulatory and standards framework for safety system design, qualification, and operation.
Rationale: Nuclear safety systems must comply with governing regulatory framework (10 CFR 50.55a, IEEE 603, IEC 61513) as a condition of NRC licensing. Non-compliance prevents plant operation and may void safety analysis basis.
Inspection stakeholder, regulatory, session-199
STK-NEEDS-002 The Nuclear Reactor Protection System SHALL automatically initiate reactor trip and engineered safety features actuation without operator action when plant parameters exceed safety limits, ensuring protection of the reactor core, primary pressure boundary, and containment.
Rationale: Primary safety function of the RPS: prevent core damage, pressure boundary failure, and containment breach during design-basis events. Automatic initiation required because operator response times (minutes) exceed the timeline of fast transients like rod ejection or large-break LOCA (seconds).
Demonstration stakeholder, operator, session-199
STK-NEEDS-003 The Nuclear Reactor Protection System SHALL achieve a probability of failure on demand of less than 1E-5 per demand for reactor trip and less than 1E-4 per demand for each ESF actuation function, demonstrated through probabilistic risk assessment.
Rationale: PFD targets of 1E-5 (trip) and 1E-4 (ESF) derive from NRC regulatory expectations for safety system reliability consistent with Core Damage Frequency goals of 1E-4/reactor-year. Lower PFD for trip reflects its role as primary protection barrier.
Analysis stakeholder, reliability, session-199
STK-NEEDS-004 The Nuclear Reactor Protection System SHALL limit spurious reactor trips to no more than one per year attributable to protection system malfunctions, balancing safety reliability against plant availability and economic impact.
Rationale: Spurious trips cause thermal cycling stress on reactor components, economic losses (~$1M per event for a PWR), and potential for operator error during unnecessary transients. One per year is industry good practice per EPRI guidelines, balancing safety margin against availability.
Analysis stakeholder, availability, session-199
STK-NEEDS-005 The Nuclear Reactor Protection System SHALL support complete surveillance testing of all trip functions during power operation without requiring plant shutdown or reducing the safety function capability below the minimum required by Technical Specifications.
Rationale: Technical Specifications require periodic surveillance testing (typically 92-day intervals per NUREG-1431). Testing must be possible at power because refueling outage frequency (18-24 months) far exceeds required test intervals. Degrading safety capability during testing would violate single-failure criterion.
Demonstration stakeholder, maintenance, session-199
STK-NEEDS-006 The Nuclear Reactor Protection System SHALL provide operators with reliable indication of critical safety parameters during and after design-basis accidents per Regulatory Guide 1.97, enabling informed decisions on emergency operating procedures.
Rationale: RG 1.97 post-accident monitoring is required by 10 CFR 50.34(f)(2)(xix). Operators must assess plant state during accidents to select emergency operating procedures and determine need for protective actions. Without qualified indications, operators cannot verify automatic safety system response or take manual corrective action.
Inspection stakeholder, operator, session-199
STK-NEEDS-007 The Nuclear Reactor Protection System SHALL maintain physical, electrical, and functional independence from non-safety plant control systems to prevent common-cause failures and ensure that no single credible failure or malfunction in the non-safety systems can prevent the safety function.
Rationale: Independence from non-safety systems is a fundamental principle of IEEE 603 Clause 5.6 and NRC GDC 24. Common-cause failure between safety and non-safety systems was a contributing factor in multiple nuclear incidents. Any coupling creates a path for non-safety system faults to disable protection.
Inspection stakeholder, safety, session-199
STK-NEEDS-008 The Nuclear Reactor Protection System SHALL be environmentally and seismically qualified to perform its safety functions under all postulated normal, abnormal, and accident conditions including loss-of-coolant accident, main steam line break, and safe shutdown earthquake per IEEE 323 and IEEE 344.
Rationale: Environmental and seismic qualification ensures the RPS functions during the very conditions it must protect against. IEEE 323 (environmental) and IEEE 344 (seismic) qualification programs provide evidence that equipment will perform under LOCA, MSLB, and SSE conditions. Without qualification, safety analyses have no basis.
Test stakeholder, qualification, session-199

System Requirements (SYS)

RefRequirementV&VTags
SYS-REQS-001 The Nuclear Reactor Protection System SHALL initiate opening of the reactor trip breakers within 2.0 seconds of any monitored parameter reaching its trip setpoint, measured from sensor output to breaker opening.
Rationale: 2.0-second trip response time is derived from FSAR Chapter 15 accident analysis assumptions. Faster-developing transients (e.g., rod ejection, large-break LOCA) assume protection system response within this budget. Exceeding 2.0s invalidates the safety analysis and may result in fuel damage before protective action completes.
Test system, performance, session-199
SYS-REQS-002 The Nuclear Reactor Protection System SHALL implement 2-out-of-4 coincidence voting logic for each reactor trip function, with automatic reduction to 2-out-of-3 when one channel is bypassed for maintenance.
Rationale: 2-out-of-4 voting provides the optimum balance: tolerates one channel failure or bypass without losing protective capability, while requiring agreement of two independent channels to prevent spurious trips. Auto-reduction to 2-out-of-3 during maintenance preserves single-failure tolerance per IEEE 603.
Test system, architecture, session-199
SYS-REQS-003 The Nuclear Reactor Protection System SHALL maintain four physically separated and electrically isolated protection channels, with no shared active components, power supplies, or signal paths between any two channels.
Rationale: Four-channel independence satisfies IEEE 603 Clause 5.6 and NRC GDC 21/22. Physical separation prevents fire, flood, or missile from disabling multiple channels. Electrical isolation prevents fault propagation. No shared components ensures a single failure affects only one channel, preserving 2-out-of-4 voting integrity.
Inspection system, independence, session-199
SYS-REQS-004 The Nuclear Reactor Protection System SHALL be designed fail-safe such that any single credible failure within the protection system, including loss of power, shall result in a channel trip output rather than inhibiting the protective action.
Rationale: Fail-safe design is a fundamental nuclear safety principle per IEEE 603 Clause 5.2. Loss of power or component failure must produce a trip signal (safe state) rather than masking a trip condition. This ensures that equipment degradation moves the system toward reactor shutdown, not away from it.
Analysis system, safety, session-199
SYS-REQS-005 The Nuclear Reactor Protection System SHALL initiate engineered safety feature actuation signals within 2.0 seconds of the monitored parameter reaching its actuation setpoint, with completion of all valve and pump sequencing within the time assumed in the FSAR Chapter 15 accident analyses.
Rationale: 2.0-second ESF actuation initiation time is derived from FSAR Chapter 15 safety analyses for LOCA and MSLB. Sequential valve and pump starts must complete within the analysis timeline to ensure emergency core cooling and containment isolation functions are met. Failure to meet timing assumptions may result in exceeding 10 CFR 50.46 acceptance criteria.
Test system, performance, session-199
SYS-REQS-006 The Nuclear Reactor Protection System SHALL remain fully functional during and after a Safe Shutdown Earthquake of 0.3g horizontal and 0.2g vertical peak ground acceleration, with all components qualified per IEEE 344.
Rationale: 0.3g horizontal / 0.2g vertical PGA envelope the site-specific SSE per 10 CFR 100 Appendix A. IEEE 344 qualification by shake-table testing or analysis demonstrates structural integrity and functional capability. If protection equipment fails during an earthquake, seismic-induced transients cannot be mitigated.
Test system, qualification, session-199
SYS-REQS-007 The Nuclear Reactor Protection System SHALL communicate with non-safety plant computer systems only through qualified one-way isolation devices that prevent any data or electrical feedback from the non-safety system to the protection system.
Rationale: One-way isolation satisfies NRC GDC 24 and IEEE 603 Clause 5.6.3. Hardware-enforced unidirectionality prevents cyber attack vectors and fault propagation from non-safety systems. Software-only isolation is insufficient per NRC ISG-04; physical absence of receive capability on the safety side eliminates the attack surface.
Test system, independence, session-199
SYS-REQS-008 The Nuclear Reactor Protection System SHALL provide overlap testing capability from sensor input through logic processing to final actuation device, with each test segment executable at power with no more than one channel per trip function bypassed at any time.
Rationale: Overlap testing per IEEE 338 ensures complete coverage from sensor to actuator with no untested gaps. One-channel-at-a-time bypass limit preserves 2-out-of-3 voting during test, maintaining Technical Specification minimum operable channels. Without overlap coverage, hidden failures in the signal path could accumulate undetected.
Demonstration system, testability, session-199
SYS-REQS-009 The Nuclear Reactor Protection System SHALL provide continuous, qualified indication of Regulatory Guide 1.97 Category 1 variables on dual-redundant displays in the main control room, powered by Class 1E batteries with minimum 4-hour capacity without AC power.
Rationale: RG 1.97 Category 1 variables require qualified, redundant, continuously-available displays for post-accident operator decision-making. 4-hour battery capacity ensures display availability during station blackout (SBO) scenarios per 10 CFR 50.63, which assumes loss of all AC power. Dual redundancy ensures single display failure does not blind operators.
Test system, monitoring, session-199
SYS-REQS-010 While exposed to post-LOCA containment conditions of 340F temperature, 60 psig pressure, and 1E8 rad total integrated dose, the Nuclear Reactor Protection System containment-located instrumentation SHALL continue to provide accurate process measurements within specified accuracy bands for a minimum of 30 days.
Rationale: 340°F, 60 psig, and 1E8 rad envelope the worst-case post-LOCA containment conditions for a large dry PWR containment per FSAR Chapter 6 analysis. 30-day operability covers the period to cold shutdown and accident assessment. IEEE 323 Type Test or analysis must demonstrate these instruments survive the combined thermal, pressure, radiation, and chemical spray environment.
Test system, qualification, session-199
SYS-REQS-011 The Nuclear Reactor Protection System SHALL satisfy single failure criterion per IEEE 603 Clause 5.1, such that no single detectable failure shall prevent the system from performing its minimum required safety functions.
Rationale: Single failure criterion is mandated by NRC GDC 21 and IEEE 603 Clause 5.1. The safety analysis assumes no more than one concurrent failure in the protection system. This requirement ensures that no single detectable failure (electrical, mechanical, or software) can prevent the minimum required safety functions.
Analysis system, safety, session-199
SYS-REQS-012 The Nuclear Reactor Protection System SHALL provide a hardwired manual reactor trip capability from the main control room that is independent of all automatic trip logic and directly opens the reactor trip breakers through a minimum of electrical components.
Rationale: Manual trip provides defense-in-depth against common-cause failure of automatic trip logic, per NRC GDC 20 and BTP 7-19. Independence from automatic logic ensures operators can shut down the reactor even if digital systems suffer common-mode software failure. Minimum electrical components in the manual path reduces failure probability.
Demonstration system, safety, session-199
SYS-REQS-013 The Nuclear Reactor Protection System SHALL implement a cyber security program per 10 CFR 73.54 that protects digital computer and communication systems performing safety functions from cyber attacks, including network isolation of safety-critical digital assets from all external networks, removal or disabling of all unnecessary communication ports and services, and monitoring of access attempts to safety system digital assets with tamper indication at each protection division cabinet.
Rationale: 10 CFR 73.54 mandates cyber security for digital safety systems. Network isolation eliminates remote attack vectors. Port/service reduction minimizes attack surface. Tamper monitoring provides detection of physical access attempts. Failure to implement allows potential adversary manipulation of safety functions — an unacceptable nuclear safety risk.
Inspection system, cybersecurity, session-205
SYS-REQS-014 The Nuclear Reactor Protection System SHALL implement a cyber security program per 10 CFR 73.54 that protects digital computer and communication systems performing safety functions from cyber attacks, including network isolation of safety-critical digital assets from all external networks, removal or disabling of all unnecessary communication ports and services, and monitoring of access attempts to safety system digital assets with tamper indication at each protection division cabinet.
Rationale: DUPLICATE of SYS-REQS-013. Same cyber security requirement text. Should be consolidated during next revision.
Inspection duplicate-of-SYS-REQS-013, session-223
SYS-REQS-015 The Nuclear Reactor Protection System SHALL incorporate diversity and defense-in-depth measures per NRC BTP 7-19 such that no postulated common-cause failure of digital systems can prevent the reactor trip or ESF actuation safety functions. The system SHALL implement at least two diverse processing technologies (FPGA-based coincidence logic and microprocessor-based bistable processing) and SHALL provide a diverse manual actuation path independent of all digital processors for reactor trip and ESF actuation.
Rationale: NRC BTP 7-19 requires diversity and defense-in-depth (D3) analysis demonstrating no common-cause failure of digital systems can prevent safety functions. Two diverse processing technologies (FPGA + microprocessor) ensure software common-cause failure affects at most one processing platform. Diverse manual path provides ultimate backup independent of all digital systems.
Demonstration system, d3, diversity, session-205
SYS-REQS-016 The Nuclear Reactor Protection System SHALL be qualified for electromagnetic compatibility per Regulatory Guide 1.180, with all digital safety system cabinets withstanding conducted and radiated electromagnetic interference at levels enveloping the measured in-plant environment plus 6dB margin, without loss of safety function or generation of spurious actuation signals.
Rationale: EMC qualification per RG 1.180 ensures digital safety systems operate correctly in the plant electromagnetic environment. 6dB margin above measured in-plant levels provides guard band against unmeasured transient sources (e.g., breaker switching, walkie-talkies). Without EMC qualification, conducted or radiated interference could cause spurious trips or inhibit protective action.
Test system, emc, qualification, session-205

Requirements by Category (IEEE 29148)

4
Functional Requirements
8
Performance Requirements
2
Interface Requirements
1
Safety Requirements
2
Security Requirements
1
Environmental Requirements
1
Reliability & Availability
6
Compliance & Regulatory
2
Other

Traceability Matrix — STK to SYS

SourceTargetTypeDescription
STK-NEEDS-007 SYS-REQS-013 derives
STK-NEEDS-008 SYS-REQS-016 derives
STK-NEEDS-002 SYS-REQS-015 derives
STK-NEEDS-007 SYS-REQS-014 derives
STK-NEEDS-002 SYS-REQS-012 derives
STK-NEEDS-001 SYS-REQS-011 derives
STK-NEEDS-008 SYS-REQS-010 derives
STK-NEEDS-006 SYS-REQS-009 derives
STK-NEEDS-005 SYS-REQS-008 derives
STK-NEEDS-007 SYS-REQS-007 derives
STK-NEEDS-008 SYS-REQS-006 derives
STK-NEEDS-002 SYS-REQS-005 derives
STK-NEEDS-002 SYS-REQS-004 derives
STK-NEEDS-007 SYS-REQS-003 derives
STK-NEEDS-004 SYS-REQS-002 derives
STK-NEEDS-003 SYS-REQS-002 derives
STK-NEEDS-002 SYS-REQS-001 derives