← All reports
PDF Excel ReqIF

Emergency Diesel Generator for a UK Nuclear Licensed Site

Hazard & Risk Analysis (HRA) — ISO/IEC/IEEE 15289 — Report | IEC 61508 Phase 3
Generated 2026-03-27 — UHT Journal / universalhex.org

Hazard Register

HazardSeverityFrequencySILSafe State
H-001: Failure to start on demand catastrophic low SIL 3 Reactor trip with diverse backup power (gas turbine or batteries) or immediate controlled shutdown
H-002: Loss of output during operation catastrophic rare SIL 3 Automatic transfer to alternate EDG or grid restoration with reactor trip if neither available
H-003: Engine overspeed critical rare SIL 2 Engine stopped via mechanical overspeed trip and fuel cutoff
H-004: Fire in EDG building critical rare SIL 2 Fire suppression activated, EDG isolated, alternate EDG available
H-005: Fuel contamination or exhaustion critical low SIL 2 Transfer to alternate fuel tank, activate fuel replenishment, alternate EDG available
H-006: Cooling system failure critical low SIL 2 EDG trips on high temperature, alternate EDG takes load
H-007: Common cause failure of multiple EDGs catastrophic rare SIL 4 Diverse alternate AC source (gas turbine, portable generator), DC battery for essential loads, reactor trip and passive cooling
H-008: Seismic damage critical rare SIL 2 Post-seismic inspection before reliance, seismically qualified to design basis
H-009: Spurious start or protection trip major medium SIL 1 Operator verification, manual override with appropriate authorisation
H-010: Cyber attack on control system catastrophic rare SIL 3 Air-gapped backup controls, hardwired trips, manual local operation capability

SIL-Allocated Requirements

RefSILRequirementV&V
IFC-REQ-008 SIL 3 The interface between the Diesel Engine Assembly (Fuel Injection System) and the Fuel Oil System SHALL deliver filtered diesel fuel at 3.0 to 5.0 bar ... Test
IFC-REQ-009 SIL 3 The interface between the Diesel Engine Assembly (Engine Block) and the Engine Cooling System SHALL accept coolant flow at the engine inlet at a minim... Test
IFC-REQ-010 SIL 3 The interface between the Diesel Engine Assembly (Engine Block, Turbocharger) and the Lubrication Oil System SHALL provide lubricating oil at the main... Test
IFC-REQ-011 SIL 3 The Starting Air System–Engine Assembly interface SHALL supply 25–30 bar compressed air to the air start distributor inlet, cranking the engine to at ... Test
IFC-REQ-012 SIL 3 The interface between the Diesel Engine Assembly and the EDG Instrumentation and Control System SHALL provide continuous 4-20 mA analogue signals for:... Inspection
IFC-REQ-013 SIL 3 The interface between the Diesel Engine Assembly (Crankshaft and Flexible Shaft Coupling) and the Synchronous Generator rotor shaft SHALL transmit rat... Test
IFC-REQ-014 SIL 3 The interface between the EDG Instrumentation and Control System and the Starting Air System Air Start Valve SHALL transmit a 125VDC Class 1E start co... Test
IFC-REQ-016 SIL 3 The interface between the Bus Undervoltage Sensing Relay and the Generator Circuit Breaker shall carry a hardwired Class 1E 125VDC discrete start init... Test
IFC-REQ-017 SIL 3 The interface between the Synchronising Check Relay and the Generator Circuit Breaker SHALL carry a hardwired 125VDC discrete close-permission signal ... Test
IFC-REQ-018 SIL 3 The interface between the Generator Electrical Protection Relay Package and the Generator Circuit Breaker SHALL deliver a hardwired trip signal via a ... Test
IFC-REQ-022 SIL 2 The interface between the Coolant Circulation Pump and the Engine Jacket Water Circuit SHALL transmit coolant at a minimum flow rate of 150 L/min at 0... Test
IFC-REQ-023 SIL 2 The interface between the Engine Pre-heat System and the Engine Jacket Water Circuit SHALL maintain standby jacket water temperature at ≥35°C using a ... Demonstration
IFC-REQ-024 SIL 2 The interface between the Thermostatic Control Valve and the Radiator/Heat Exchanger SHALL route hot-side coolant flow to the heat exchanger at 0% to ... Test
IFC-REQ-025 SIL 2 The interface between the Engine Cooling System and the EDG Instrumentation and Control System SHALL provide two independent 4-20 mA Pt100 temperature... Inspection
IFC-REQ-026 SIL 2 The interface between the Fuel Transfer Pump and the Day Tank SHALL deliver fuel at a minimum transfer rate of 50 L/min from the Bulk Storage Tank, co... Test
IFC-REQ-027 SIL 2 The interface between the Day Tank and the engine fuel injection system SHALL provide a continuous, uninterrupted fuel supply at 0.3 bar to 0.7 bar ga... Test
IFC-REQ-028 SIL 2 The interface between the Fuel Oil Strainer and Filter Assembly and the engine fuel injection system SHALL provide clean fuel at ISO 4406 ≤16/13/10, w... Inspection
SUB-REQ-001 SIL 3 The Diesel Engine Assembly SHALL achieve self-sustaining engine rotation within 3 seconds of receiving a start signal from the Starting Air System, wi... Test
SUB-REQ-002 SIL 3 The Diesel Engine Assembly SHALL maintain engine speed within 750 rpm ±1.5 rpm (±0.2%) in steady-state operation under all loads from 0% to 110% rated... Test
SUB-REQ-003 SIL 3 The Diesel Engine Assembly SHALL sustain continuous mechanical power output at 100% rated brake mean effective pressure for a minimum of 720 hours (30... Analysis
SUB-REQ-004 SIL 3 The Engine Protection Relay Package SHALL detect engine overspeed exceeding 863 rpm (115% of rated 750 rpm), and SHALL trip the Diesel Fuel Injection ... Test
SUB-REQ-005 SIL 3 The Engine Protection Relay Package SHALL detect engine lubricating oil pressure below 2.0 bar at the main oil gallery, and SHALL initiate an engine t... Test
SUB-REQ-006 SIL 3 The Engine Protection Relay Package SHALL detect engine jacket water coolant temperature exceeding 90°C at the cylinder head outlet, and SHALL initiat... Test
SUB-REQ-007 SIL 3 The Diesel Fuel Injection System SHALL meter fuel delivery with a maximum cylinder-to-cylinder variation of ±3% of mean fuel quantity per injection ev... Test
SUB-REQ-008 SIL 3 The Diesel Engine Assembly, including all sub-components and their mounting interfaces, SHALL be qualified to remain functional during and after a sei... Analysis
SUB-REQ-009 SIL 3 When any Engine Protection Relay Package trip setpoint is exceeded, the Diesel Engine Assembly SHALL transition to its safe state (all fuel injection ... Test
SUB-REQ-012 SIL 3 The Engine Protection Relay Package SHALL implement a fail-safe de-energise-to-trip relay architecture such that loss of 125VDC control power to any t... Demonstration
SUB-REQ-014 SIL 3 The Starting Air System Air Receiver Banks (A and B) SHALL each maintain a minimum stored pressure of 25 bar and a maximum operating pressure of 30 ba... Test
SUB-REQ-015 SIL 3 The Starting Air System Air Start Valve and Distribution Manifold SHALL fully open and deliver compressed air to all engine cylinders within 0.5 secon... Test
SUB-REQ-018 SIL 3 When Starting Air System receiver pressure drops to 27 bar on either bank, the Pressure Monitoring and Low-Pressure Alarm component SHALL generate a c... Test
SUB-REQ-019 SIL 3 The EDG Instrumentation and Control System Automatic Start Logic Controller SHALL detect emergency bus undervoltage below 5.94 kV within 100 ms and is... Test
SUB-REQ-020 SIL 3 The EDG Instrumentation and Control System Engine and Generator Protection Logic SHALL generate a de-energise-to-trip relay output within 200 ms of an... Analysis
SUB-REQ-021 SIL 3 The EDG Instrumentation and Control System Qualified I/O Module Assembly SHALL provide Class 1E qualified electrical isolation of at least 1.5 kV RMS ... Test
SUB-REQ-022 SIL 3 The EDG Instrumentation and Control System Plant Communication Gateway SHALL be implemented as a unidirectional data diode transmitting EDG status dat... Inspection
SUB-REQ-023 SIL 3 When the EDG Instrumentation and Control System Automatic Start Logic Controller detects a self-diagnostic fault in any SIL 3 function, the I&C System... Test
SUB-REQ-024 SIL 3 The Bus Undervoltage Sensing Relay SHALL detect 6.6kV emergency bus voltage below 4.6kV (70% nominal) sustained for more than 200ms and issue an EDG a... Test
SUB-REQ-025 SIL 3 The Generator Circuit Breaker SHALL close onto the 6.6kV emergency bus within 100ms of receiving a close command from the Synchronising Check Relay (l... Test
SUB-REQ-026 SIL 3 The Synchronising Check Relay SHALL permit Generator Circuit Breaker closure only when EDG output voltage is within ±10% of 6.6kV, frequency is within... Test
SUB-REQ-027 SIL 3 The Generator Electrical Protection Relay Package SHALL provide differential protection (87G) with a minimum operating current of 10% rated generator ... Test
SUB-REQ-028 SIL 3 When the Generator Electrical Protection Relay Package detects a protection trip condition or when the Class 1E Switchgear Control Power Supply falls ... Test
SUB-REQ-029 SIL 2 The EDG Building and Support Systems SHALL incorporate an automatic gaseous total-flood fire suppression system (HFC-227ea or CO2 with pre-discharge a... Inspection
SUB-REQ-030 SIL 2 The Category 1 Building Structure SHALL maintain structural integrity and continue to house and protect all installed EDG equipment during and followi... Test
SUB-REQ-031 SIL 2 The Category 1 Building Structure SHALL provide physical separation between EDG trains by a minimum 2-hour rated fire barrier, such that a design basi... Inspection
SUB-REQ-032 SIL 2 The Ventilation and Combustion Air System SHALL supply a minimum of 0.55 kg/s of combustion air per MW of rated engine output at an inlet temperature ... Test
SUB-REQ-033 SIL 2 When the EDG receives an automatic start signal, the Ventilation and Combustion Air System SHALL initiate fan motor start within 5 seconds and achieve... Test
SUB-REQ-034 SIL 2 The Exhaust Silencer and Discharge Stack SHALL limit exhaust gas backpressure to not more than 50 mbar at the turbocharger outlet under all operating ... Test
SUB-REQ-035 SIL 2 The Drain and Spill Containment System SHALL provide bunded containment with a minimum capacity of 110% of the largest single fluid inventory within t... Inspection
SUB-REQ-036 SIL 2 When a Category 1 Building Structure breach is detected by the structural monitoring system, the EDG Building and Support Systems SHALL automatically ... Demonstration
SUB-REQ-037 SIL 2 The Engine Cooling System SHALL maintain engine jacket water outlet temperature within 75°C to 85°C during continuous operation at any load from 25% t... Test
SUB-REQ-038 SIL 2 While in standby, the Engine Cooling System SHALL maintain jacket water temperature at not less than 35°C using the Engine Pre-heat System to ensure t... Demonstration
SUB-REQ-039 SIL 2 The Engine Cooling System SHALL dissipate engine thermal rejection at not less than 110% of rated thermal load at a maximum ambient temperature of 35°... Test
SUB-REQ-040 SIL 2 When jacket water outlet temperature exceeds 95°C or jacket water circuit pressure falls below 0.5 bar gauge, the Engine Cooling System SHALL generate... Test
SUB-REQ-041 SIL 2 The Coolant Circulation Pump SHALL maintain a minimum coolant flow rate of 150 L/min at 0.8 bar differential pressure throughout the engine load range... Test
SUB-REQ-042 SIL 2 The Thermostatic Control Valve SHALL modulate bypass coolant flow to maintain jacket water temperature within ±3°C of the 80°C setpoint during steady-... Test
SUB-REQ-043 SIL 2 The Engine Cooling System pressure boundary, including the Engine Jacket Water Circuit, Coolant Circulation Pump, and Radiator/Heat Exchanger, SHALL r... Analysis
SUB-REQ-044 SIL 2 The Fuel Oil System SHALL supply diesel fuel to the engine injection system at a pressure of 0.3 bar to 0.7 bar gauge and a flow rate sufficient for r... Test
SUB-REQ-045 SIL 2 The Bulk Storage Tank SHALL maintain a minimum fuel inventory of 110% of the 7-day fuel demand at 100% rated load as specified in SYS-REQ-008, with a ... Inspection
SUB-REQ-046 SIL 2 The Day Tank SHALL maintain a working inventory of not less than 4 hours of fuel at rated engine load to provide autonomous operation during a Bulk St... Test
SUB-REQ-047 SIL 2 The Fuel Oil Strainer and Filter Assembly SHALL maintain fuel particle contamination downstream of the filter element at ISO 4406 cleanliness code 16/... Test
SUB-REQ-048 SIL 2 When Day Tank level falls below the transfer initiation setpoint, the Fuel Transfer Pump SHALL automatically start and transfer fuel from the Bulk Sto... Demonstration
SUB-REQ-049 SIL 2 When Day Tank fuel level falls below the engine fuel inlet connection height, the Fuel Oil System SHALL generate a hardwired low-fuel trip signal to t... Test
SUB-REQ-050 SIL 2 The Fuel Oil System bulk storage tank, day tank, pipework, and filter assembly SHALL comply with ATEX Directive 2014/34/EU Zone 2 classification, incl... Inspection
SYS-REQ-001 SIL 3 The Emergency Diesel Generator SHALL start and reach rated voltage (6.6kV ±10%) and rated frequency (50Hz ±2%) within 10 seconds of receiving a loss-o... Test
SYS-REQ-002 SIL 3 The Emergency Diesel Generator SHALL automatically start upon detection of bus undervoltage below 5.94kV (90% of nominal) without operator action, wit... Test
SYS-REQ-003 SIL 3 The Emergency Diesel Generator SHALL connect safety loads to the emergency bus via a priority-based load sequencer, with all safety loads energised wi... Test
SYS-REQ-007 SIL 4 The Emergency Diesel Generator installation SHALL comprise two independent, redundant trains (Train A and Train B) with no shared active components, s... Analysis
SYS-REQ-008 SIL 2 The Emergency Diesel Generator fuel storage system SHALL hold a minimum 7-day fuel inventory at 100% rated load, with automatic transfer from bulk sto... Inspection
SYS-REQ-009 SIL 2 The Emergency Diesel Generator SHALL remain functional during and after a design basis earthquake of 0.2g peak ground acceleration (Seismic Category I... Analysis
SYS-REQ-010 SIL 2 The Emergency Diesel Generator engine SHALL be protected by independent, hardwired trip circuits for overspeed (>115% rated), high coolant temperature... Test
SYS-REQ-011 SIL 2 The Emergency Diesel Generator building SHALL incorporate automatic fire detection and suppression to extinguish diesel fuel fires without manual inte... Test
SYS-REQ-012 SIL 3 The Emergency Diesel Generator safety-related control and protection systems SHALL be isolated from non-safety networks, with safety trip functions im... Analysis
SYS-REQ-014 SIL 3 When one EDG train is inoperable, the remaining train SHALL be capable of supplying 100% of the safety-critical electrical load, with the plant enteri... Analysis
SYS-REQ-015 SIL 4 The Emergency Diesel Generator system SHALL provide a diverse alternate AC power source connection point, capable of accepting a mobile diesel generat... Demonstration
VER-REQ-002 SIL 3 The Engine Protection Relay Package functional test SHALL confirm each trip relay (overspeed at 865 rpm, high coolant temperature at 91°C, low oil pre... Test
VER-REQ-003 SIL 3 The Diesel Engine Assembly protection trip test SHALL confirm engine standstill (crankshaft speed below 5 rpm) within 5 seconds of manual trip signal ... Test
VER-REQ-005 SIL 3 The Starting Air System interface test SHALL confirm air start distributor inlet pressure of 25–30 bar at start signal initiation and engine cranking ... Test
VER-REQ-006 SIL 3 The end-to-end EDG start chain acceptance test SHALL confirm bus undervoltage detection within 100 ms, rated voltage and frequency within 10 seconds, ... Test
VER-REQ-018 SIL 3 Verify SUB-REQ-019: I&C LOOP detection acceptance test SHALL apply a simulated bus undervoltage to the Qualified I/O Module input, confirm undervoltag... Test
VER-REQ-019 SIL 3 Verify SUB-REQ-020: Engine and Generator Protection Logic functional test SHALL inject simulated overspeed, low oil pressure, and high coolant tempera... Test
VER-REQ-020 SIL 3 Verify SUB-REQ-023: I&C self-diagnostic safe-state test SHALL inject a simulated SIL 3 logic self-fault and confirm de-energise-to-trip output within ... Test
VER-REQ-023 SIL 3 Verify SUB-REQ-024: The Bus Undervoltage Sensing Relay factory acceptance test SHALL inject a simulated 4.5kV signal (sustained for 250ms) on each of ... Test
VER-REQ-024 SIL 3 Verify SUB-REQ-026: The Synchronising Check Relay acceptance test SHALL inject voltage, frequency, and phase angle combinations at boundary conditions... Test
VER-REQ-025 SIL 3 Verify IFC-REQ-016: Integration test SHALL measure cable loop resistance on the BUVR-to-GCB start circuit at commissioning and confirm it is below 20 ... Test
VER-REQ-026 SIL 3 Verify IFC-REQ-018: The trip circuit commissioning test SHALL measure total trip circuit resistance and confirm it does not exceed 10 ohms; SHALL appl... Test
VER-REQ-027 SIL 3 Verify IFC-REQ-017: The Synchronising Check Relay to GCB close-permission interface acceptance test SHALL confirm close permission asserts only when b... Test
VER-REQ-040 SIL 2 Verify SUB-REQ-030: Perform seismic analysis of the Category 1 Building Structure in accordance with BS EN 1998-1 (Eurocode 8: Design of Structures fo... Analysis
VER-REQ-047 SIL 2 Verify IFC-REQ-022: Coolant Circulation Pump performance test at 25%, 50%, 75%, 100%, and 110% rated engine load. Pass criterion: flow ≥150 L/min, del... Test
VER-REQ-055 SIL 2 Verify IFC-REQ-023: Pre-heat system functional test during AC blackout simulation. Procedure: disconnect normal AC supply, confirm UPS feed energises ... Demonstration
VER-REQ-056 SIL 2 Verify IFC-REQ-024: Thermostatic valve response time and flow characteristic test. Apply 10°C step change from 72°C to 85°C at pump inlet; measure val... Test
VER-REQ-057 SIL 2 Verify IFC-REQ-025: Engine Cooling to I&C signal interface inspection and functional test. Perform cable routing inspection for physical segregation; ... Test
VER-REQ-058 SIL 2 Verify SUB-REQ-037 and SUB-REQ-039: Endurance test at 110% rated load, 35°C ambient, for 4 hours minimum. Pass criterion: jacket water outlet temperat... Test
VER-REQ-059 SIL 2 Verify IFC-REQ-026: Fuel Transfer Pump commissioning test. Simulate low Day Tank level (float switch activation), confirm pump starts automatically an... Test
VER-REQ-060 SIL 2 Verify IFC-REQ-027 and SUB-REQ-044: Fuel system endurance and temperature test. Run engine at 100% rated load for 2 hours. Measure fuel inlet pressure... Test
VER-REQ-061 SIL 2 Verify IFC-REQ-028 and SUB-REQ-047: Fuel filter differential pressure test. Introduce controlled particulate loading to filter inlet to simulate conta... Test

Safety Case Structure (GSN)

Goal Structuring Notation per GSN Community Standard v3. Top goal decomposes into hazard mitigation sub-goals, each supported by SIL-allocated requirements and verification evidence.

flowchart TD
  G0["<b>G0: Top Goal</b><br/>Emergency Diesel Generator for a UK Nuclear Licensed Site is acceptably safe"]
  S0{"<b>S0: Strategy</b><br/>Argument by hazard<br/>mitigation per IEC 61508"}
  G0 --> S0
  G1["<b>G1: H-001</b><br/>Failure to start on demand<br/>SIL 3"]
  S0 --> G1
  Sn0_0(["<b>SUB-REQ-004</b>"])
  G1 --> Sn0_0
  Sn0_1(["<b>SUB-REQ-007</b>"])
  G1 --> Sn0_1
  Sn0_2(["<b>SYS-REQ-001</b>"])
  G1 --> Sn0_2
  G2["<b>G2: H-002</b><br/>Loss of output during operation<br/>SIL 3"]
  S0 --> G2
  G3["<b>G3: H-003</b><br/>Engine overspeed<br/>SIL 2"]
  S0 --> G3
  Sn2_0(["<b>SUB-REQ-005</b>"])
  G3 --> Sn2_0
  Sn2_1(["<b>SYS-REQ-010</b>"])
  G3 --> Sn2_1
  G4["<b>G4: H-004</b><br/>Fire in EDG building<br/>SIL 2"]
  S0 --> G4
  Sn3_0(["<b>SUB-REQ-029</b>"])
  G4 --> Sn3_0
  Sn3_1(["<b>SYS-REQ-011</b>"])
  G4 --> Sn3_1
  G5["<b>G5: H-005</b><br/>Fuel contamination or exhaustion<br/>SIL 2"]
  S0 --> G5
  Sn4_0(["<b>SYS-REQ-008</b>"])
  G5 --> Sn4_0
  G6["<b>G6: H-006</b><br/>Cooling system failure<br/>SIL 2"]
  S0 --> G6
  Sn5_0(["<b>SUB-REQ-006</b>"])
  G6 --> Sn5_0
  Sn5_1(["<b>SYS-REQ-010</b>"])
  G6 --> Sn5_1
  G7["<b>G7: H-007</b><br/>Common cause failure of multiple EDGs<br/>SIL 4"]
  S0 --> G7
  Sn6_0(["<b>SYS-REQ-007</b>"])
  G7 --> Sn6_0
  Sn6_1(["<b>SYS-REQ-015</b>"])
  G7 --> Sn6_1
  G8["<b>G8: H-008</b><br/>Seismic damage<br/>SIL 2"]
  S0 --> G8
  Sn7_0(["<b>SYS-REQ-009</b>"])
  G8 --> Sn7_0
  G9["<b>G9: H-009</b><br/>Spurious start or protection trip<br/>SIL 1"]
  S0 --> G9
  G10["<b>G10: H-010</b><br/>Cyber attack on control system<br/>SIL 3"]
  S0 --> G10
  Sn9_0(["<b>SYS-REQ-012</b>"])
  G10 --> Sn9_0

GSN Export (YAML)

Machine-readable safety case structure. Import into GSN tools (Astah GSN, ASCE, NOR-STA).

# GSN Safety Case — Emergency Diesel Generator for a UK Nuclear Licensed Site
# Generated 2026-03-27
# Goal Structuring Notation (GSN) per GSN Community Standard v3

goals:
  G0:
    text: "Emergency Diesel Generator for a UK Nuclear Licensed Site is acceptably safe"
    type: top-goal
    supported_by: [S0]

strategies:
  S0:
    text: "Argument by hazard mitigation per IEC 61508"
    supported_by: [G1, G2, G3, G4, G5, G6, G7, G8, G9, G10]

  G1:
    text: "H-001: Failure to start on demand"
    sil: 3
    safe_state: "Reactor trip with diverse backup power (gas turbine or batteries) or immediate controlled shutdown"
    supported_by: [SUB-REQ-004, SUB-REQ-007, SYS-REQ-001, SYS-REQ-002]
    evidence: [VER-REQ-002, VER-REQ-011]
  G2:
    text: "H-002: Loss of output during operation"
    sil: 3
    safe_state: "Automatic transfer to alternate EDG or grid restoration with reactor trip if neither available"
    supported_by: []
    evidence: []
  G3:
    text: "H-003: Engine overspeed"
    sil: 2
    safe_state: "Engine stopped via mechanical overspeed trip and fuel cutoff"
    supported_by: [SUB-REQ-005, SYS-REQ-010]
    evidence: [VER-REQ-002]
  G4:
    text: "H-004: Fire in EDG building"
    sil: 2
    safe_state: "Fire suppression activated, EDG isolated, alternate EDG available"
    supported_by: [SUB-REQ-029, SYS-REQ-011]
    evidence: [VER-REQ-036]
  G5:
    text: "H-005: Fuel contamination or exhaustion"
    sil: 2
    safe_state: "Transfer to alternate fuel tank, activate fuel replenishment, alternate EDG available"
    supported_by: [SYS-REQ-008]
    evidence: []
  G6:
    text: "H-006: Cooling system failure"
    sil: 2
    safe_state: "EDG trips on high temperature, alternate EDG takes load"
    supported_by: [SUB-REQ-006, SYS-REQ-010]
    evidence: [VER-REQ-002]
  G7:
    text: "H-007: Common cause failure of multiple EDGs"
    sil: 4
    safe_state: "Diverse alternate AC source (gas turbine, portable generator), DC battery for essential loads, reactor trip and passive cooling"
    supported_by: [SYS-REQ-007, SYS-REQ-015]
    evidence: []
  G8:
    text: "H-008: Seismic damage"
    sil: 2
    safe_state: "Post-seismic inspection before reliance, seismically qualified to design basis"
    supported_by: [SYS-REQ-009]
    evidence: []
  G9:
    text: "H-009: Spurious start or protection trip"
    sil: 1
    safe_state: "Operator verification, manual override with appropriate authorisation"
    supported_by: []
    evidence: []
  G10:
    text: "H-010: Cyber attack on control system"
    sil: 3
    safe_state: "Air-gapped backup controls, hardwired trips, manual local operation capability"
    supported_by: [SYS-REQ-012]
    evidence: []

solutions:
  IFC-REQ-008:
    text: "The interface between the Diesel Engine Assembly (Fuel Injection System) and the Fuel Oil System SHALL deliver filtered "
    verification: Test
    sil: 3
  IFC-REQ-009:
    text: "The interface between the Diesel Engine Assembly (Engine Block) and the Engine Cooling System SHALL accept coolant flow "
    verification: Test
    sil: 3
  IFC-REQ-010:
    text: "The interface between the Diesel Engine Assembly (Engine Block, Turbocharger) and the Lubrication Oil System SHALL provi"
    verification: Test
    sil: 3
  IFC-REQ-011:
    text: "The Starting Air System–Engine Assembly interface SHALL supply 25–30 bar compressed air to the air start distributor inl"
    verification: Test
    sil: 3
  IFC-REQ-012:
    text: "The interface between the Diesel Engine Assembly and the EDG Instrumentation and Control System SHALL provide continuous"
    verification: Inspection
    sil: 3
  IFC-REQ-013:
    text: "The interface between the Diesel Engine Assembly (Crankshaft and Flexible Shaft Coupling) and the Synchronous Generator "
    verification: Test
    sil: 3
  IFC-REQ-014:
    text: "The interface between the EDG Instrumentation and Control System and the Starting Air System Air Start Valve SHALL trans"
    verification: Test
    sil: 3
  IFC-REQ-016:
    text: "The interface between the Bus Undervoltage Sensing Relay and the Generator Circuit Breaker shall carry a hardwired Class"
    verification: Test
    sil: 3
  IFC-REQ-017:
    text: "The interface between the Synchronising Check Relay and the Generator Circuit Breaker SHALL carry a hardwired 125VDC dis"
    verification: Test
    sil: 3
  IFC-REQ-018:
    text: "The interface between the Generator Electrical Protection Relay Package and the Generator Circuit Breaker SHALL deliver "
    verification: Test
    sil: 3
  IFC-REQ-022:
    text: "The interface between the Coolant Circulation Pump and the Engine Jacket Water Circuit SHALL transmit coolant at a minim"
    verification: Test
    sil: 2
  IFC-REQ-023:
    text: "The interface between the Engine Pre-heat System and the Engine Jacket Water Circuit SHALL maintain standby jacket water"
    verification: Demonstration
    sil: 2
  IFC-REQ-024:
    text: "The interface between the Thermostatic Control Valve and the Radiator/Heat Exchanger SHALL route hot-side coolant flow t"
    verification: Test
    sil: 2
  IFC-REQ-025:
    text: "The interface between the Engine Cooling System and the EDG Instrumentation and Control System SHALL provide two indepen"
    verification: Inspection
    sil: 2
  IFC-REQ-026:
    text: "The interface between the Fuel Transfer Pump and the Day Tank SHALL deliver fuel at a minimum transfer rate of 50 L/min "
    verification: Test
    sil: 2
  IFC-REQ-027:
    text: "The interface between the Day Tank and the engine fuel injection system SHALL provide a continuous, uninterrupted fuel s"
    verification: Test
    sil: 2
  IFC-REQ-028:
    text: "The interface between the Fuel Oil Strainer and Filter Assembly and the engine fuel injection system SHALL provide clean"
    verification: Inspection
    sil: 2
  SUB-REQ-001:
    text: "The Diesel Engine Assembly SHALL achieve self-sustaining engine rotation within 3 seconds of receiving a start signal fr"
    verification: Test
    sil: 3
  SUB-REQ-002:
    text: "The Diesel Engine Assembly SHALL maintain engine speed within 750 rpm ±1.5 rpm (±0.2%) in steady-state operation under a"
    verification: Test
    sil: 3
  SUB-REQ-003:
    text: "The Diesel Engine Assembly SHALL sustain continuous mechanical power output at 100% rated brake mean effective pressure "
    verification: Analysis
    sil: 3
  SUB-REQ-004:
    text: "The Engine Protection Relay Package SHALL detect engine overspeed exceeding 863 rpm (115% of rated 750 rpm), and SHALL t"
    verification: Test
    sil: 3
  SUB-REQ-005:
    text: "The Engine Protection Relay Package SHALL detect engine lubricating oil pressure below 2.0 bar at the main oil gallery, "
    verification: Test
    sil: 3
  SUB-REQ-006:
    text: "The Engine Protection Relay Package SHALL detect engine jacket water coolant temperature exceeding 90°C at the cylinder "
    verification: Test
    sil: 3
  SUB-REQ-007:
    text: "The Diesel Fuel Injection System SHALL meter fuel delivery with a maximum cylinder-to-cylinder variation of ±3% of mean "
    verification: Test
    sil: 3
  SUB-REQ-008:
    text: "The Diesel Engine Assembly, including all sub-components and their mounting interfaces, SHALL be qualified to remain fun"
    verification: Analysis
    sil: 3
  SUB-REQ-009:
    text: "When any Engine Protection Relay Package trip setpoint is exceeded, the Diesel Engine Assembly SHALL transition to its s"
    verification: Test
    sil: 3
  SUB-REQ-012:
    text: "The Engine Protection Relay Package SHALL implement a fail-safe de-energise-to-trip relay architecture such that loss of"
    verification: Demonstration
    sil: 3
  SUB-REQ-014:
    text: "The Starting Air System Air Receiver Banks (A and B) SHALL each maintain a minimum stored pressure of 25 bar and a maxim"
    verification: Test
    sil: 3
  SUB-REQ-015:
    text: "The Starting Air System Air Start Valve and Distribution Manifold SHALL fully open and deliver compressed air to all eng"
    verification: Test
    sil: 3
  SUB-REQ-018:
    text: "When Starting Air System receiver pressure drops to 27 bar on either bank, the Pressure Monitoring and Low-Pressure Alar"
    verification: Test
    sil: 3
  SUB-REQ-019:
    text: "The EDG Instrumentation and Control System Automatic Start Logic Controller SHALL detect emergency bus undervoltage belo"
    verification: Test
    sil: 3
  SUB-REQ-020:
    text: "The EDG Instrumentation and Control System Engine and Generator Protection Logic SHALL generate a de-energise-to-trip re"
    verification: Analysis
    sil: 3
  SUB-REQ-021:
    text: "The EDG Instrumentation and Control System Qualified I/O Module Assembly SHALL provide Class 1E qualified electrical iso"
    verification: Test
    sil: 3
  SUB-REQ-022:
    text: "The EDG Instrumentation and Control System Plant Communication Gateway SHALL be implemented as a unidirectional data dio"
    verification: Inspection
    sil: 3
  SUB-REQ-023:
    text: "When the EDG Instrumentation and Control System Automatic Start Logic Controller detects a self-diagnostic fault in any "
    verification: Test
    sil: 3
  SUB-REQ-024:
    text: "The Bus Undervoltage Sensing Relay SHALL detect 6.6kV emergency bus voltage below 4.6kV (70% nominal) sustained for more"
    verification: Test
    sil: 3
  SUB-REQ-025:
    text: "The Generator Circuit Breaker SHALL close onto the 6.6kV emergency bus within 100ms of receiving a close command from th"
    verification: Test
    sil: 3
  SUB-REQ-026:
    text: "The Synchronising Check Relay SHALL permit Generator Circuit Breaker closure only when EDG output voltage is within ±10%"
    verification: Test
    sil: 3
  SUB-REQ-027:
    text: "The Generator Electrical Protection Relay Package SHALL provide differential protection (87G) with a minimum operating c"
    verification: Test
    sil: 3
  SUB-REQ-028:
    text: "When the Generator Electrical Protection Relay Package detects a protection trip condition or when the Class 1E Switchge"
    verification: Test
    sil: 3
  SUB-REQ-029:
    text: "The EDG Building and Support Systems SHALL incorporate an automatic gaseous total-flood fire suppression system (HFC-227"
    verification: Inspection
    sil: 2
  SUB-REQ-030:
    text: "The Category 1 Building Structure SHALL maintain structural integrity and continue to house and protect all installed ED"
    verification: Test
    sil: 2
  SUB-REQ-031:
    text: "The Category 1 Building Structure SHALL provide physical separation between EDG trains by a minimum 2-hour rated fire ba"
    verification: Inspection
    sil: 2
  SUB-REQ-032:
    text: "The Ventilation and Combustion Air System SHALL supply a minimum of 0.55 kg/s of combustion air per MW of rated engine o"
    verification: Test
    sil: 2
  SUB-REQ-033:
    text: "When the EDG receives an automatic start signal, the Ventilation and Combustion Air System SHALL initiate fan motor star"
    verification: Test
    sil: 2
  SUB-REQ-034:
    text: "The Exhaust Silencer and Discharge Stack SHALL limit exhaust gas backpressure to not more than 50 mbar at the turbocharg"
    verification: Test
    sil: 2
  SUB-REQ-035:
    text: "The Drain and Spill Containment System SHALL provide bunded containment with a minimum capacity of 110% of the largest s"
    verification: Inspection
    sil: 2
  SUB-REQ-036:
    text: "When a Category 1 Building Structure breach is detected by the structural monitoring system, the EDG Building and Suppor"
    verification: Demonstration
    sil: 2
  SUB-REQ-037:
    text: "The Engine Cooling System SHALL maintain engine jacket water outlet temperature within 75°C to 85°C during continuous op"
    verification: Test
    sil: 2
  SUB-REQ-038:
    text: "While in standby, the Engine Cooling System SHALL maintain jacket water temperature at not less than 35°C using the Engi"
    verification: Demonstration
    sil: 2
  SUB-REQ-039:
    text: "The Engine Cooling System SHALL dissipate engine thermal rejection at not less than 110% of rated thermal load at a maxi"
    verification: Test
    sil: 2
  SUB-REQ-040:
    text: "When jacket water outlet temperature exceeds 95°C or jacket water circuit pressure falls below 0.5 bar gauge, the Engine"
    verification: Test
    sil: 2
  SUB-REQ-041:
    text: "The Coolant Circulation Pump SHALL maintain a minimum coolant flow rate of 150 L/min at 0.8 bar differential pressure th"
    verification: Test
    sil: 2
  SUB-REQ-042:
    text: "The Thermostatic Control Valve SHALL modulate bypass coolant flow to maintain jacket water temperature within ±3°C of th"
    verification: Test
    sil: 2
  SUB-REQ-043:
    text: "The Engine Cooling System pressure boundary, including the Engine Jacket Water Circuit, Coolant Circulation Pump, and Ra"
    verification: Analysis
    sil: 2
  SUB-REQ-044:
    text: "The Fuel Oil System SHALL supply diesel fuel to the engine injection system at a pressure of 0.3 bar to 0.7 bar gauge an"
    verification: Test
    sil: 2
  SUB-REQ-045:
    text: "The Bulk Storage Tank SHALL maintain a minimum fuel inventory of 110% of the 7-day fuel demand at 100% rated load as spe"
    verification: Inspection
    sil: 2
  SUB-REQ-046:
    text: "The Day Tank SHALL maintain a working inventory of not less than 4 hours of fuel at rated engine load to provide autonom"
    verification: Test
    sil: 2
  SUB-REQ-047:
    text: "The Fuel Oil Strainer and Filter Assembly SHALL maintain fuel particle contamination downstream of the filter element at"
    verification: Test
    sil: 2
  SUB-REQ-048:
    text: "When Day Tank level falls below the transfer initiation setpoint, the Fuel Transfer Pump SHALL automatically start and t"
    verification: Demonstration
    sil: 2
  SUB-REQ-049:
    text: "When Day Tank fuel level falls below the engine fuel inlet connection height, the Fuel Oil System SHALL generate a hardw"
    verification: Test
    sil: 2
  SUB-REQ-050:
    text: "The Fuel Oil System bulk storage tank, day tank, pipework, and filter assembly SHALL comply with ATEX Directive 2014/34/"
    verification: Inspection
    sil: 2
  SYS-REQ-001:
    text: "The Emergency Diesel Generator SHALL start and reach rated voltage (6.6kV ±10%) and rated frequency (50Hz ±2%) within 10"
    verification: Test
    sil: 3
  SYS-REQ-002:
    text: "The Emergency Diesel Generator SHALL automatically start upon detection of bus undervoltage below 5.94kV (90% of nominal"
    verification: Test
    sil: 3
  SYS-REQ-003:
    text: "The Emergency Diesel Generator SHALL connect safety loads to the emergency bus via a priority-based load sequencer, with"
    verification: Test
    sil: 3
  SYS-REQ-007:
    text: "The Emergency Diesel Generator installation SHALL comprise two independent, redundant trains (Train A and Train B) with "
    verification: Analysis
    sil: 4
  SYS-REQ-008:
    text: "The Emergency Diesel Generator fuel storage system SHALL hold a minimum 7-day fuel inventory at 100% rated load, with au"
    verification: Inspection
    sil: 2
  SYS-REQ-009:
    text: "The Emergency Diesel Generator SHALL remain functional during and after a design basis earthquake of 0.2g peak ground ac"
    verification: Analysis
    sil: 2
  SYS-REQ-010:
    text: "The Emergency Diesel Generator engine SHALL be protected by independent, hardwired trip circuits for overspeed (>115% ra"
    verification: Test
    sil: 2
  SYS-REQ-011:
    text: "The Emergency Diesel Generator building SHALL incorporate automatic fire detection and suppression to extinguish diesel "
    verification: Test
    sil: 2
  SYS-REQ-012:
    text: "The Emergency Diesel Generator safety-related control and protection systems SHALL be isolated from non-safety networks,"
    verification: Analysis
    sil: 3
  SYS-REQ-014:
    text: "When one EDG train is inoperable, the remaining train SHALL be capable of supplying 100% of the safety-critical electric"
    verification: Analysis
    sil: 3
  SYS-REQ-015:
    text: "The Emergency Diesel Generator system SHALL provide a diverse alternate AC power source connection point, capable of acc"
    verification: Demonstration
    sil: 4
  VER-REQ-002:
    text: "The Engine Protection Relay Package functional test SHALL confirm each trip relay (overspeed at 865 rpm, high coolant te"
    verification: Test
    sil: 3
  VER-REQ-003:
    text: "The Diesel Engine Assembly protection trip test SHALL confirm engine standstill (crankshaft speed below 5 rpm) within 5 "
    verification: Test
    sil: 3
  VER-REQ-005:
    text: "The Starting Air System interface test SHALL confirm air start distributor inlet pressure of 25–30 bar at start signal i"
    verification: Test
    sil: 3
  VER-REQ-006:
    text: "The end-to-end EDG start chain acceptance test SHALL confirm bus undervoltage detection within 100 ms, rated voltage and"
    verification: Test
    sil: 3
  VER-REQ-018:
    text: "Verify SUB-REQ-019: I&C LOOP detection acceptance test SHALL apply a simulated bus undervoltage to the Qualified I/O Mod"
    verification: Test
    sil: 3
  VER-REQ-019:
    text: "Verify SUB-REQ-020: Engine and Generator Protection Logic functional test SHALL inject simulated overspeed, low oil pres"
    verification: Test
    sil: 3
  VER-REQ-020:
    text: "Verify SUB-REQ-023: I&C self-diagnostic safe-state test SHALL inject a simulated SIL 3 logic self-fault and confirm de-e"
    verification: Test
    sil: 3
  VER-REQ-023:
    text: "Verify SUB-REQ-024: The Bus Undervoltage Sensing Relay factory acceptance test SHALL inject a simulated 4.5kV signal (su"
    verification: Test
    sil: 3
  VER-REQ-024:
    text: "Verify SUB-REQ-026: The Synchronising Check Relay acceptance test SHALL inject voltage, frequency, and phase angle combi"
    verification: Test
    sil: 3
  VER-REQ-025:
    text: "Verify IFC-REQ-016: Integration test SHALL measure cable loop resistance on the BUVR-to-GCB start circuit at commissioni"
    verification: Test
    sil: 3
  VER-REQ-026:
    text: "Verify IFC-REQ-018: The trip circuit commissioning test SHALL measure total trip circuit resistance and confirm it does "
    verification: Test
    sil: 3
  VER-REQ-027:
    text: "Verify IFC-REQ-017: The Synchronising Check Relay to GCB close-permission interface acceptance test SHALL confirm close "
    verification: Test
    sil: 3
  VER-REQ-040:
    text: "Verify SUB-REQ-030: Perform seismic analysis of the Category 1 Building Structure in accordance with BS EN 1998-1 (Euroc"
    verification: Analysis
    sil: 2
  VER-REQ-047:
    text: "Verify IFC-REQ-022: Coolant Circulation Pump performance test at 25%, 50%, 75%, 100%, and 110% rated engine load. Pass c"
    verification: Test
    sil: 2
  VER-REQ-055:
    text: "Verify IFC-REQ-023: Pre-heat system functional test during AC blackout simulation. Procedure: disconnect normal AC suppl"
    verification: Demonstration
    sil: 2
  VER-REQ-056:
    text: "Verify IFC-REQ-024: Thermostatic valve response time and flow characteristic test. Apply 10°C step change from 72°C to 8"
    verification: Test
    sil: 2
  VER-REQ-057:
    text: "Verify IFC-REQ-025: Engine Cooling to I&C signal interface inspection and functional test. Perform cable routing inspect"
    verification: Test
    sil: 2
  VER-REQ-058:
    text: "Verify SUB-REQ-037 and SUB-REQ-039: Endurance test at 110% rated load, 35°C ambient, for 4 hours minimum. Pass criterion"
    verification: Test
    sil: 2
  VER-REQ-059:
    text: "Verify IFC-REQ-026: Fuel Transfer Pump commissioning test. Simulate low Day Tank level (float switch activation), confir"
    verification: Test
    sil: 2
  VER-REQ-060:
    text: "Verify IFC-REQ-027 and SUB-REQ-044: Fuel system endurance and temperature test. Run engine at 100% rated load for 2 hour"
    verification: Test
    sil: 2
  VER-REQ-061:
    text: "Verify IFC-REQ-028 and SUB-REQ-047: Fuel filter differential pressure test. Introduce controlled particulate loading to "
    verification: Test
    sil: 2