← All reports
PDF Excel ReqIF

Emergency Diesel Generator for a UK Nuclear Licensed Site

Verification Plan (SVP) — ISO/IEC/IEEE 15289 — Plan | IEEE 29148 §6.6
Generated 2026-03-27 — UHT Journal / universalhex.org

59
Verification Entries
85
Verification Links
70
Orphans

Verification Requirements (VER)

RefRequirementMethodTags
VER-REQ-001 The Diesel Engine Assembly cold-start acceptance test SHALL confirm self-sustaining rotation within 3 seconds of start signal when tested from -10°C ambient with the starting air system pre-charged to 25 bar.
Rationale: Cold start at -10°C is the worst-case scenario for start time per STK-REQ-017; if the engine meets the 3-second criterion at minimum temperature it will meet it at all higher temperatures. The test confirms fuel injection system and compression pressure are sufficient for cold combustion. Procedure: record time via exhaust thermocouple response and starter air valve closure.
Test verification, diesel-engine-assembly, session-571, idempotency:ver-sub001-cold-start-571, reqs-eng-session-577
VER-REQ-002 The Engine Protection Relay Package functional test SHALL confirm each trip relay (overspeed at 865 rpm, high coolant temperature at 91°C, low oil pressure at 1.9 bar) actuates within 2 seconds with the digital control system de-energised.
Rationale: Testing with the digital control system de-energised confirms fail-safe operation of the hardwired protection as required by ARC-REQ-002 and IEC 61513. The 2-second criterion is derived from the 5-second engine standstill requirement (VER-REQ-003) leaving margin for fuel rack response. Each channel must be tested independently to confirm there is no shared-mode defeat path.
Test verification, diesel-engine-assembly, sil-3, safety-trip, session-571, idempotency:ver-sub-protection-trips-571, reqs-eng-session-577
VER-REQ-003 The Diesel Engine Assembly protection trip test SHALL confirm engine standstill (crankshaft speed below 5 rpm) within 5 seconds of manual trip signal for each of the three protection relay channels at 50% rated load.
Rationale: Testing at 50% load represents a conservative loaded condition without risk of overloading the test power system. Five seconds to standstill bounds the fuel injection system response time and confirms the mechanical trip train integrity. Each of the three channels is tested in independent runs to eliminate compensating failure detection.
Test verification, diesel-engine-assembly, sil-3, safe-state, session-571, idempotency:ver-sub009-safe-state-571, reqs-eng-session-577
VER-REQ-004 The Fuel Injection System interface acceptance test SHALL confirm steady-state fuel feed pressure at the injection pump inlet is 3.0–5.0 bar and fuel cleanliness is ISO 4406 class 18/16/13 or cleaner at rated engine load.
Rationale: The 3.0–5.0 bar pressure range is the OEM injection pump inlet specification; exceedance causes injector spray pattern degradation and sub-band triggers pump cavitation. ISO 4406 class 18/16/13 is the OEM-specified cleanliness limit above which injection nozzle wear rate increases non-linearly. Test at rated load produces worst-case fuel flow and thermal state.
Test verification, diesel-engine-assembly, session-571, idempotency:ver-ifc008-fuel-supply-571, reqs-eng-session-577
VER-REQ-005 The Starting Air System interface test SHALL confirm air start distributor inlet pressure of 25–30 bar at start signal initiation and engine cranking speed reaching 120 rpm within 1.5 seconds, repeated at -10°C ambient.
Rationale: The 25–30 bar inlet pressure range brackets the OEM cranking torque requirement for reliable first-cycle ignition. Achieving 120 rpm within 1.5 seconds confirms the air volume and flow rate are sufficient for the mechanical compression ratio of the engine. Repeating at -10°C validates the system under the worst-case viscosity and thermal conditions per STK-REQ-017.
Test verification, diesel-engine-assembly, sil-3, session-571, idempotency:ver-ifc011-start-air-571, reqs-eng-session-577
VER-REQ-006 The end-to-end EDG start chain acceptance test SHALL confirm bus undervoltage detection within 100 ms, rated voltage and frequency within 10 seconds, and all safety loads connected within 60 seconds of a LOOP signal below 5.94 kV under 100% rated load.
Rationale: This integrated test verifies the complete start chain: LOOP detection (SYS-REQ-002), engine start (SUB-REQ-001), rated output (SYS-REQ-001), and load sequencing (SYS-REQ-003). Testing under 100% rated load step represents the worst-case voltage dip at breaker close. Data sampled at 100 Hz from LOOP detection to full load connection provides the evidence chain for ONR surveillance records.
Test verification, integration, sil-3, session-571, idempotency:ver-integration-edg-start-chain-571, reqs-eng-session-577
VER-REQ-007 The Diesel Engine Assembly 24-hour endurance test SHALL confirm continuous operation at rated output with speed variation not exceeding 750 rpm ±7.5 rpm at all measurement points throughout the test duration.
Rationale: The 24-hour duration demonstrates suitability for extended station blackout events per IEEE 387 and STK-REQ-005. Speed variation ±1% of synchronous speed (750 ±7.5 rpm) is the IEC 60034 governing limit for generator frequency stability; exceedance would cause protective relay operations. Speed is recorded at 1-second intervals at 0h, 1h, 4h, 8h, 16h, and 24h to detect drift and degradation.
Test session-572, verification, diesel-engine-assembly, idempotency:ver-sub002-003-endurance-572, reqs-eng-session-577
VER-REQ-008 The EDG automatic start acceptance test SHALL confirm LOOP detection within 200 ms and bus voltage rising to 6.6 kV ±10% within 10 seconds of a simulated undervoltage signal at 5.80 kV, verified in three consecutive tests from cold standby.
Rationale: Three consecutive tests from cold standby demonstrate the statistical reliability of the start chain rather than a single-shot result. The 5.80 kV stimulus (below the 5.94 kV threshold) represents the worst-case detection-margin operating point. Ten-second voltage rise aligns with SYS-REQ-001 and IEEE 387 acceptance criteria for nuclear emergency diesel generators.
Test session-572, verification, loop-detection, idempotency:ver-ifc001-002-loop-572, reqs-eng-session-577
VER-REQ-009 The Emergency Diesel Generator seismic qualification SHALL demonstrate by analysis per IEEE 344 that all safety-related mounting interfaces maintain structural integrity and functionality at Seismic Category I (0.3g horizontal, 0.2g vertical ZPA).
Rationale: IEEE 344 (IEEE Recommended Practice for Seismic Qualification of Class 1E Equipment for Nuclear Power Generating Stations) is the mandatory qualification standard for safety-related equipment. Analysis using the Original Design Specification static seismic loads is the primary method; shake table testing per IEC 60980 is the fallback if analysis is insufficient. Qualification covers engine cradle welds, generator stator support, and control panel anchors.
Analysis session-572, verification, seismic, idempotency:ver-sub008-seismic-572, reqs-eng-session-577
VER-REQ-010 The Load Sequencer acceptance test SHALL confirm the first priority load group connects within 1 second of generator breaker closure and total safety load restoration completes within 10 seconds with generator voltage remaining within 6.6 kV ±10%.
Rationale: The 1-second first-group connection criterion limits the dip in essential bus voltage to within generator transient recovery limits. The 10-second total restoration window aligns with SYS-REQ-003 load connection requirement. The 500 ms minimum interval between groups is the OEM-specified generator transient recovery time to prevent cumulative voltage collapse. Test uses a resistive load bank per priority group at 10 ms timestamp resolution.
Test session-572, verification, switchgear-load-sequencer, idempotency:ver-sub010-load-seq-572, reqs-eng-session-577
VER-REQ-011 The Diesel Fuel Injection System acceptance test SHALL confirm fuel delivery metering by measuring cylinder-to-cylinder fuel quantity variation using a calibrated combustion analyser at steady-state rated load, achieving ≤±3% of mean fuel quantity per injection event per SUB-REQ-007.
Rationale: SUB-REQ-007 mandates ±3% cylinder-to-cylinder fuel variation to prevent thermal overload; this VER entry provides the specific test procedure — combustion analyser measurement during the monthly surveillance test (SYS-REQ-013). Without an explicit test, injection pump calibration drift could exceed the limit between overhaul intervals, increasing crankshaft fatigue and catastrophic failure risk (hazard H-001).
Test session-580, qc, verification, diesel-engine-assembly, idempotency:ver-fuel-injection-metering-580
VER-REQ-012 The Fuel Oil System volume acceptance test SHALL confirm minimum usable fuel inventory by physical measurement of day tank and bulk storage tank levels under operating conditions, verifying ≥7,000 litres per EDG train with fuel meeting CIMAC Class DM specification per SUB-REQ-011.
Rationale: SUB-REQ-011 mandates a 7,000-litre minimum inventory for 7-day mission duration. Inspection of tank contents and fuel quality certificate ensures the 7-day SBO mission (STK-REQ-005, SYS-REQ-008) can be sustained. Fuel quality verification (CIMAC DM) prevents injection system contamination damage during extended operation when no commercial resupply is possible.
Inspection session-580, qc, verification, fuel-oil-system, idempotency:ver-fuel-oil-inventory-580
VER-REQ-013 The Ultimate Heat Sink cooling water interface acceptance test SHALL confirm minimum flow of 150 m³/h at ≤30°C inlet temperature under rated load conditions using calibrated flow meters, verifying IFC-REQ-003 compliance and confirming jacket water outlet temperature remains below 88°C thermostat setpoint.
Rationale: IFC-REQ-003 defines the cooling water flow and temperature requirement at the EDG/UHS boundary. Testing under rated load conditions is required to confirm heat exchanger performance prior to nuclear plant commissioning — failure to achieve adequate flow would cause engine overtemperature and forced shutdown of the EDG, defeating the safety function during accident conditions.
Test session-580, qc, verification, cooling, idempotency:ver-uhs-cooling-interface-580
VER-REQ-014 The Emergency Diesel Generator MCR interface functional test SHALL verify that all specified analogue and digital EDG operating parameters display correctly at the MCR console, all abnormal condition alarms actuate within 2 seconds of simulated fault injection, and manual start/stop commands are executed within 5 seconds, over the qualified Class 1E cabling per IFC-REQ-005.
Rationale: IFC-REQ-005 specifies the MCR interface signals required for operator monitoring and control. Functional testing of all alarm and command channels is required by ONR Safety Assessment Principles — the operator must be able to diagnose and respond to EDG abnormalities from the MCR during a design basis accident. Without testing, Class 1E cabling faults may prevent alarms from reaching the operator at the critical moment.
Test session-580, qc, verification, mcr-interface, idempotency:ver-mcr-interface-580
VER-REQ-015 The Fuel Supply infrastructure interface inspection SHALL verify the fuel fill connection, overfill protection activation at 95% tank capacity, and automatic day tank level management by confirming minimum 2-hour fuel reserve is maintained during simulated bulk transfer pump failure per IFC-REQ-006.
Rationale: IFC-REQ-006 defines overfill protection and day tank management at the external fuel supply boundary. Demonstration of overfill cutoff prevents environmental release of diesel fuel (a licensable offence at a nuclear site). The 2-hour day tank reserve demonstration confirms EDG resilience to a short-duration bulk transfer pump failure without manual intervention, which is the credited operator action in the fuel replenishment scenario.
Demonstration session-580, qc, verification, fuel-supply-interface, idempotency:ver-fuel-supply-interface-580
VER-REQ-016 The DC Battery System interface acceptance test SHALL verify 125VDC Class 1E control power availability to EDG instrumentation and control equipment with battery voltage maintained within ±2% of nominal during simulated LOOP conditions, and confirm battery charger re-energisation from EDG output bus within 30 seconds of EDG starting per IFC-REQ-007.
Rationale: IFC-REQ-007 specifies the DC power interface critical for EDG control system function and subsequent restart capability. The battery charger re-energisation test validates the feedback loop (EDG powers charger → charger maintains battery → battery enables subsequent starts) that must function during extended LOOP events. Voltage tolerance of ±2% ensures relay pick-up voltages remain within manufacturer specification throughout the demand event.
Test session-580, qc, verification, dc-battery-interface, idempotency:ver-dc-battery-interface-580
VER-REQ-017 Verify SUB-REQ-014: Starting Air System factory acceptance test SHALL measure actual air receiver bank pressure using calibrated gauges after full charge, confirm minimum 25 bar and maximum 30 bar on both banks, then perform three consecutive simulated start blows and confirm post-test pressure on each bank remains above 20 bar.
Rationale: Direct pressure measurement confirms receiver sizing and charge pressure setpoints. Three-blow test confirms capacity margin for the minimum required start attempts without recharging.
Test verification, starting-air-system, session-581, idempotency:ver-sub014-sas-receivers-581
VER-REQ-018 Verify SUB-REQ-019: I&C LOOP detection acceptance test SHALL apply a simulated bus undervoltage to the Qualified I/O Module input, confirm undervoltage flag set within 100 ms by data logging at 1 ms resolution, and confirm air start command hardwired output energised within 200 ms of input application. Test shall be repeated five times with no failures.
Rationale: Timing verification at 1 ms resolution is necessary to demonstrate 100 ms detection budget compliance. Five repetitions provide statistical confidence that the timing is not marginal. Pass criterion is 100 percent compliance — a single timing violation fails the test.
Test verification, ic-system, sil-3, session-581, idempotency:ver-sub019-ic-loop-detection-581
VER-REQ-019 Verify SUB-REQ-020: Engine and Generator Protection Logic functional test SHALL inject simulated overspeed, low oil pressure, and high coolant temperature signals at trip setpoints and confirm de-energise-to-trip relay output achieved within 200 ms of signal injection, measured by oscilloscope at 0.1 ms resolution. Each trip function shall be tested individually and in combination.
Rationale: Individual and combination testing confirms that no single trip function can be masked by another and that the combined protection logic does not introduce additional latency when multiple alarms are active simultaneously.
Test verification, ic-system, sil-3, safety-trip, session-581, idempotency:ver-sub020-ic-protection-trip-581
VER-REQ-020 Verify SUB-REQ-023: I&C self-diagnostic safe-state test SHALL inject a simulated SIL 3 logic self-fault and confirm de-energise-to-trip output within 500 ms, control room fault alarm within 5 seconds, and last-good HMI status data preserved. Pass criterion: all three conditions met in five consecutive fault injections.
Rationale: Safe-state transition testing is mandatory under IEC 61508 SIL 3 to demonstrate the safe failure fraction target. Five repetitions confirm reproducibility. HMI data preservation is verified separately to confirm operators are not left without status during a critical event.
Test verification, ic-system, sil-3, safe-state, session-581, idempotency:ver-sub023-ic-safe-state-581
VER-REQ-021 Verify IFC-REQ-014: Integration test SHALL energise the I&C start command hardwired output to the SAS air start valve, confirm solenoid energisation by discrete feedback within 200 ms of simulated LOOP signal, and verify 125VDC Class 1E power rail maintained throughout the test cycle under simulated loss of normal AC supply.
Rationale: Integration test at the physical interface confirms hardwired signal routing, voltage level, and timing as actually installed — bench-level component tests cannot confirm cable routing or terminal block integrity.
Test verification, interface, starting-air-system, ic-system, session-581, idempotency:ver-ifc014-ic-sas-start-581
VER-REQ-022 Verify IFC-REQ-015: SAS pressure monitoring interface test SHALL confirm 4-20 mA signal range maps correctly to 0-35 bar at the I&C input, scan interval at 1 Hz or faster, and hardwired alarm contacts close within 5 seconds of simulated low-pressure fault injection on each bank independently.
Rationale: Separate verification of the analogue and discrete paths confirms both are functional simultaneously — a common failure mode is a broken hardwired contact that is masked by the healthy analogue signal.
Test verification, interface, starting-air-system, ic-system, session-581, idempotency:ver-ifc015-sas-pressure-monitor-581
VER-REQ-023 Verify SUB-REQ-024: The Bus Undervoltage Sensing Relay factory acceptance test SHALL inject a simulated 4.5kV signal (sustained for 250ms) on each of the three VT inputs independently and confirm automatic start output active within 200ms; SHALL inject a transient dip to 4.5kV lasting only 150ms and confirm no start output; SHALL disable one VT input and confirm two-out-of-three voting still produces start output at 4.5kV sustained 250ms.
Rationale: Three test scenarios verify the three distinct aspects of SUB-REQ-024: timing, transient rejection, and voting logic. All three must pass for the requirement to be verified; failure of any one scenario is a compliance failure against the safety function.
Test verification, electrical-switchgear-and-load-sequencer, sil-3, session-582, idempotency:ver-sub024-buvr-582
VER-REQ-024 Verify SUB-REQ-026: The Synchronising Check Relay acceptance test SHALL inject voltage, frequency, and phase angle combinations at boundary conditions (voltage ±10% nominal, frequency ±0.5Hz, phase ±10 degrees) and verify close permission asserts only within the window; SHALL reduce bus voltage to 10% nominal (0.66kV) sustained for 600ms and verify dead-bus close permission asserts without frequency or phase angle check within 500ms.
Rationale: Boundary condition testing of each synchronising window independently confirms the requirement is met at the most challenging operating points. The dead-bus override test uses 10% nominal (half the 20% threshold) to confirm reliable operation; testing at exactly 20% is insufficient because relay operating band tolerances could cause a false pass.
Test verification, electrical-switchgear-and-load-sequencer, sil-3, session-582, idempotency:ver-sub026-sync-check-582
VER-REQ-025 Verify IFC-REQ-016: Integration test SHALL measure cable loop resistance on the BUVR-to-GCB start circuit at commissioning and confirm it is below 20 ohms; SHALL inject open-circuit fault on the start signal cable and confirm the EDG automatic start sequence initiates (failsafe open-circuit equals start demand); SHALL verify cable routing segregation from non-Class 1E cables by visual inspection against cable tray drawings.
Rationale: Three verification methods address the three distinct aspects of IFC-REQ-016: cable resistance (continuity), failsafe logic (functional), and segregation (inspection). Resistance must be measured at commissioning not just at factory because field cable lengths are not fixed at design. Segregation requires visual inspection against as-built drawings since it cannot be functionally tested.
Test verification, electrical-switchgear-and-load-sequencer, sil-3, session-582, idempotency:ver-ifc016-buvr-gcb-582
VER-REQ-026 Verify IFC-REQ-018: The trip circuit commissioning test SHALL measure total trip circuit resistance and confirm it does not exceed 10 ohms; SHALL apply an open-circuit fault at the protection relay trip contact and verify an MCR alarm appears within 5 seconds; SHALL inject a simulated protection trip and measure GCB trip time from protection relay output to GCB open confirming it is within 100ms at nominal 125VDC and 95VDC.
Rationale: Trip circuit resistance and timing must both be measured at commissioning because field cabling resistance is not determined until installation. The supervision alarm test verifies the wiring integrity monitoring function independently. Testing at 95VDC (minimum battery voltage) is required by IEC 61508 SIL 3 hardware validation to demonstrate worst-case operation under degraded power supply conditions.
Test verification, electrical-switchgear-and-load-sequencer, sil-3, session-582, idempotency:ver-ifc018-geprp-gcb-trip-582
VER-REQ-027 Verify IFC-REQ-017: The Synchronising Check Relay to GCB close-permission interface acceptance test SHALL confirm close permission asserts only when both voltage and frequency are simultaneously within window (boundary combination testing with 9 combinations covering all quadrant boundaries); SHALL inject an anti-pumping test with two consecutive close commands and confirm only one close attempt completes; SHALL withdraw synchronising permission mid-operation and confirm GCB close does not complete.
Rationale: Nine boundary-combination tests are the minimum to verify the AND logic of the three synchronising conditions without testing all permutations. Anti-pumping and permission-withdrawal tests verify the two protection mechanisms specified in IFC-REQ-017 that cannot be inferred from steady-state tests alone.
Test verification, electrical-switchgear-and-load-sequencer, sil-3, session-582, idempotency:ver-ifc017-scr-gcb-close-582
VER-REQ-028 The Generator Circuit Breaker close-time acceptance test SHALL confirm GCB closure onto the 6.6 kV emergency bus within 100 ms of receiving a close command, measured from control relay energisation to primary contact make, under rated bus voltage with simulated safety load.
Rationale: SUB-REQ-025 specifies GCB close time of 100 ms; safety-critical because post-LOOP bus restoration depends on GCB closing before load sequencing begins, and a slow GCB extends bus dead time beyond the 10-second SYS-REQ-001 budget. MoP basis: IEC 62271-100 (High-voltage alternating-current circuit-breakers) defines close-time as the interval from close-coil energisation to primary contact make; 100 ms is within the Class C2 mechanical operating time envelope for 6.6 kV vacuum circuit-breakers.
Test idempotency:ver-req-sub025-gcb-583, reqs-eng-session-583
VER-REQ-029 The Generator Electrical Protection Relay Package functional test SHALL inject a simulated differential current exceeding 5% of rated CT primary current and confirm trip relay operation within 50 ms, with secondary injection confirming correct phase angle discrimination.
Rationale: SUB-REQ-027 requires 87G differential protection with a pickup threshold; this test confirms relay operation within specified timing at the threshold current, the minimum demonstration needed for IEC 60255-151 (Measuring relays and protection equipment) compliance on a UK nuclear site.
Test idempotency:ver-req-sub027-gen-87g-583, reqs-eng-session-583
VER-REQ-030 The Generator Electrical Protection Relay Package trip circuit test SHALL confirm that a protection trip condition causes GCB trip coil energisation within 60 ms and generator field de-excitation within 200 ms, measured from initial fault signal to generator terminal voltage below 10% rated.
Rationale: SUB-REQ-028 specifies the generator de-energise path on protection trip; timing from fault to terminal voltage collapse determines the duration of fault current fed into any bus fault, so the 60ms/200ms thresholds protect against damage to safety loads on the 6.6kV bus. MoP basis: IEC 60255-151 (Measuring relays and protection equipment — functional requirements for over/undercurrent protection) requires relay operate time measurement within ±5% of stated value; 60 ms trip coil energisation and 200 ms field collapse are derived from the generator manufacturer's demagnetisation time constant (typically 100–300 ms for safety-grade machines).
Test idempotency:ver-req-sub028-gen-trip-583, reqs-eng-session-583
VER-REQ-031 The EDG I&C Qualified I/O Module Assembly isolation qualification test SHALL apply 1.5 kV RMS AC voltage for 60 seconds between each safety-classified circuit and non-Class-1E circuit, confirming leakage current below 1 mA, and SHALL repeat after a simulated 0.3g PGA seismic table test per IEEE 344.
Rationale: SUB-REQ-021 requires 1.5 kV RMS Class 1E isolation maintained post-seismic; IEC 60780 (Nuclear power plants — Electrical equipment of the safety system) and IEC 60255 (Measuring relays and protection equipment) both specify dielectric withstand at 1.5 kV as the acceptance threshold for Class 1E signal isolation. The post-seismic repeat confirms that the seismic event has not degraded the isolation barrier — a critical pass for the common-cause failure safety argument.
Test idempotency:ver-req-sub021-io-isolation-583, reqs-eng-session-583
VER-REQ-032 The Starting Air System Air Compressor and Recharge Unit recharge acceptance test SHALL start both compressors with both Air Receiver Banks at 20 bar and confirm pressure of 30 bar is reached within 30 minutes, measured at the receiver outlets, with the compressors at ambient temperature at test start.
Rationale: SUB-REQ-016 specifies a 30-bar/30-minute recharge criterion following a three-start sequence. Post-start recharge capability is safety-critical because a second emergency demand within 30 minutes requires a full-pressure air system. The acceptance test must start from the worst-case 20-bar post-start low to confirm the compressor capacity under design conditions, not just steady-state operation.
Test session-585, qc, starting-air-system, idempotency:ver-sub016-recharge-585
VER-REQ-033 The Starting Air System Moisture Separator and Drain System commissioning inspection SHALL measure compressed air dewpoint at each Air Receiver Bank outlet using a calibrated chilled-mirror hygrometer after 24 hours of system operation, confirming dewpoint at or below minus 40°C at atmospheric pressure.
Rationale: SUB-REQ-017 requires dewpoint ≤ −40°C to prevent ice formation in distribution manifolds and air-start valves during cold ambient conditions (design minimum: −15°C). Chilled-mirror hygrometry is the accepted reference measurement method per ISO 8573-1 (Compressed air quality). The 24-hour steady-state operation period ensures the separator and auto-drain cycle are active and the air system has purged residual commissioning moisture before measurement.
Inspection session-585, qc, starting-air-system, idempotency:ver-sub017-dewpoint-585
VER-REQ-034 The Starting Air System pressure monitoring functional test SHALL verify: (a) with receiver pressure reduced to 27 bar, a control room annunciation appears within 5 seconds; (b) with pressure reduced to 22 bar, the EDG I&C inhibits further start attempts from that bank; (c) with pressure restored above 25 bar, the inhibit clears and start attempts are permitted.
Rationale: SUB-REQ-018 requires two threshold-triggered actions (27-bar alarm, 22-bar inhibit) that protect the starting air system from being depleted below the minimum single-start pressure. Testing each threshold in sequence verifies both the alarm function and the inhibit logic, and the restore test confirms the inhibit is not latching beyond design intent — all three checks are required to verify the complete requirement.
Test session-585, qc, starting-air-system, idempotency:ver-sub018-pressure-alarm-585
VER-REQ-035 The EDG I&C Plant Communication Gateway isolation verification test SHALL confirm unidirectionality by: (a) transmitting a data packet from the safety-classified I&C to the MCR network side; (b) injecting an arbitrary signal on the MCR network side and confirming no signal is detectable on the safety-classified I&C side using a calibrated oscilloscope with 1mV sensitivity.
Rationale: SUB-REQ-022 requires a data diode with no return path to safety-classified I&C. A passive electrical injection test from the normal side — not just a software-level attempt — is required because the safety case must exclude hardware-level coupled pathways. The 1mV sensitivity threshold is taken from IEC 62645 (Nuclear power plants — I&C systems — Requirements for security programmes) acceptance criteria for isolation verification.
Test session-585, qc, ic-system, cybersecurity, idempotency:ver-sub022-data-diode-585
VER-REQ-036 The EDG Building fire protection commissioning inspection SHALL confirm: (a) automatic suppression system actuates on test signal within 5 seconds of detector activation and achieves gas concentration per BS EN 15004 within 30 seconds; (b) two-hour fire-rated barrier is confirmed by documentation review of BS 476 Part 22 certification for all penetrations, doors, and cable transits between Train A and Train B rooms.
Rationale: SUB-REQ-029 specifies a 30-second suppression criterion and a two-hour fire barrier. The inspection combines a functional actuation test (verifying the 30-second time criterion on the actual installed system) with documentary evidence review for the barrier certification, since the two-hour rating is established by material qualification test certificates, not an in-situ burndown test.
Inspection session-585, qc, edg-building, fire-protection, idempotency:ver-sub029-fire-585
VER-REQ-037 Verify IFC-REQ-019: During commissioning, measure combustion air velocity at three points across the engine intake plenum cross-section using a calibrated anemometer at rated fan speed. PASS if all readings are at or below 8 m/s and filter differential pressure is within the range specified for ISO 16890 ePM1 55% filters.
Rationale: Integration test verifying intake air velocity and filter compliance at the engine air intake plenum. Velocity at three points covers the cross-section to detect non-uniform flow distribution that could cause localised engine intake starvation.
Test verification, edg-building, hvac, session-586, idempotency:ver-ifc019-hvac-air-v2-586
VER-REQ-038 Verify IFC-REQ-020: During integrated fire protection commissioning, simulate a confirmed fire detection signal and measure elapsed time from signal generation to full damper closure and fan de-energisation. PASS if both conditions are achieved within 5 seconds on all three test repetitions; any single-run time exceeding 7 seconds is a fail.
Rationale: End-to-end functional test of the fire detection to HVAC isolation hardwired interface. Three repetitions detect intermittent relay faults or damper actuator stiction. The 7-second single-run limit provides margin for relay pick-up jitter while ensuring the mean meets the 5-second requirement threshold.
Test verification, edg-building, fire, hvac, session-586, idempotency:ver-ifc020-fire-hvac-v2-586
VER-REQ-039 Verify IFC-REQ-021: During commissioning inspection, trace the bunded drain path from each Fuel Oil System component (day tank, fill connections, transfer pump, fuel filter) to the sump. PASS if every fuel-wetted component has a continuous bunded path to the sump with no uncontained intermediate drip points, and sump net capacity (measured by survey) equals or exceeds 4,400 litres.
Rationale: Bunded drain path integrity cannot be verified by functional test without deliberate fuel release; inspection of the physical drain routing during commissioning is the appropriate verification method. Sump capacity is verified by dimensional survey against the design drawing, which is both more accurate and safer than a wet test with 4,000L of diesel fuel in a nuclear facility.
Inspection verification, edg-building, flood, fuel, session-586, idempotency:ver-ifc021-drain-fuel-586
VER-REQ-040 Verify SUB-REQ-030: Perform seismic analysis of the Category 1 Building Structure in accordance with BS EN 1998-1 (Eurocode 8: Design of Structures for Earthquake Resistance) using the site-specific design basis spectrum at 0.2g PGA. PASS if maximum computed deflection at any equipment anchor point is at or below 10mm under the design basis loading combination.
Rationale: Full-scale seismic testing of a reinforced concrete EDG building is not practicable; analysis to Eurocode 8 is the standard method accepted by ONR for demonstrating seismic Category I structural integrity. The analysis must use the site-specific design response spectrum, not a generic spectrum, to account for local soil conditions at the nuclear site.
Analysis verification, edg-building, seismic, sil-2, session-586, idempotency:ver-sub030-seismic-586
VER-REQ-041 Verify EDG Building and Support Systems integration: During EDG system integrated test, initiate EDG start from simulated LOOP signal and verify simultaneously: (a) HVAC fans reach rated airflow within 30 seconds; (b) exhaust backpressure does not exceed 50 mbar at 100% rated load; (c) sump high-level alarm is operational; (d) fire detection to HVAC damper isolation operates within 5 seconds on test signal. PASS if all four criteria are met in a single test run at rated load.
Rationale: Integration test exercises all EDG Building and Support Systems components simultaneously as the EDG loads to rated output. Individual component tests cannot detect integration conflicts such as HVAC fan vibration affecting fire detector sensitivity, or exhaust system resonance under combined HVAC and engine load. This test validates that all building sub-functions are compatible at full load.
Test verification, edg-building, integration, session-586, idempotency:ver-building-integration-586
VER-REQ-042 Verify EDG Building inter-train separation: During pre-operational inspection, measure the clear distance between Train A and Train B building compartments at the nearest point and confirm not less than 600 mm. Verify that no penetrations, shared ducting, or cable routes cross the separation barrier without fire stops. PASS if measured separation is ≥600 mm and no unprotected penetrations are found.
Rationale: Physical separation between trains is a passive, permanent attribute of the building structure that can only be verified by dimensional inspection; functional testing cannot confirm structural independence. The 600 mm minimum from SUB-REQ-031 is derived from nuclear separation distance requirements in BS EN 61513.
Inspection verification, edg-building, seismic, session-589, qc, idempotency:ver-building-separation-589, idempotency:ver-building-separation-589
VER-REQ-043 Verify Ventilation and Combustion Air System airflow performance: With the EDG running at 100% rated load, measure total combustion air mass flow at the engine air intake manifold using calibrated anemometry. PASS criterion: measured airflow ≥0.55 kg/s. Perform at ambient temperatures of 10°C, 25°C, and 40°C to verify margin across the design envelope.
Rationale: Combustion air supply is a direct determinant of engine power output and fuel combustion efficiency; insufficient airflow at rated load causes manifold pressure drop, elevated exhaust temperature, and power output shortfall. Testing at three ambient temperatures confirms that the passive inlet design in SUB-REQ-032 delivers the required flow across the full UK operating temperature range.
Test verification, edg-building, hvac, session-589, qc, idempotency:ver-combustion-air-flow-589, idempotency:ver-combustion-air-flow-589
VER-REQ-044 Verify EDG Building structural breach detection and automatic trip: With EDG in running state, simulate a structural breach detection signal via test input to the structural monitoring system. Verify that the EDG automatic trip signal is generated and the engine initiates shutdown within 5 seconds of simulated breach detection. PASS if shutdown sequence initiates within 5 seconds and main control room alarm is annunciated within 60 seconds.
Rationale: Structural breach detection and automatic trip is a safety function preventing EDG operation in a structurally compromised enclosure (e.g., post-seismic event with building damage); the trip must be fast enough to prevent additional secondary damage while the main control room alarm allows operators to assess and respond. Functional test using simulated input per IEC 61513 (Nuclear power plants — Instrumentation and control important to safety — General requirements for systems) verification requirements is necessary to confirm the monitoring-to-trip signal chain without inducing actual structural damage.
Test verification, edg-building, seismic, session-589, qc, idempotency:ver-building-breach-trip-589, idempotency:ver-building-breach-trip-589
VER-REQ-047 Verify IFC-REQ-022: Coolant Circulation Pump performance test at 25%, 50%, 75%, 100%, and 110% rated engine load. Pass criterion: flow ≥150 L/min, delivery pressure ≥0.8 bar gauge, suction pressure ≥0.2 bar at each load point. Measured by calibrated flow meter and pressure transducers at pump inlet and outlet.
Rationale: Integration test to verify interface compliance at system boundaries. Pump cavitation at standby diesel start-up has caused cooling circuit failures in similar nuclear applications; physical flow measurement under load is the only reliable verification method.
Test verification, engine-cooling, sil-2, session-591, idempotency:ver-ifc022-ec-pump-v2-591
VER-REQ-048 The Pre-Lube and Post-Lube Pump pre-lubrication functional test SHALL confirm that lubricating oil gallery pressure reaches 1.5 bar within 20 seconds of pre-lube command initiation during factory acceptance testing, with the engine at rest, oil at 20°C ambient temperature, and the start air valve confirm-closed interlock engaged.
Rationale: Verifies REQ-SEEDGUKNUCLEAR-066: demonstrates that pre-lube timing and pressure specification are met before air start valve is permitted to open, as required for IEEE 387 compliance
Test
VER-REQ-049 The Engine-Driven Lube Oil Pump pressure performance test SHALL confirm oil gallery pressure within 3.5 bar to 5.5 bar at rated engine speed (750 rpm) across the operating temperature range by measuring main gallery pressure at three oil temperatures: 60°C, 80°C, and 100°C during the 24-hour endurance run.
Rationale: Verifies REQ-SEEDGUKNUCLEAR-067: temperature-swept pressure measurement during endurance test confirms pump performance at all operating viscosity points; cannot be verified by inspection alone as viscosity-dependent performance requires thermal soak
Test
VER-REQ-050 The Post-Lube and post-shutdown oil circulation test SHALL confirm that oil gallery pressure remains above 0.8 bar for no less than 10 minutes following a simulated manual shutdown from 100% rated load, with turbocharger inlet temperature measured at 1-minute intervals to confirm thermal purge.
Rationale: Verifies REQ-SEEDGUKNUCLEAR-070: post-lube duration at minimum pressure is the only way to confirm that turbocharger bearing cartridge heat purge is adequate; analysis alone cannot substitute for empirical thermal measurement
Test
VER-REQ-051 The Automatic Voltage Regulator steady-state regulation acceptance test SHALL apply step loads at 25%, 50%, 75%, and 100% rated output at power factors of 0.8 lagging and unity, measuring terminal voltage at each steady-state point to confirm it remains within ±1% of 6.6kV (6.534kV to 6.666kV).
Rationale: Verifies REQ-SEEDGUKNUCLEAR-072: steady-state voltage accuracy at all load points and power factors must be measured empirically; the IEEE Std 387 generator acceptance test protocol requires voltage regulation verification across the full load envelope
Test
VER-REQ-052 The Automatic Voltage Regulator transient recovery test SHALL apply a block load step equivalent to the largest single load group in the sequencer table while measuring terminal voltage at 100ms intervals, confirming voltage recovery to within ±3% of 6.6kV within 1.5 seconds with no generator protection trip.
Rationale: Verifies REQ-SEEDGUKNUCLEAR-073: block-load step testing is mandatory per IEEE Std 387 generator acceptance; the 1.5-second window and ±3% recovery threshold must be demonstrated empirically to confirm downstream motor contactor immunity
Test
VER-REQ-053 The Generator Neutral Earthing Unit design verification SHALL confirm by calculation per IEC 60034-3 that the resistor-loaded transformer limits phase-to-earth fault current to not more than 5 amperes at generator terminal voltage, with the calculation peer-reviewed and included in the safety case documentation.
Rationale: Verifies REQ-SEEDGUKNUCLEAR-074: high-impedance earthing is verified by design analysis rather than fault injection testing, as intentional earth fault injection at generator voltage would risk winding damage; impedance calculation is standard practice per IEC 60034-3 and ONR NS-TAST-GD-013
Analysis
VER-REQ-054 The Automatic Voltage Regulator Class 1E qualification inspection SHALL verify by review of the equipment qualification documentation file (EQF) that the AVR has been qualified per IEC 60780 (Class 1E), IEEE Std 344 (seismic at 0.5g/5Hz), and IEEE Std 603 (safety I&C requirements), with certificates reviewed by the Nuclear Licensing Inspector.
Rationale: Verifies REQ-SEEDGUKNUCLEAR-076: Class 1E qualification is verified by inspection of the EQF and qualification test reports; physical re-testing on site is not required provided the original qualification envelope (environment, seismic demand) bounds the as-installed conditions, consistent with ONR ENSREG qualification guidance
Inspection
VER-REQ-055 Verify IFC-REQ-023: Pre-heat system functional test during AC blackout simulation. Procedure: disconnect normal AC supply, confirm UPS feed energises heater, measure jacket water temperature over 4 hours from ambient 10°C. Pass criterion: temperature ≥35°C maintained throughout; thermostat cycling within ±2°C hysteresis band.
Rationale: The pre-heat must remain active during AC blackout precisely when it matters most. A blackout simulation is the only way to verify UPS supply path continuity and thermostat control under actual LOOP event conditions.
Demonstration verification, engine-cooling, sil-2, session-591, idempotency:ver-ifc023-ec-preheat-v2-591
VER-REQ-056 Verify IFC-REQ-024: Thermostatic valve response time and flow characteristic test. Apply 10°C step change from 72°C to 85°C at pump inlet; measure valve stroke completion time and flow split at outlet. Pass: full stroke within 5 seconds; bypass flow ≤5% at 82°C; bypass flow ≥95% at 75°C.
Rationale: The valve stroke response time determines peak coolant temperature overshoot during load steps; measurement at representative temperatures is required to confirm the thermostat characteristic matches design intent.
Test verification, engine-cooling, sil-2, session-591, idempotency:ver-ifc024-ec-thermostat-v2-591
VER-REQ-057 Verify IFC-REQ-025: Engine Cooling to I&C signal interface inspection and functional test. Perform cable routing inspection for physical segregation; loop calibration of both Pt100 4-20mA channels against traceable reference; inject simulated overtemperature condition and confirm trip signal received by I&C within 200ms. Pass: segregation verified, channels within ±1°C, trip response ≤200ms.
Rationale: SIL 2 signal interface requires physical segregation inspection per BS EN 61000 and channel calibration; 200ms trip response is the SIL 2 safety function response time. Only system-level injection test can verify the complete signal chain from sensor to protection relay.
Test verification, engine-cooling, sil-2, safety-critical, session-591, idempotency:ver-ifc025-ec-ic-signals-591
VER-REQ-058 Verify SUB-REQ-037 and SUB-REQ-039: Endurance test at 110% rated load, 35°C ambient, for 4 hours minimum. Pass criterion: jacket water outlet temperature 75°C–85°C maintained continuously; no coolant loss; heat exchanger outlet air below design maximum. Instrumentation: 4 Pt100 sensors in jacket water circuit, 2 in radiator airflow.
Rationale: Combined thermal performance requirements can only be verified together under simultaneous high-load and high-ambient conditions representative of a summer LOOP event. Four hours ensures steady-state thermal equilibrium is reached after the warm-up transient.
Test verification, engine-cooling, sil-2, session-591, idempotency:ver-sub037-039-ec-thermal-591
VER-REQ-059 Verify IFC-REQ-026: Fuel Transfer Pump commissioning test. Simulate low Day Tank level (float switch activation), confirm pump starts automatically and delivers fuel at ≥50 L/min to Day Tank. Measure transfer time from low-level alarm to high-level cutoff. Pass: transfer completes within 30 minutes, pump auto-stops on high level, I&C panel shows correct pump status.
Rationale: The automatic transfer sequence must be verified end-to-end to confirm that float switch, pump control, and I&C monitoring all function correctly together under conditions representative of autonomous engine room operation during a LOOP event.
Test verification, fuel-oil, sil-2, session-591, idempotency:ver-ifc026-fo-pump-591
VER-REQ-060 Verify IFC-REQ-027 and SUB-REQ-044: Fuel system endurance and temperature test. Run engine at 100% rated load for 2 hours. Measure fuel inlet pressure and temperature at injection pump inlet at 30-minute intervals. Pass: pressure continuously 0.3–0.7 bar; temperature 10–40°C; no fuel system faults or alarms; engine maintains rated load throughout.
Rationale: Fuel delivery temperature and pressure must be verified under sustained engine loading to confirm that the EDG building thermal environment and fuel system design maintain the OEM injection pump operating envelope. Short-duration tests do not expose thermal soak effects.
Test verification, fuel-oil, sil-2, session-591, idempotency:ver-ifc027-fo-supply-591
VER-REQ-061 Verify IFC-REQ-028 and SUB-REQ-047: Fuel filter differential pressure test. Introduce controlled particulate loading to filter inlet to simulate contaminated fuel. Measure differential pressure and downstream cleanliness (particle count). Pass: alarm activates at 0.5 bar differential; bypass opens at 1.0 bar; downstream cleanliness ≤ISO 4406 16/13/10 below bypass threshold.
Rationale: Filter performance under contamination conditions is the only means to verify that the bypass valve set-point relationship with the alarm threshold meets the design intent that alarm precedes bypass. Reliance on specification data alone is insufficient for SIL 2 verification.
Test verification, fuel-oil, sil-2, session-591, idempotency:ver-ifc028-fo-filter-591

Traceability Matrix — Verification

RequirementVerified ByDescription
REQ-SEEDGUKNUCLEAR-062 SUB-REQ-039 Endurance test also verifies SUB-REQ-039 heat rejection margin
REQ-SEEDGUKNUCLEAR-083 REQ-SEEDGUKNUCLEAR-076 EQF inspection verifies AVR Class 1E qualification certificates
REQ-SEEDGUKNUCLEAR-082 REQ-SEEDGUKNUCLEAR-074 Design analysis verifies neutral earthing unit limits fault current to 5A
REQ-SEEDGUKNUCLEAR-081 REQ-SEEDGUKNUCLEAR-073 Block-load transient test verifies 1.5s AVR recovery window
REQ-SEEDGUKNUCLEAR-080 REQ-SEEDGUKNUCLEAR-072 AVR steady-state test verifies voltage regulation ±1% across load envelope
REQ-SEEDGUKNUCLEAR-079 REQ-SEEDGUKNUCLEAR-070 Post-lube duration test verifies 10-minute minimum post-shutdown circulation
REQ-SEEDGUKNUCLEAR-078 REQ-SEEDGUKNUCLEAR-067 Engine-Driven pump pressure test verifies steady-state oil pressure band
REQ-SEEDGUKNUCLEAR-077 REQ-SEEDGUKNUCLEAR-066 Pre-lube acceptance test verifies pre-lube timing and pressure spec
REQ-SEEDGUKNUCLEAR-065 SUB-REQ-047 Filter test also verifies SUB-REQ-047 contamination class specification
REQ-SEEDGUKNUCLEAR-064 SUB-REQ-044 Fuel endurance test also verifies SUB-REQ-044 fuel delivery pressure
VER-REQ-003 SUB-REQ-009 Safe state test verifies engine transition to standstill within 5 seconds
VER-REQ-002 SUB-REQ-006 Protection trip test verifies hardwired trip function
VER-REQ-002 SUB-REQ-005 Protection trip test verifies hardwired trip function
VER-REQ-002 SUB-REQ-004 Protection trip test verifies hardwired trip function
VER-REQ-001 SUB-REQ-001 Cold start acceptance test verifies engine start self-sustain budget
VER-REQ-006 SUB-REQ-001 End-to-end start chain test verifies cold start self-sustaining rotation requirement
VER-REQ-007 SUB-REQ-002 24-hour endurance test verifies engine speed regulation within ±1.5 rpm
VER-REQ-007 SUB-REQ-003 24-hour endurance test verifies engine steady-state speed regulation
VER-REQ-009 SUB-REQ-008 Seismic qualification analysis verifies engine assembly seismic resistance
VER-REQ-010 SUB-REQ-010 Load sequencer test verifies priority-based load connection sequence
VER-REQ-023 SUB-REQ-024 BUVR factory acceptance test verifies SUB-REQ-024 detection threshold and voting logic
VER-REQ-024 SUB-REQ-026 Sync check relay acceptance test verifies SUB-REQ-026 synchronising windows and dead-bus override
VER-REQ-020 SUB-REQ-023 I&C safe-state test verifies de-energise-to-trip transition
VER-REQ-019 SUB-REQ-020 Protection trip timing test verifies I&C response latency
VER-REQ-018 SUB-REQ-019 LOOP detection timing test verifies I&C start command latency
VER-REQ-017 SUB-REQ-014 Receiver pressure acceptance test verifies SAS capacity requirement
VER-REQ-012 SUB-REQ-011 Tank volume inspection verifies 7,000-litre minimum fuel inventory
VER-REQ-011 SUB-REQ-007 Combustion analyser metering test verifies ±3% fuel variation requirement
VER-REQ-002 SUB-REQ-012 Engine Protection Relay Package test verifies fail-safe architecture
VER-REQ-011 SUB-REQ-013 Fuel Injection System test under Class 1E supply verifies power supply requirement
VER-REQ-005 SUB-REQ-015 Starting Air interface test confirms air start valve opening performance
REQ-SEEDGUKNUCLEAR-047 SUB-REQ-025 GCB acceptance test verifies 100ms close-time requirement
REQ-SEEDGUKNUCLEAR-048 SUB-REQ-027 Differential protection test verifies 87G pickup threshold and trip timing
REQ-SEEDGUKNUCLEAR-049 SUB-REQ-028 Generator trip circuit test verifies protection trip timing and de-excitation
REQ-SEEDGUKNUCLEAR-050 SUB-REQ-021 Class 1E isolation qualification test verifies I/O module isolation and seismic survivability
VER-REQ-032 SUB-REQ-016 Air receiver recharge acceptance test verifies compressor recharge capacity
VER-REQ-033 SUB-REQ-017 Dewpoint commissioning inspection verifies moisture separator performance
VER-REQ-034 SUB-REQ-018 Pressure alarm and inhibit functional test verifies both threshold actions
VER-REQ-035 SUB-REQ-022 Data diode unidirectionality test verifies no return path to safety I&C
VER-REQ-036 SUB-REQ-029 Fire protection commissioning inspection verifies suppression time and fire barrier certification
VER-REQ-040 SUB-REQ-030 Seismic structural analysis verifies building structure anchor deformation requirement
VER-REQ-041 SUB-REQ-034
VER-REQ-041 SUB-REQ-035
VER-REQ-041 SUB-REQ-033
VER-REQ-042 SUB-REQ-031
VER-REQ-043 SUB-REQ-032
VER-REQ-044 SUB-REQ-036
VER-REQ-001 SUB-REQ-001 test
REQ-SEEDGUKNUCLEAR-066 REQ-SEEDGUKNUCLEAR-077 Pre-lube pressure acceptance test verifies pre-lube timing and pressure spec
REQ-SEEDGUKNUCLEAR-067 REQ-SEEDGUKNUCLEAR-078 Engine-Driven pump pressure test verifies steady-state oil pressure band
REQ-SEEDGUKNUCLEAR-070 REQ-SEEDGUKNUCLEAR-079 Post-lube duration test verifies 10-minute minimum circulation after shutdown
REQ-SEEDGUKNUCLEAR-072 REQ-SEEDGUKNUCLEAR-080 AVR steady-state test verifies voltage regulation ±1% across load envelope
REQ-SEEDGUKNUCLEAR-073 REQ-SEEDGUKNUCLEAR-081 Block-load transient test verifies 1.5s recovery window
REQ-SEEDGUKNUCLEAR-074 REQ-SEEDGUKNUCLEAR-082 Design analysis verifies neutral earthing unit limits fault current to 5A
REQ-SEEDGUKNUCLEAR-076 REQ-SEEDGUKNUCLEAR-083 EQF inspection verifies AVR Class 1E qualification certificates
REQ-SEEDGUKNUCLEAR-062 SUB-REQ-037 Endurance test verifies SUB-REQ-037 jacket water temperature band
REQ-SEEDGUKNUCLEAR-065 IFC-REQ-028 Filter differential pressure test verifies IFC-REQ-028 filter interface
REQ-SEEDGUKNUCLEAR-064 IFC-REQ-027 Fuel endurance test verifies IFC-REQ-027 day tank to engine fuel supply
REQ-SEEDGUKNUCLEAR-063 IFC-REQ-026 Fuel Transfer Pump test verifies IFC-REQ-026 transfer pump to day tank
REQ-SEEDGUKNUCLEAR-061 IFC-REQ-025 Cooling to I&C signal test verifies IFC-REQ-025 interface
REQ-SEEDGUKNUCLEAR-060 IFC-REQ-024 Thermostatic valve test verifies IFC-REQ-024 thermostat-to-radiator interface
REQ-SEEDGUKNUCLEAR-059 IFC-REQ-023 Pre-heat system test verifies IFC-REQ-023 pre-heat to jacket water interface
REQ-SEEDGUKNUCLEAR-058 IFC-REQ-022 Coolant Pump performance test verifies IFC-REQ-022 pump-to-jacket interface
IFC-REQ-022 VER-REQ-001 test link
VER-REQ-037 IFC-REQ-019 HVAC-engine air intake commissioning test verifies IFC-REQ-019
VER-REQ-038 IFC-REQ-020 Fire-to-HVAC isolation timing test verifies IFC-REQ-020
VER-REQ-039 IFC-REQ-021 Drain bunding commissioning inspection verifies IFC-REQ-021
VER-REQ-013 REQ-SEEDGUKNUCLEAR-042 UHS cooling flow test verifies EDG-to-UHS thermal interface performance
VER-REQ-014 REQ-SEEDGUKNUCLEAR-044 MCR interface functional test verifies all alarm, display, and command channels
VER-REQ-015 REQ-SEEDGUKNUCLEAR-045 Fuel supply demonstration verifies overfill protection and day tank reserve
VER-REQ-016 REQ-SEEDGUKNUCLEAR-046 DC battery interface test verifies 125VDC supply and charger feedback under LOOP
VER-REQ-021 IFC-REQ-014 Integration test verifies I&C to SAS start command interface
VER-REQ-022 IFC-REQ-015 SAS pressure monitoring interface test verifies IFC-REQ-015
VER-REQ-027 IFC-REQ-017 Sync check relay close permission acceptance test verifies IFC-REQ-017
VER-REQ-026 IFC-REQ-018 GEPRP to GCB trip circuit test verifies IFC-REQ-018 resistance, supervision, and trip timing
VER-REQ-025 IFC-REQ-016 BUVR to GCB interface integration test verifies IFC-REQ-016 resistance, failsafe, and segregation
VER-REQ-006 REQ-SEEDGUKNUCLEAR-043 End-to-end start chain test verifies the PPS-to-EDG LOOP signal interface
VER-REQ-002 IFC-REQ-012 Protection relay functional test verifies the engine-instrumentation interface
VER-REQ-007 IFC-REQ-013 24-hour endurance test verifies the crankshaft-to-generator mechanical coupling
VER-REQ-007 IFC-REQ-010 24-hour endurance test verifies the engine-lube oil system interface
VER-REQ-007 IFC-REQ-009 24-hour endurance test verifies the engine-cooling system thermal interface
VER-REQ-008 REQ-SEEDGUKNUCLEAR-041 EDG automatic start test verifies LOOP detection and bus energisation timing
VER-REQ-008 REQ-SEEDGUKNUCLEAR-040 EDG automatic start test verifies LOOP detection interface with National Grid monitor
VER-REQ-004 IFC-REQ-008 Fuel supply test verifies injection pump inlet pressure and cleanliness
VER-REQ-005 IFC-REQ-011 Air start test verifies distributor inlet pressure and cranking speed

Orphan Requirements (no trace links)

RefDocumentRequirement
IFC-REQ-001 interface-requirements The interface between the Emergency Diesel Generator and the National Grid SHALL detect loss of offsite power via redund...
IFC-REQ-002 interface-requirements The interface between the Emergency Diesel Generator and the Emergency AC Bus SHALL deliver 6.6kV 3-phase 50Hz power thr...
IFC-REQ-003 interface-requirements The interface between the Emergency Diesel Generator and the Ultimate Heat Sink SHALL provide cooling water flow of at l...
IFC-REQ-004 interface-requirements The interface between the Emergency Diesel Generator and the Plant Protection System SHALL accept a hardwired LOOP start...
IFC-REQ-005 interface-requirements The interface between the Emergency Diesel Generator and the Main Control Room SHALL provide continuous analogue and dig...
IFC-REQ-006 interface-requirements The interface between the Emergency Diesel Generator and the Fuel Supply infrastructure SHALL accept diesel fuel deliver...
IFC-REQ-007 interface-requirements The interface between the Emergency Diesel Generator and the DC Battery System SHALL provide 125VDC Class 1E control pow...
STK-REQ-001 stakeholder-requirements The Emergency Diesel Generator system SHALL provide the control room operator with continuous real-time display of EDG o...
STK-REQ-002 stakeholder-requirements The Emergency Diesel Generator system SHALL enable the control room operator to manually start, stop, and authorise load...
STK-REQ-003 stakeholder-requirements The Emergency Diesel Generator system SHALL annunciate all abnormal EDG conditions as distinct alarms in the main contro...
STK-REQ-004 stakeholder-requirements The Emergency Diesel Generator system SHALL provide sufficient information to the shift supervisor to support Limiting C...
STK-REQ-005 stakeholder-requirements The Emergency Diesel Generator system SHALL support implementation of station blackout emergency operating procedures, i...
STK-REQ-006 stakeholder-requirements The Emergency Diesel Generator system SHALL enable fault diagnosis through locally accessible instrumentation and test p...
STK-REQ-007 stakeholder-requirements The Emergency Diesel Generator system SHALL support safe maintenance isolation through lock-out/tag-out provisions on al...
STK-REQ-008 stakeholder-requirements The Emergency Diesel Generator system SHALL support calibration and functional testing of all protection and control ins...
STK-REQ-009 stakeholder-requirements The Emergency Diesel Generator system SHALL provide diagnostic access to control system parameters and protection setpoi...
STK-REQ-010 stakeholder-requirements The Emergency Diesel Generator system SHALL demonstrate compliance with ONR Safety Assessment Principles (SAPs) for engi...
STK-REQ-011 stakeholder-requirements The Emergency Diesel Generator system SHALL maintain a deterministic safety case demonstrating that the EDG fulfils its ...
STK-REQ-012 stakeholder-requirements The Emergency Diesel Generator system SHALL achieve a start-on-demand reliability of at least 0.975 and a 24-hour missio...
STK-REQ-013 stakeholder-requirements The Emergency Diesel Generator system SHALL maintain complete qualification evidence, maintenance records, and modificat...
STK-REQ-014 stakeholder-requirements The Emergency Diesel Generator system SHALL accommodate OEM-specified maintenance regimes and accept qualified replaceme...
STK-REQ-015 stakeholder-requirements The Emergency Diesel Generator system SHALL prevent failure of backup power supply from contributing to an uncontrolled ...
STK-REQ-016 stakeholder-requirements The Emergency Diesel Generator system SHALL remain functional during and after a design basis earthquake of 0.2g peak gr...
STK-REQ-017 stakeholder-requirements The Emergency Diesel Generator system SHALL operate across the full ambient temperature range of -10°C to +40°C and with...
STK-REQ-018 stakeholder-requirements The Emergency Diesel Generator system SHALL not produce electromagnetic interference that could cause spurious actuation...
SUB-REQ-051 subsystem-requirements The Pre-Lube and Post-Lube Pump SHALL establish a minimum lubricating oil pressure of 1.5 bar at the engine main gallery...
SUB-REQ-052 subsystem-requirements The Engine-Driven Lube Oil Pump SHALL maintain engine main gallery oil pressure within 3.5 bar to 5.5 bar at rated engin...
SUB-REQ-053 subsystem-requirements The Lube Oil Cooler SHALL maintain engine lubricating oil outlet temperature within 80°C to 100°C at 100% rated engine l...
SUB-REQ-054 subsystem-requirements The Lube Oil Filter and Strainer SHALL maintain lubricating oil particle contamination downstream of the filter to ISO 4...
SUB-REQ-055 subsystem-requirements The Pre-Lube and Post-Lube Pump SHALL continue post-shutdown lubrication circulation for a minimum of 10 minutes followi...
SUB-REQ-056 subsystem-requirements When engine lubricating oil gallery pressure falls below 2.0 bar at any time during engine operation, the Engine Protect...
SUB-REQ-057 subsystem-requirements The Automatic Voltage Regulator SHALL maintain the Synchronous Generator terminal voltage within ±1% of 6.6kV in steady-...
SUB-REQ-058 subsystem-requirements The Automatic Voltage Regulator SHALL restore terminal voltage to within ±3% of 6.6kV within 1.5 seconds following a ste...
SUB-REQ-059 subsystem-requirements The Generator Neutral Earthing Unit SHALL limit the earth fault current at the generator terminals to not more than 5 am...
SUB-REQ-060 subsystem-requirements The Generator Cooling Fan SHALL start automatically upon engine rotation exceeding 50 rpm, maintain airflow through the ...
SUB-REQ-061 subsystem-requirements The Automatic Voltage Regulator SHALL be classified as Class 1E I&C equipment per IEC 60780 and IEEE Std 603, and SHALL ...
SYS-REQ-001 system-requirements The Emergency Diesel Generator SHALL start and reach rated voltage (6.6kV ±10%) and rated frequency (50Hz ±2%) within 10...
SYS-REQ-002 system-requirements The Emergency Diesel Generator SHALL automatically start upon detection of bus undervoltage below 5.94kV (90% of nominal...
SYS-REQ-003 system-requirements The Emergency Diesel Generator SHALL connect safety loads to the emergency bus via a priority-based load sequencer, with...
SYS-REQ-004 system-requirements The Emergency Diesel Generator SHALL achieve a start-on-demand reliability of not less than 0.975 per demand, demonstrat...
SYS-REQ-005 system-requirements The Emergency Diesel Generator SHALL sustain continuous operation at rated load for a minimum of 24 hours with a mission...
SYS-REQ-006 system-requirements The Emergency Diesel Generator SHALL maintain output voltage within 6.6kV ±10% and frequency within 50Hz ±2% under all l...
SYS-REQ-007 system-requirements The Emergency Diesel Generator installation SHALL comprise two independent, redundant trains (Train A and Train B) with ...
SYS-REQ-008 system-requirements The Emergency Diesel Generator fuel storage system SHALL hold a minimum 7-day fuel inventory at 100% rated load, with au...
SYS-REQ-009 system-requirements The Emergency Diesel Generator SHALL remain functional during and after a design basis earthquake of 0.2g peak ground ac...
SYS-REQ-010 system-requirements The Emergency Diesel Generator engine SHALL be protected by independent, hardwired trip circuits for overspeed (>115% ra...
SYS-REQ-011 system-requirements The Emergency Diesel Generator building SHALL incorporate automatic fire detection and suppression to extinguish diesel ...
SYS-REQ-012 system-requirements The Emergency Diesel Generator safety-related control and protection systems SHALL be isolated from non-safety networks,...
SYS-REQ-013 system-requirements The Emergency Diesel Generator SHALL support monthly surveillance testing via simulated LOOP signal initiation, a 2-hour...
SYS-REQ-014 system-requirements When one EDG train is inoperable, the remaining train SHALL be capable of supplying 100% of the safety-critical electric...
SYS-REQ-015 system-requirements The Emergency Diesel Generator system SHALL provide a diverse alternate AC power source connection point, capable of acc...
VER-REQ-028 verification-plan The Generator Circuit Breaker close-time acceptance test SHALL confirm GCB closure onto the 6.6 kV emergency bus within ...
VER-REQ-029 verification-plan The Generator Electrical Protection Relay Package functional test SHALL inject a simulated differential current exceedin...
VER-REQ-030 verification-plan The Generator Electrical Protection Relay Package trip circuit test SHALL confirm that a protection trip condition cause...
VER-REQ-031 verification-plan The EDG I&C Qualified I/O Module Assembly isolation qualification test SHALL apply 1.5 kV RMS AC voltage for 60 seconds ...
VER-REQ-047 verification-plan Verify IFC-REQ-022: Coolant Circulation Pump performance test at 25%, 50%, 75%, 100%, and 110% rated engine load. Pass c...
VER-REQ-048 verification-plan The Pre-Lube and Post-Lube Pump pre-lubrication functional test SHALL confirm that lubricating oil gallery pressure reac...
VER-REQ-049 verification-plan The Engine-Driven Lube Oil Pump pressure performance test SHALL confirm oil gallery pressure within 3.5 bar to 5.5 bar a...
VER-REQ-050 verification-plan The Post-Lube and post-shutdown oil circulation test SHALL confirm that oil gallery pressure remains above 0.8 bar for n...
VER-REQ-051 verification-plan The Automatic Voltage Regulator steady-state regulation acceptance test SHALL apply step loads at 25%, 50%, 75%, and 100...
VER-REQ-052 verification-plan The Automatic Voltage Regulator transient recovery test SHALL apply a block load step equivalent to the largest single l...
VER-REQ-053 verification-plan The Generator Neutral Earthing Unit design verification SHALL confirm by calculation per IEC 60034-3 that the resistor-l...
VER-REQ-054 verification-plan The Automatic Voltage Regulator Class 1E qualification inspection SHALL verify by review of the equipment qualification ...
VER-REQ-055 verification-plan Verify IFC-REQ-023: Pre-heat system functional test during AC blackout simulation. Procedure: disconnect normal AC suppl...
VER-REQ-056 verification-plan Verify IFC-REQ-024: Thermostatic valve response time and flow characteristic test. Apply 10°C step change from 72°C to 8...
VER-REQ-057 verification-plan Verify IFC-REQ-025: Engine Cooling to I&C signal interface inspection and functional test. Perform cable routing inspect...
VER-REQ-058 verification-plan Verify SUB-REQ-037 and SUB-REQ-039: Endurance test at 110% rated load, 35°C ambient, for 4 hours minimum. Pass criterion...
VER-REQ-059 verification-plan Verify IFC-REQ-026: Fuel Transfer Pump commissioning test. Simulate low Day Tank level (float switch activation), confir...
VER-REQ-060 verification-plan Verify IFC-REQ-027 and SUB-REQ-044: Fuel system endurance and temperature test. Run engine at 100% rated load for 2 hour...
VER-REQ-061 verification-plan Verify IFC-REQ-028 and SUB-REQ-047: Fuel filter differential pressure test. Introduce controlled particulate loading to ...