← All reports
PDF Excel ReqIF

Pharmaceutical Manufacturing Line

Verification Plan (SVP) — ISO/IEC/IEEE 15289 — Plan | IEEE 29148 §6.6
Generated 2026-03-27 — UHT Journal / universalhex.org

116
Verification Entries
155
Verification Links
26
Orphans

Verification Requirements (VER)

RefRequirementMethodTags
VER-108 Verify SUB-REQ-063: During factory acceptance testing, operate the HVAC Air Handling Unit at nominal setpoints for 2 hours and record temperature, RH, and ACH at six measurement points across the ISO 7 cleanroom bay. Pass criterion: all six locations within 20±2°C, 45±5% RH, and minimum 20 ACH continuously for 60 minutes.
Rationale: FAT under controlled factory conditions allows verification of HVAC performance against cleanroom specification before GMP facility installation. Six measurement points ensure spatial uniformity is confirmed, not just average values.
Test verification, containment, hvac, session-548, idempotency:ver-sub-063-hvac-conditions-548
VER-109 Verify SUB-REQ-065: In a qualified test environment, simulate containment integrity failure by reducing isolator pressure above -5 Pa for 6 seconds. Measure time from PLC fault detection to confirmation of: HVAC 100% exhaust mode, supply dampers sealed, and Level 1 alarm triggered. Pass criterion: all three responses achieved within 30 seconds.
Rationale: Safe state transition test is the primary SIL-2 verification method per IEC 61508-4 Section 7.4. The test must be executed with the actual safety PLC and HVAC hardware under worst-case conditions (highest process load) to be valid for the safety case.
Test verification, containment, safe-state, sil-2, session-548, idempotency:ver-sub-065-safe-state-548
VER-110 Verify IFC-021: Generate an environmental alarm event in the EMS test environment and measure end-to-end latency from alarm trigger to receipt of OPC UA message in the MES EBR engine. Verify alarm record includes timestamp, severity, and audit trail entry per 21 CFR Part 11. Pass criterion: latency less than 10 seconds across 20 consecutive trials with no failed transmissions.
Rationale: Integration test at the EMS-MES boundary is the minimum viable verification for a GxP data interface. Twenty consecutive trials at production load provides statistical confidence that the interface meets the 10-second latency requirement under realistic EMS polling cycles.
Test verification, containment, ems, mes, interface, session-548, idempotency:ver-ifc-021-ems-mes-548
VER-111 Verify IFC-022: Interrupt the 24 VDC hardwired signal bus between the Containment Safety PLC and the HVAC Air Handling Unit by disconnecting the emergency exhaust command signal. Measure time to HVAC exhaust mode activation. Pass criterion: HVAC switches to exhaust mode within 100 ms of signal interruption (open-circuit = fail-safe).
Rationale: Fail-safe open-circuit behaviour is a SIL-2 architectural requirement per IEC 61508. The hardwired channel cannot be verified by software simulation alone; physical disconnection testing is required to confirm the fail-safe direction and timing for the safety case.
Test verification, containment, safety-plc, hvac, sil-2, interface, session-548, idempotency:ver-ifc-022-safetyplc-hvac-548
VER-112 Verify end-to-end containment response chain: introduce a simulated OEB 4 API dust release at the Potent Compound Isolator exhaust port and measure the sequence from airborne concentration exceeding 80% OEL (detected by API monitor) through Safety PLC fault response to HVAC exhaust mode activation and EMS alarm embedding in MES EBR. Pass criterion: complete chain within 30 seconds, EBR entry created with alarm timestamp.
Rationale: End-to-end system integration test validates the SIL-2 safety chain from sensor detection through logic to actuator response and data recording, as required by IEC 61508 Section 7.4 for functional safety verification. This test cannot be replaced by individual component tests because it verifies the timing of the complete chain under realistic conditions.
Test verification, containment, e2e, integration, sil-2, session-548, idempotency:ver-cec-e2e-integration-548
VER-113 Verify IFC-023: Connect a calibrated position sensor to a HVAC VAV damper actuator. Command position changes via the Differential Pressure Monitoring Controller at 1-second intervals. Verify PID closed-loop response updates within 1 second and position feedback remains within 5% of commanded value. Inject a blocked actuator fault; verify alarm within 10 seconds. Pass criterion: all 20 command cycles within 1s, zero false positives.
Rationale: IFC-023 specifies 1-second PID update cycle and 5% position tolerance. The PID response test must be performed at the physical actuator interface to confirm that the analogue 4-20 mA control loop achieves the specified accuracy under realistic HVAC load conditions.
Test verification, containment, dp-controller, hvac, interface, session-548, idempotency:ver-ifc-023-dp-hvac-548
VER-114 Verify SUB-REQ-064: Disturb cleanroom pressure by propping a pass-through door open for 10 seconds during operational conditions. Measure time for Differential Pressure Monitoring Controller to restore: +10 Pa between ISO 7 cleanroom and corridor, and -12.5 Pa inside Potent Compound Isolator. Pass criterion: both setpoints restored within 30 seconds, no pressure undershoot below -15 Pa in isolator.
Rationale: Pressure cascade setpoint recovery under door-disturbance is the worst-case realistic test for HVAC PID response in a pharmaceutical cleanroom. The 30-second recovery criterion is the same as the containment safe state transition budget, ensuring the HVAC can restore containment before the safety PLC would trip.
Test verification, containment, pressure-cascade, sil-2, session-548, idempotency:ver-sub-064-pressure-cascade-548
VER-REQ-001 The verification activity for SUB-REQ-003 SHALL inject a pre-characterised reference standard tablet spectrum into the PAT DAC Workstation and confirm that CQA model evaluation completes and returns a pass/fail classification within the specified 30-second sample interval cycle.
Rationale: SIL-3 H-004 safety function: CQA model latency directly determines how many OOS tablets pass before the diversion valve responds. The 2-second criterion bounds the number of tablets at risk between sensor acquisition and valve actuation at 60 RPM press speed (approximately 4 tablets per second) to fewer than 8 tablets, which is within the divertible buffer volume.
Test reqs-eng-session-555
VER-REQ-002 The verification activity for SUB-REQ-004 SHALL apply a CQA limit-exceedance command to the Diversion Valve Assembly pneumatic solenoid at operating pressure (5-7 bar) and confirm that valve position transitions from accept to reject within 2 seconds as measured by dual limit switch feedback across 10 test actuations.
Rationale: SIL-3 H-004 safe state: the valve must reach the reject position before the next tablet reaches the accept stream. At 60 RPM press speed, tablets exit at 1-second intervals; 500ms actuation leaves a 500ms margin. The spring-return test verifies fail-safe behaviour — the hardware safety function independent of software.
Test reqs-eng-session-555
VER-REQ-003 The verification activity for SUB-REQ-005 SHALL inject a degraded NIR reference spectrum (SNR reduced by 50% via attenuation filter) into the PAT subsystem and confirm that the sensor diagnostic algorithm detects the degradation within 15 seconds and generates a sensor health alert to the DAC Workstation.
Rationale: SIL-3 H-004: sensor degradation that is not detected means CQA model predictions are based on corrupted spectra, potentially releasing OOS product without triggering diversion. The 15-second detection window allows one to two press rotations before the operator is notified to switch to manual sampling mode.
Test reqs-eng-session-555
VER-REQ-004 The verification activity for IFC-REQ-001 SHALL inject 100 consecutive simulated CQA limit-exceedance events at the PAT DAC Workstation OPC-UA server, measure the alarm transit time to confirmed receipt at the MES OPC-UA client, and confirm that all 100 events arrive within 500 ms with zero loss.
Rationale: SIL-3 H-004 interface criticality: the CQA alarm is the trigger for MES to confirm diversion and lock the batch record. If the alarm is lost or delayed beyond 500ms, OOS product may enter the accept stream. The 1000-event soak test detects intermittent OPC-UA subscription failures that may not appear in short tests.
Test reqs-eng-session-555
VER-REQ-005 The verification activity for IFC-REQ-003 SHALL measure, following receipt of a CQA alarm from the PAT subsystem, the elapsed time for the MES to transmit a diversion acknowledgment and operator disposition to the PAT DAC Workstation, and confirm transmission completes within the specified interface latency for 20 consecutive alarm events.
Rationale: SIL-3 H-004 interface: the acknowledgment confirms to the PAT system that the MES has registered the diversion event and locked the relevant batch record segment. Without this confirmation, the PAT system cannot determine whether a second CQA exceedance is a new event or a duplicate of the unacknowledged prior alarm.
Test reqs-eng-session-555
VER-REQ-006 The verification activity for SUB-REQ-008 SHALL attempt to execute each of the five 21 CFR Part 11 critical EBR actions (batch initiation, exception handling, parameter override, batch release, deviation closure) without providing valid electronic credentials, and confirm that the MES rejects all five attempts without committing any record.
Rationale: SIL-2 H-006 data integrity: unsigned EBR entries are inadmissible as evidence in FDA inspection and can result in consent decree or product recall. The 100% rejection criterion is absolute — no partial authentication tolerance exists under 21 CFR Part 11.50.
Test reqs-eng-session-555
VER-REQ-007 The verification activity for SUB-REQ-011 SHALL apply a maintenance lock to the rotary tablet press entry in the MES LOTO registry and confirm that subsequent equipment restart commands issued via operator HMI and programmatic API are both rejected with an interlock alarm until the lock is formally removed.
Rationale: SIL-2 H-007 mechanical entrapment: the LOTO restart prevention is the primary software barrier preventing a maintenance technician from being caught in moving equipment. The test must exercise the OPC-UA programmatic path — not only the HMI path — because PLC restart commands may bypass the HMI in some process recovery sequences.
Test reqs-eng-session-555
VER-REQ-008 The verification activity for SUB-REQ-010 SHALL write 500 sequential EBR entries via the MES API, run the hash chain integrity verification job, confirm no discontinuities, then modify one mid-chain record directly and confirm the MES detects the discontinuity and generates an integrity alert within 60 seconds.
Rationale: SIL-2 H-006: the SHA-256 hash chain is the technical control proving EBR entries have not been altered post-signature. The tamper detection test must use direct database manipulation rather than API manipulation because 21 CFR Part 11 treats database-level tampering as the primary threat model for electronic records.
Test reqs-eng-session-555
VER-REQ-009 The verification activity for the end-to-end PAT-to-diversion chain SHALL measure total latency from spectrum injection at the NIR spectrometer through CQA model evaluation, OPC-UA alarm to MES, MES diversion acknowledgment, and Diversion Valve Assembly confirmed actuation, and confirm the cumulative chain latency is within the SIL-3 H-004 limit for 5 consecutive test runs.
Rationale: The end-to-end test is the definitive SIL-3 H-004 safety case evidence. Individual component tests confirm subsystem compliance but do not demonstrate that the chain functions correctly under realistic load conditions. The 3-second total budget combines the 2-second model evaluation bound plus 500ms alarm transmission plus 500ms valve actuation margin.
Test reqs-eng-session-555
VER-REQ-010 The verification activity for SUB-REQ-002 SHALL scan a certified reference material (polystyrene NIST SRM 1921b) using the Raman spectrometer and confirm that the instrument acquires a full spectrum covering the 200–3200 cm-1 range with spectral resolution ≤4 cm-1 at the 30-second specified interval.
Rationale: Raman spectrometer performance verification confirms the instrument meets specification for blend uniformity monitoring. NIST-traceable reference materials provide measurement traceability required for GxP instrument qualification (IQ/OQ).
Test reqs-eng-session-555
VER-REQ-011 The verification activity for SUB-REQ-007 SHALL measure a certified glass bead reference standard (NIST SRM 1018c, D50 = 57 µm ±3%) using the laser diffraction analyser with dry dispersion at 0.5 bar, and confirm the measured D10/D50/D90 values are within the certified tolerance band in 5 consecutive measurements.
Rationale: Laser diffraction qualification confirms the instrument meets specification for granulation endpoint monitoring. D50 accuracy within 5% is the ICH Q8 acceptance criterion for particle size measurement in granulation development; repeatability RSD <2% meets GAMP 5 Category 3 instrument qualification requirements.
Test reqs-eng-session-555
VER-REQ-012 The verification activity for SUB-REQ-015 SHALL simulate an EBR data integrity failure by injecting a hash chain discontinuity and confirm that the MES transitions operators to paper-backup recording mode within 30 minutes, that paper backup records are available to operators within 5 minutes of the alert, and that recovery to electronic recording is possible from the last verified backup.
Rationale: SIL-2 H-006 safe state: when electronic records cannot be guaranteed tamper-evident, GMP requires a fallback to paper records to maintain the manufacturing record continuity required for batch release. The 30-minute window reflects the EU GMP Annex 11 requirement for backup systems to be available promptly.
Demonstration reqs-eng-session-555
VER-REQ-013 The verification activity for IFC-REQ-006 SHALL connect a calibrated NIR reference spectrometer in parallel with the FBD in-line probe, inject 10 pre-characterised reference spectra spanning the LOD validation range (0.5% to 3.5%), and confirm that the LOD values reported via the G&B subsystem interface agree with the reference within the specified tolerance.
Rationale: IFC-REQ-006 specifies maximum 30-second spectral data intervals and 5-second CQA model evaluation latency for the G&B-to-PAT NIR interface. The parallel-reference-spectrometer test method is chosen because it provides independent ground truth for both the data values (via certified reference spectra) and the timing (via synchronized timestamps). If this interface has latency >5 seconds under load, the PAT system receives stale LOD values and may issue false blend-endpoint signals — potentially releasing under-dried granulate with LOD above target into the IBC blender.
Test reqs-eng-session-555
VER-REQ-014 The verification activity for IFC-REQ-007 SHALL trigger a simulated G&B batch start in the MES and measure the elapsed time from MES step initiation signal to PLC setpoint receipt confirmation at the HSG, FBD, and IBC Blender PLCs, confirming all three PLCs acknowledge within the specified interface response time.
Rationale: Integration test to verify MES-to-G&B recipe delivery latency and EBR feedback interval under production load conditions.
Test reqs-eng-session-555
VER-REQ-015 The verification activity for the end-to-end Granulation and Blending cycle SHALL load a validated product recipe into the MES, execute one complete G&B cycle from API powder charge to IBC seal, and confirm granulation endpoint, drying LOD within specification, sized granule D90 ≤ 1 mm, blend RSD ≤ 5.0% across stratified samples, and complete MES batch record with all IPC entries.
Rationale: End-to-end integration test verifying the complete G&B process train produces granules meeting all CQA specifications under recipe control. This test is the minimum viable verification for GMP process validation (PV Stage 2) sign-off of the G&B subsystem.
Test reqs-eng-session-555
VER-REQ-016 The verification activity for IFC-REQ-008 SHALL complete a G&B cycle producing a sealed IBC, inspect the tamper-evident seal, and confirm that the MES batch genealogy record contains the IBC mass, blend authorisation code, and lot number linking the IBC to its input raw material charges.
Rationale: IBC handoff integrity is verified by inspection of the seal and genealogy record, with a negative test (blocked press start) confirming the MES access control. This matches the regulatory requirement for documented batch record evidence (21 CFR 211.182).
Inspection reqs-eng-session-555
VER-REQ-017 The verification activity for IFC-REQ-002 SHALL inject an NIR reference degradation (40% signal attenuation) while the PAT subsystem is in nominal operation, and confirm that the MES receives an OPC UA sensor health update indicating degraded status within 10 seconds of the attenuation event.
Rationale: IFC-REQ-002 is the primary early-warning signal for the PAT-MES CQA diversion path. Verification requires injecting a controlled degradation to confirm the OPC UA publish cycle, field completeness, and state machine transition. Failure to verify this interface could allow undetected sensor drift to produce undetected quality deviations in product.
Test reqs-eng-session-555
VER-REQ-018 The verification activity for IFC-REQ-004 SHALL log MES CQA data receipt timestamps against PAT OPC UA publish timestamps during a simulated production run, inject a known OOS API concentration sample, and confirm the diversion decision is transmitted to the MES within the specified interface latency.
Rationale: IFC-REQ-004 is the real-time CQA measurement stream that drives diversion decisions. End-to-end latency of the MES OPC UA subscription must be verified under live production protocol to confirm diversion is triggered within the 2-second hard limit before non-conforming material passes the diversion valve. This is the safety-critical data path for batch release.
Test reqs-eng-session-555
VER-REQ-019 The verification activity for SUB-REQ-009 SHALL attempt to modify a completed EBR field via direct database access and via the MES UI, and confirm in both cases that the hash chain invalidation is detected and a tamper alert is generated within 60 seconds without the modification being accepted.
Rationale: SUB-REQ-009 implements the 21 CFR Part 11 (Electronic Records; Electronic Signatures) requirement for tamper-evident records. This is a regulatory compliance test: FDA expects evidence that the hash chain integrity mechanism actually detects record modification. Pass/fail determines whether the batch release system meets 21 CFR Part 11 Subpart B Section 11.10(e) audit trail requirements.
Test reqs-eng-session-555
VER-REQ-020 The verification activity for SUB-REQ-020 SHALL complete a validation blending run using placebo granules with tracer API equivalent, collect 10 stratified samples from IBC discharge points after blend-endpoint indication, and confirm that API content RSD across all samples is ≤5.0%.
Rationale: SUB-REQ-020 sets the blend uniformity acceptance criterion for IBC blending. ICH Q2(R1) (Validation of Analytical Procedures: Text and Methodology) requires offline HPLC confirmation of the NIR endpoint model during process validation. The 10-sample stratified plan is the minimum statistical design that detects a pattern-based segregation within the IBC at 95% confidence. Failure of this test would require revalidation of the blend process.
Test reqs-eng-session-555
VER-REQ-021 The verification activity for SUB-REQ-001 SHALL configure the NIR spectrometer for the 900–1700 nm range with 256-channel resolution, record 100 consecutive spectra during a simulated production run, and confirm all spectra are acquired at the 30-second interval with signal-to-noise ratio meeting the diagnostic acceptance criterion.
Rationale: SUB-REQ-001 defines the minimum spectral parameters of the NIR spectrometer as the primary CQA sensor. Verification of spectral range and channel count ensures the PLS chemometric model built for this instrument remains valid under the as-deployed configuration. A failure here would require re-validation of the entire NIR calibration model before the instrument can be used for batch release decisions.
Test reqs-eng-session-555
VER-REQ-022 The verification activity for IFC-REQ-009 SHALL trigger a PAT degraded-mode transition by disabling the NIR sensor in a simulated production environment, measure the elapsed time from mode transition to MES command receipt at the PAT subsystem, confirm continuity of CQA monitoring on the remaining active sensor channels throughout the transition, and verify that the MES manual sampling schedule command is issued within 30 seconds of degradation detection. Pass criterion: (a) MES degraded-mode command received by PAT subsystem within 30 seconds; (b) ≥1 CQA evaluation completed on each remaining active channel during the transition interval; (c) manual sampling schedule issued with 15-minute interval and sample point specification.
Rationale: IFC-REQ-009 adds quantified performance thresholds to the degraded mode MES-PAT protocol. The 30-second MES command delivery window and CQA monitoring continuity criteria are the testable acceptance criteria for the degraded mode qualification test. Explicit pass criteria required per IEC 61508 (Functional safety of E/E/PE safety-related systems) for SIL-rated interface verification — binary pass/fail must be demonstrable. Updated per validation session 566 to resolve ambiguousReqs blocker.
Test reqs-eng-session-555
VER-REQ-023 The verification activity for SUB-REQ-024 SHALL induce degradation on one NIR sensor channel, measure the elapsed time from the first degraded spectrum to suspension of CQA model evaluation on that channel, and confirm that the remaining two channels continue model evaluation throughout the suspension period. Pass criterion: suspension of the degraded channel occurs within 5 seconds of first degraded spectrum; unaffected channels maintain ≥1 CQA model evaluation per 30-second cycle throughout the test; minimum CQA throughput on remaining channels is ≥70% of nominal three-channel throughput.
Rationale: SUB-REQ-024 quantifies response times and channel-failure thresholds for the PAT degraded-mode protocol. The 5-second suspension window and ≥70% CQA throughput retention on remaining channels are the minimum performance criteria required to assure product quality surveillance is maintained during single-channel failure. Explicit pass criteria are required so the test result is binary and auditable per EU GMP Annex 11.
Test reqs-eng-session-555
VER-REQ-024 The verification activity for SUB-REQ-027 SHALL open a guard door on the Rotary Tablet Press while the press is operating at nominal speed (60 RPM), and confirm that: (a) the main drive de-energises within 200ms of guard opening as measured by current-clamp on the drive power supply; (b) the turret braking system brings turret speed to zero within 3 seconds; and (c) the MES LOTO registry logs the guard-open event with timestamp accurate to 1 second. Test shall be repeated 5 times. Pass criterion: all 5 trials meet both timing thresholds.
Rationale: EN ISO 13849-1 (Safety of machinery: Safety-related parts of control systems) Category 3 guard interlock requires Test verification with measured response times. The 200ms and 3-second thresholds derive from the maximum kinetic energy of the turret at 60 RPM and the stopping distance required to prevent punch-tip contact with an intruding hand.
Test session-556, idempotency:ver-sub027-tc-loto-556
VER-REQ-025 The verification activity for SUB-REQ-028 SHALL install a calibrated differential pressure transmitter at the Tablet Compression Containment Housing during press operation at 120 RPM, and confirm that: (a) steady-state differential pressure is maintained at -15 Pa ± 5 Pa relative to the adjacent room; (b) when a 10mm gap is simulated at the transfer sleeve, an alarm is generated within 10 seconds; and (c) the HVAC switches to 100% exhaust within 30 seconds of alarm confirmation. Pass criterion: all acceptance values met across 3 measurement cycles.
Rationale: The -15 Pa containment threshold is derived from OEL 0.5 µg/m³ containment modelling per ISPE Good Practice Guide for Pharmaceutical Equipment Containment. Test verification is required because containment performance depends on actual airflow dynamics that cannot be confirmed by inspection or analysis alone.
Test session-556, idempotency:ver-sub028-tc-containment-556
VER-REQ-026 The verification activity for IFC-REQ-010 SHALL run the rotary tablet press at 120 RPM with every-30th-tablet auto-sampling enabled, use OPC-UA monitoring software to log the IPC data stream for 30 minutes, and confirm: (a) message delivery rate ≥99.5% (measured as received messages / expected messages at 2 Hz sampling × 1800 s); (b) maximum single-message latency ≤500ms; (c) all tablet weight, hardness, and thickness values are present in each message with no null fields. Pass criterion: all three acceptance criteria met across the full 30-minute run.
Rationale: The 99.5% delivery rate and 500ms latency limits are derived from the in-process control response time required to detect and reject out-of-specification tablets before more than 2 tablets beyond the detected outlier pass the rejection point. Test verification is mandatory because OPC-UA message delivery performance depends on actual network configuration and cannot be demonstrated by inspection.
Test session-556, idempotency:ver-ifc010-tc-pat-556
VER-REQ-027 The verification activity for IFC-REQ-011 SHALL inject 50 deliberate rejection events (by commanding out-of-band force values to the IPC at 10 events/minute) and 5 operational state transitions (normal → degraded → normal → emergency stop → normal) via the test harness, and confirm: (a) each rejection event generates a corresponding rejection command to the tablet reject mechanism within 200ms; (b) each state transition event is received and displayed in the MES within 2 seconds; (c) all 55 events are recorded in the EBR with correct timestamps and event types. Pass criterion: 100% event receipt with zero dropped events and all timing thresholds met.
Rationale: Zero-drop event delivery is required for 21 CFR Part 11 (Electronic Records; Electronic Signatures) EBR completeness — any dropped rejection event could result in a non-conforming tablet escaping to the batch. The 200ms rejection response limit is derived from tablet press throughput: at 120 RPM × 60 stations, tablets exit at 120/s, so a 200ms window allows at most 24 tablets to pass the reject point after a defect is detected.
Test session-556, idempotency:ver-ifc011-tc-mes-556
VER-REQ-028 The verification activity for IFC-REQ-012 SHALL execute a simulated film coating batch cycle, logging all coating parameters (pan speed, inlet temperature, spray rate, atomisation pressure, weight gain) to the MES EBR and confirming that each parameter write completes within 60 seconds of measurement, with end-to-end data integrity confirmed by LIMS audit trail review.
Rationale: IFC-REQ-012 requires 30-second update intervals and 60-second EBR write completion. This test validates both timing constraints under representative production load conditions, confirming that the Film Coating Subsystem to MES data channel meets GMP EBR completeness and timeliness requirements.
Test session-558, qc, ver, film-coating, mes, idempotency:ver-028-ifc-012-v1
VER-REQ-029 The verification activity for IFC-REQ-013 SHALL present the Film Coating Subsystem with a compression-to-coating transfer IBC containing a complete signed transfer record, confirm the subsystem accepts the transfer and commences the coating cycle, then repeat with a second IBC containing a deliberately out-of-specification core hardness value and confirm the subsystem rejects the transfer and raises an MES alert within 30 seconds.
Rationale: IFC-REQ-013 requires a hard reject gate at the coating subsystem boundary for out-of-specification core attributes. The pass/reject test pair validates both the acceptance and rejection paths, confirming that the inter-subsystem transfer control prevents quality-compromised material from entering the coating operation.
Test session-558, qc, ver, tablet-compression, film-coating, idempotency:ver-029-ifc-013-v1
VER-REQ-030 The verification activity for IFC-REQ-014 SHALL complete a packaging line run of 1,000 serialised units, confirm 100% serial number reconciliation against the MES batch record within 5 minutes of line clearance, then simulate a line run without a valid ERP production order and confirm the MES blocks packaging start.
Rationale: IFC-REQ-014 requires 100% serial number reconciliation within 5 minutes and MES block without production order. The 1,000-unit run provides a statistically representative sample for serialisation throughput. The production-order-absent negative test confirms the GMP authority control at packaging.
Test session-558, qc, ver, packaging, mes, idempotency:ver-030-ifc-014-v1
VER-REQ-031 The verification activity for IFC-REQ-015 SHALL present the Packaging Subsystem with a film-to-packaging transfer IBC accompanied by a complete in-process release record showing all CQA attributes within specification, confirm packaging start is permitted; then repeat with a release record containing a deliberate out-of-specification coating weight gain result and confirm the Packaging Subsystem blocks line start and notifies the MES within 30 seconds.
Rationale: IFC-REQ-015 requires a hard interlock preventing packaging without a valid release record. The dual-path test (compliant/non-compliant transfer) validates both the acceptance and blocking logic, confirming that the packaging subsystem cannot process tablets that fail coating CQA release criteria.
Test session-558, qc, ver, film-coating, packaging, idempotency:ver-031-ifc-015-v1
VER-REQ-032 The verification activity for IFC-REQ-016 SHALL confirm that environmental monitoring data (temperature, RH, differential pressure, particle counts) are received in the MES at the required 5-minute intervals during a simulated production shift, then inject a simulated pressure differential exceedance signal and confirm the MES halts the affected manufacturing operation and writes an environmental deviation event to the EBR within 30 seconds.
Rationale: IFC-REQ-016 requires a 30-second MES halt response to environmental exceedances. The timing test is critical for OEB 4/5 containment: a pressure differential loss in a potent compound area is a personnel safety event. The 30-second window must be verified under representative system load conditions to confirm the safety-critical response time is achievable.
Test session-558, qc, ver, containment, mes, idempotency:ver-032-ifc-016-v1
VER-REQ-033 The verification activity for IFC-REQ-017 SHALL complete 20 consecutive dispensing operations with a calibrated balance, confirm each weighing record (material identity, actual weight, operator ID, balance calibration status) is written to the MES EBR within 60 seconds, then simulate a dispensing event with actual weight at +0.6% of target and confirm the MES records a GMP deviation event.
Rationale: IFC-REQ-017 requires 60-second EBR write completion per dispensing event and a GMP deviation for >±0.5% weight deviation. The 20-operation run validates the timing requirement under representative throughput. The deliberate-exceedance test confirms the rejection gate at the GMP deviation threshold.
Test session-558, qc, ver, material-handling, mes, idempotency:ver-033-ifc-017-v1
VER-REQ-034 The verification activity for IFC-REQ-018 SHALL present the Granulation Subsystem charge point with a correctly labelled container barcode and confirm the identity verification scan passes and charge is permitted; then present a container barcode not matching the dispensing record and confirm the subsystem rejects the charge and notifies the MES within 15 seconds.
Rationale: IFC-REQ-018 requires a secondary identity scan at the granulation charge point to enforce the double-verification anti-mix-up protocol. The negative test (mismatched barcode) is the safety-critical path: a false-pass (allowing a wrong material into the granulator) would contaminate the entire batch. The 15-second response window is consistent with the granulation charge sequence timing.
Test session-558, qc, ver, material-handling, granulation, idempotency:ver-034-ifc-018-v1
VER-REQ-035 The verification activity for IFC-REQ-019 SHALL issue a production order from the ERP test system at least 24 hours before a simulated manufacturing start, confirm the MES receives and stages the order correctly, complete a simulated batch cycle, and verify batch yield and material consumption data are returned to ERP within 4 hours of batch completion; then attempt to start manufacturing without a valid ERP production order reference in the EBR header and confirm the MES blocks the operation.
Rationale: IFC-REQ-019 requires 24-hour advance order notification, 4-hour yield return, and an MES block without production order. These three constraints collectively enforce the GMP authority chain from ERP to MES. Each must be independently verified; the timing constraints cannot be inferred from design inspection alone.
Test session-558, qc, ver, erp, mes, idempotency:ver-035-ifc-019-v1
VER-REQ-036 The verification activity for IFC-REQ-020 SHALL generate a batch sample request in the MES, confirm the LIMS receives and registers the request with correct test method and specification reference, return a passing analytical result and confirm the MES receives it within the master test schedule turnaround time; then attempt to advance batch disposition to 'released' with an outstanding LIMS result and confirm the MES blocks disposition.
Rationale: IFC-REQ-020 requires a closed-loop LIMS-MES release workflow with the MES blocking batch disposition until all release results are received. The pass and blocking tests together validate the two critical control points: data completeness (all results received) and data quality (passing verdict required). These cannot be validated by inspection of the interface specification alone.
Test session-558, qc, ver, lims, mes, idempotency:ver-036-ifc-020-v1
VER-REQ-037 The verification activity for SUB-REQ-012 SHALL apply a maintenance lock to a designated piece of equipment via the MES LOTO registry, attempt a restart command (confirming denial), remove the lock, re-attempt restart (confirming success), then attempt a lock override via the maintenance UI and confirm the system denies and logs the override attempt; all six events (lock applied, restart denied, lock removed, restart permitted, override attempted, override denied) SHALL appear in the EBR audit log with correct operator ID, equipment ID, timestamp, and outcome within 10 seconds of each event.
Rationale: SUB-REQ-012 requires complete LOTO event logging covering all four event types. The positive-path (lock and release) tests confirm nominal logging. The override-attempt test is the safety-critical path: a false-permit on an energised machine is an H-007 mechanical entrapment hazard. SIL-2 allocation requires test-method verification, not analysis.
Test session-560, validation, mes, loto, sil-2, h-007, idempotency:session560-ver-037-sub012-loto-logging
VER-REQ-038 The verification activity for SUB-REQ-014 SHALL run the MES EBR database for a simulated 4-hour production period, confirm automated backup events occur at intervals not exceeding 15 minutes by inspecting backup logs with timestamps, verify each backup file hash against the stored integrity hash; then simulate a data integrity failure by corrupting the primary EBR database, initiate restore from the most recent verified backup, and confirm full system functionality is restored within 30 minutes of failure detection, with no EBR data loss beyond the last verified backup interval.
Rationale: SUB-REQ-014 specifies a 15-minute backup interval and 30-minute RTO. These timing requirements protect against H-006 EBR data integrity failure. The 30-minute RTO is the regulatory recovery window before a batch must be quarantined. Neither the backup interval nor the restore time can be verified by analysis of the backup architecture alone; both require measured test execution.
Test session-560, validation, mes, backup, sil-2, h-006, idempotency:session560-ver-038-sub014-ebr-backup
VER-REQ-039 The verification activity for SUB-REQ-016 SHALL execute three consecutive High Shear Granulator runs using a validated placebo formulation with a characterised endpoint torque profile; inject a simulated endpoint signal (torque or NIR wet-mass spectrum at validated criterion) and measure the elapsed time from endpoint signal to granulation stop and Fluid Bed Dryer transfer initiation command, confirming the stop-and-transfer sequence completes within 10 seconds in all three runs; pass criteria: 100% of runs stop within 10 seconds, transfer initiated in all runs, endpoint event logged in EBR with timestamp.
Rationale: SUB-REQ-016 specifies a 10-second stop-and-transfer response at granulation endpoint. Late endpoint response causes over-granulation (too dense granules), producing tablets with hardness outside specification. SIL-2 tagging requires test verification; the 10-second constraint is a real-time control loop timing requirement that cannot be demonstrated by design inspection.
Test session-560, validation, granulation-blending, sil-2, idempotency:session560-ver-039-sub016-hsg-endpoint
VER-REQ-040 The verification activity for SUB-REQ-022 SHALL disable the PAT NIR blend-endpoint monitor (simulate sensor fault) mid-blending cycle, confirm the IBC blender continues for the MES-recipe fixed-time minimum duration (≥20 minutes at validated RPM) without issuing blend-complete, confirm the MES prompts for supervisory authorisation at blend time expiry and blocks blend-complete without the authorisation signature, confirm the authorised signature permits blend-complete, and verify the EBR contains a PAT-unavailable event record with timestamp and reason; then re-enable PAT and confirm normal endpoint monitoring resumes.
Rationale: SUB-REQ-022 is the degraded-mode safety net for H-004: when PAT is unavailable, a fixed-time blend with supervisory gate prevents release of a potentially non-homogeneous batch. The supervisory authorisation gate (the safety-critical control) can only be verified by attempting blend-complete without authorisation and confirming the block. Analysis of the software design cannot substitute for this negative test.
Test session-560, validation, granulation-blending, pat, degraded-mode, sil-2, h-004, idempotency:session560-ver-040-sub022-degraded-blend
VER-REQ-041 The verification activity for SUB-REQ-025 SHALL run the Rotary Tablet Press at nominal speed with instrumented punches and inject 20 deliberate out-of-range force events (±5 kN deviation from setpoint) distributed across 5 tooling stations; confirm each out-of-range tablet is rejected by the pneumatic ejector within 200 ms of ejection-point detection, confirm no in-specification tablet is incorrectly rejected, and confirm all 20 rejection events are logged in the MES batch record; then run 1,000 tablets within specification and confirm zero false rejections; pass criteria: 100% sensitivity and 100% specificity on rejection gate.
Rationale: SUB-REQ-025 specifies a 200 ms ejection response and a ±5 kN force gate protecting product quality (H-004). A missed rejection (false negative) releases an OOS tablet; a false acceptance of a false rejection could cause a recall if it becomes systematic. The 200 ms timing requirement cannot be verified by inspection of the ejector actuator specification. Both sensitivity and specificity require physical test execution.
Test session-560, validation, tablet-compression, sil-2, idempotency:session560-ver-041-sub025-press-force-rejection
VER-REQ-042 The verification activity for SUB-REQ-029 SHALL set the compression count on one punch station RFID tag to 499,999 in the test environment, cycle the press through one compression, and confirm the station count increments to 500,000 and the press halts with an RFID lifecycle limit event logged to the MES batch record; then present the press with one RFID tag read failure (tag disabled) and confirm the press does not start, the failed station is identified in the MES log, and the operator is prompted to replace the tooling station before restart; pass criteria: press halted on lifecycle limit, failed read blocks start.
Rationale: SUB-REQ-029 protects against tooling fatigue fracture (a broken punch tip contaminating tablets with metal fragments — an H-007 and product quality risk). The lifecycle limit gate and the read-failure block are the two safety controls. Both require physical test execution with instrumented RFID state because wear accumulation and tag fault simulation cannot be analytically verified against the subsystem implementation.
Test session-560, validation, tablet-compression, rfid, h-007, idempotency:session560-ver-042-sub029-rfid-tooling
VER-REQ-043 The verification activity for SUB-REQ-030 SHALL disable one of the three IPC measurement channels (weight, hardness, or thickness) while the press is running at nominal speed, confirm the press automatically reduces throughput to ≤60% of nominal RPM, confirm the MES displays a degraded-mode alert and begins prompting manual sample collection at 5-minute intervals, confirm the degraded-mode start time and failed channel are recorded in the MES batch record; then restore the failed channel and confirm the press returns to nominal throughput and MES reverts to automated IPC mode with no operator intervention required; repeat for each of the three channels.
Rationale: SUB-REQ-030 defines the tablet compression degraded-mode safe-state (reduced speed, manual sampling) that maintains product quality when one IPC channel fails. The 60% throughput limit prevents tablet production rate from outpacing manual sampling capacity. This is a real-time control response that cannot be verified by simulation analysis; all three channel failure modes must be physically induced to confirm the subsystem correctly identifies and responds to each.
Test session-560, validation, tablet-compression, degraded-mode, idempotency:session560-ver-043-sub030-ipc-degraded
VER-REQ-044 The verification activity for SYS-REQ-005 SHALL actuate the emergency stop function via operator E-stop button, automatic interlock, and software-initiated stop command in three separate test runs; measure elapsed time from trigger to de-energisation of all drive systems (pass: ≤3 s), closure of all product-transfer valves (pass: ≤5 s), and confirmed equipment standstill (pass: ≤10 s) using calibrated high-speed timers and actuator position feedback; all three activation paths must meet timing criteria in 3 consecutive runs per path.
Rationale: SYS-REQ-005 is the system-level emergency stop safety function covering H-001 (containment breach), H-003 (dust explosion), and H-007 (mechanical entrapment). The three timing thresholds (3/5/10 s) are safety case evidence required by IEC 61508 (Functional safety of E/E/PE safety-related systems) for SIL-2 allocation. Individual subsystem stop tests (VER-REQ-024 covers press guard interlock) do not demonstrate the system-wide coordinated stop of all drives and valves in the correct sequence. This test is the definitive system-level E-stop qualification evidence.
Test session-561, validation, estop, sil-2, h-001, h-003, h-007, system-level, idempotency:session561-ver-sys005-estop-system-level
VER-REQ-045 The verification activity for SYS-REQ-006 SHALL inject simulated parameter exceedances (differential pressure exceedance, temperature exceedance, humidity exceedance) sequentially in a qualified production environment and confirm: (a) MES alarm generated within 60 seconds of alert limit breach for each parameter; (b) MES-initiated production halt within 120 seconds of action limit breach; (c) each exceedance event recorded in the EBR with timestamp, parameter identity, actual value, and limit reference; test three parameter types, three consecutive runs per type, all nine runs must meet timing criteria.
Rationale: SYS-REQ-006 specifies system-level 60-second alarm and 120-second halt response times for cleanroom environmental exceedances. H-005 (loss of cleanroom environmental control causing microbial contamination) is SIL-1. VER-REQ-032 tests only the IFC-REQ-016 pressure-differential interface; it does not verify the system-level temperature and humidity exceedance response times, nor confirm 100% EBR recording across all three environmental parameters. This system-level test is required for EU GMP Annex 1 environmental monitoring qualification and site inspection evidence.
Test session-561, validation, cleanroom, sil-1, h-005, system-level, envmon, idempotency:session561-ver-sys006-cleanroom-system-level
VER-REQ-046 The verification activity for SYS-REQ-008 SHALL execute one complete product changeover sequence (cytotoxic to standard product) with a qualified operator: complete three-wash cleaning cycle guided by MES workflow, collect swab samples at all 15 predefined worst-case locations and rinse water samples, confirm MES prevents production start until all cleaning steps are electronically signed, confirm swab HPLC and TOC results are below acceptance limits, confirm MES blocks next batch record initiation until all cleaning verification signatures are complete; total elapsed time from cleaning start to MES release logged in EBR.
Rationale: SYS-REQ-008 is SIL-3 (H-002 cross-contamination) requiring changeover cleaning to be verified with quantitative HPLC and TOC acceptance limits. IEC 61508 (Functional safety of E/E/PE safety-related systems) SIL-3 mandates Test verification — Demonstration is insufficient because it cannot inject a deliberate OOS swab failure to confirm the MES blocks production restart. The Test method requires: (a) a passing run confirming normal changeover workflow, (b) a forced OOS swab injection at location 7 (worst-case hopper weld seam) to confirm MES blocks next batch initiation, (c) pass criterion: TOC ≤500µg/L and swab residue ≤0.004µg/cm² at all 15 locations, with MES batch initiation blocked until all electronic signatures complete.
Test session-561, validation, changeover, cleaning, sil-3, h-002, system-level, idempotency:session561-ver-sys008-changeover-system-level
VER-REQ-047 The verification activity for SUB-REQ-031 SHALL deploy a primary DAC Workstation and a configured hot-standby instance in a test environment, inject a simulated primary node failure, and confirm that: (a) the standby instance assumes primary control within 5 seconds as measured by timestamp of first CQA model output from standby; (b) the last CQA diversion state held by the primary is replicated to the standby without loss; (c) the diversion valve remains in its last commanded state throughout the transition; and (d) the test is repeated 3 times to confirm repeatability. Pass criterion: all 3 trials meet the ≤5 second switchover threshold with zero diversion state loss.
Rationale: IEC 61508 (Functional safety of E/E/PE safety-related systems) SIL-3 requires Test verification (not Analysis alone) for hardware fault tolerance claims. Analysis alone cannot demonstrate that the actual hardware/software implementation achieves HFT=1 — only a live failover test with timing measurements can. This VER resolves the silWithoutVer quality gate blocker and directly validates the hazard H-004 mitigation for OOS product release.
Test session-562, validation, pat, sil-3, h-004, architecture, redundancy, idempotency:session562-ver-sub031-sil3-hft1-failover
VER-REQ-048 The verification activity for SUB-REQ-006 SHALL place the PAT Subsystem in sensor-degraded state by disabling one NIR channel and confirm that: (a) real-time CQA model evaluation on that channel suspends within 15 seconds; (b) a PAT DEGRADED alert appears on the SCADA dashboard within 30 seconds; (c) the MES updates sampling interval guidance from 30-minute to 10-minute intervals; and (d) all actions are recorded in the EBR deviation log with timestamps. Pass criterion: all four confirmations met in 3 consecutive test runs.
Rationale: SUB-REQ-006 is a degraded-mode safety requirement — test verification is required because timing of alert propagation and EBR logging depends on software state machine transitions that cannot be confirmed from design documentation. The 15-second detection and 30-second alert thresholds are the maximum acceptable delay before manual QC sampling begins.
Test session-562, validation, pat, degraded-mode, h-004, idempotency:session562-ver-sub006-pat-degraded-alert
VER-REQ-049 The verification activity for SUB-REQ-013 SHALL execute a simulated 3-batch production run in the MES test environment and confirm the batch genealogy record for each batch links: (a) each raw material lot number consumed; (b) each in-process test result with equipment ID and timestamp; (c) the packaging serialisation range (first and last unit serial number); and (d) operator signatures for each critical step. Pass criterion: genealogy query returns all four data categories with no null fields for all 3 batches.
Rationale: 21 CFR Part 11 and EU GMP Annex 11 require complete and accurate batch genealogy as a prerequisite for batch release. Inspection of design documentation cannot demonstrate that all genealogy linkages are captured and queryable — only a functional test can confirm end-to-end traceability.
Test session-562, validation, mes, genealogy, idempotency:session562-ver-sub013-mes-genealogy
VER-REQ-050 The verification activity for SUB-REQ-017 SHALL execute three drying cycles with placebo granules at the product-specific LOD recipe target, collect 3 stratified samples at end of drying, and confirm: (a) all 3 samples achieve LOD at or below the recipe target by Karl Fischer titration; (b) FBD inlet air temperature remained within plus or minus 2 degrees Celsius of recipe setpoint throughout the cycle per MES log. Pass criterion: all acceptance criteria met across all 3 runs.
Rationale: LOD reduction to target is a CQA for tablet dissolution and stability. Karl Fischer titration per USP 921 provides the reference measurement for GMP validation of the drying endpoint per ICH Q8. Test verification is required because drying performance depends on actual feed granule properties and equipment state.
Test session-562, validation, granulation-blending, sil-2, fbd, idempotency:session562-ver-sub017-fbd-lod-target
VER-REQ-051 The verification activity for SUB-REQ-018 SHALL install calibrated thermocouples at FBD inlet air duct and product chamber, run three consecutive drying cycles at nominal recipe setpoint, and confirm: (a) inlet air temperature remains within plus or minus 2 degrees Celsius of setpoint for at least 95 percent of each cycle; (b) any exceedance beyond plus or minus 3 degrees Celsius triggers an MES alarm within 60 seconds; (c) the MES recipe interlock halts the cycle if temperature exceeds plus or minus 5 degrees Celsius for more than 2 consecutive minutes. Pass criterion: all criteria met across all 3 test cycles.
Rationale: Inlet air temperature is a KPP for granule LOD and physical properties. The control band derives from the ICH Q8 validated design space. Test verification requires calibrated instrumentation because PID control loop response cannot be demonstrated by inspection of parameter settings.
Test session-562, validation, granulation-blending, sil-2, fbd, idempotency:session562-ver-sub018-fbd-inlet-temp
VER-REQ-052 The verification activity for SUB-REQ-019 SHALL run a post-drying milling cycle on a representative placebo granule batch, collect a sample at mill discharge, measure particle size distribution by laser diffraction per ISO 13320, and confirm: (a) D90 of the milled granule is 500 micrometres or less; (b) fines fraction below 53 micrometres does not exceed 15 percent v/v; (c) mill parameters recorded in MES match the validated recipe. Pass criterion: all acceptance criteria met across 3 milling runs.
Rationale: Granule particle size directly impacts tablet compressibility and dissolution rate. The D90 and fines acceptance criteria are derived from the compression process validated design space per ICH Q8. Laser diffraction per USP 429 is the reference technique for pharmaceutical granule sizing. Test verification is required because milling performance depends on actual feed properties and equipment wear.
Test session-562, validation, granulation-blending, sil-2, mill, idempotency:session562-ver-sub019-granule-sizing-d90
VER-REQ-053 The verification activity for SUB-REQ-021 SHALL execute a complete granulation and blending campaign in the MES test environment and confirm: (a) the MES records the net mass of each material charge within plus or minus 0.1 percent of actual as verified against calibrated balance read-back; (b) all transfer operations are logged with source and destination container ID and transferred mass; (c) mass balance closure is within plus or minus 0.5 percent for each process step. Pass criterion: all mass records complete and mass balance within tolerance across a 3-batch test run.
Rationale: Accurate mass recording is required for 21 CFR Part 11 complete batch record and EU GMP Annex 11 data integrity. Mass balance closure is the primary control for detecting unmeasured losses indicating contamination or dispensing errors. The 0.5 percent closure limit detects single-operator dispensing errors exceeding 0.5 percent of batch size.
Test session-562, validation, granulation-blending, sil-2, mass-balance, idempotency:session562-ver-sub021-gb-mass-recording
VER-REQ-054 The verification activity for SUB-REQ-023 SHALL activate OEB 3 compound handling mode in the test environment, execute a full granulation and blending cycle, and confirm: (a) all IBC charging operations execute only when containment interlock confirms isolator docking is complete per sensor log; (b) continuous air monitoring in the G&B area remains below 0.8 times the OEL action limit throughout the campaign; (c) simulated containment breach injection at 1.0 times OEL triggers automatic halt of material transfer within 10 seconds. Pass criterion: all three criteria met in a single full-cycle test.
Rationale: OEB 3 containment is a SIL-2 requirement addressing H-001 airborne potent compound exposure. The 10-second auto-halt threshold is derived from operator dose accumulation modelling at the OEL action limit. Test verification is mandatory because containment interlock logic depends on physical sensor states and pneumatic actuation that cannot be verified by inspection.
Test session-562, validation, granulation-blending, sil-2, h-001, containment, idempotency:session562-ver-sub023-gb-oeb3-containment
VER-REQ-055 The verification activity for SUB-REQ-026 SHALL operate the Tablet In-Process Control System at nominal press speed (60 RPM), confirm auto-sampling of every 30th tablet via IPC log (sample count equals run duration in seconds times RPM times station count divided by 30, within plus or minus 5 percent), and confirm weight, hardness, and thickness measurements for each sampled tablet are transmitted to the PAT subsystem within 10 seconds of sampling. Pass criterion: sampling rate compliance and data transmission latency both met across a 60-minute run.
Rationale: The every-30th-tablet sampling rate meets USP 905 content uniformity statistical power requirements. The 10-second data transmission limit ensures PAT model inputs are current — stale IPC data reduces CQA prediction accuracy. Test verification is required because sampling rate depends on IPC mechanical timing which cannot be verified from design drawings.
Test session-562, validation, tablet-compression, ipc, pat, idempotency:session562-ver-sub026-ipc-sampling-rate
VER-REQ-056 The verification activity for the OEL/OEB containment system requirement (SYS-REQ-013) SHALL operate a production run with a potent compound simulant at OEB 4 containment conditions, inject a simulated air concentration at 80 percent of the OEL action limit into the continuous monitoring system, and confirm: (a) an alarm is generated within 30 seconds of the injection; (b) the alarm is visible on the MES SCADA operator display; and (c) the EBR deviation log records the event with a timestamp accurate to 1 second. Pass criterion: all three confirmations met.
Rationale: SYS-REQ-013 is a SIL-2 safety requirement driving H-001 mitigation. Test verification is required to confirm the alarm propagation latency and EBR logging are consistent with actual system behaviour under simulated exposure conditions.
Test session-562, validation, containment, sil-2, h-001, oel, idempotency:session562-ver-sys013-oel-alarm
VER-REQ-057 The verification activity for the process validation data recording requirement (SYS-REQ-014) SHALL execute a complete production batch from raw material dispense through packaging, export the batch EBR, and confirm using a data completeness checklist that all ICH Q8 required CPP and CQA data fields are present, timestamped, and associated with the correct batch ID. Pass criterion: zero missing mandatory data fields across a 3-batch validation run.
Rationale: The appropriate verification for data completeness and format compliance is Analysis against the ICH Q8 data requirements checklist. This confirms the EBR structure meets regulatory filing requirements without requiring a live regulatory submission.
Analysis session-562, validation, process-validation, ich-q8, idempotency:session562-ver-sys014-ich-q8-data
VER-REQ-058 The verification activity for the EU FMD serialisation requirement (SYS-REQ-015) SHALL execute a packaging line run of 100 serialised units in the EMVS test environment, confirm 100 percent of serial numbers are successfully submitted to the national medicines verification system within 24 hours, and confirm that attempting to verify a decommissioned serial number returns a decommissioned status within 5 seconds. Pass criterion: 100% successful submission and correct decommissioned status response.
Rationale: EU Delegated Regulation 2016/161 compliance requires functional integration with the national EMVS. Test verification against the EMVS test repository is the only way to confirm correct data format and successful API communication with the external system.
Test session-562, validation, serialisation, eu-fmd, regulatory, idempotency:session562-ver-sys015-eu-fmd
VER-REQ-059 The verification activity for the EN ISO 13849-1 machine safety requirement (SYS-REQ-016) SHALL perform a documented Performance Level calculation for the guard interlock, emergency stop, and LOTO verification safety functions using the methodology of EN ISO 13849-1:2015, confirm that each function achieves PLd or higher, and document MTTFd, DCavg, and CCF values for each safety function in the safety case. Pass criterion: all three safety functions confirmed at PLd in the documented calculation.
Rationale: EN ISO 13849-1 PL determination is a structured analytical process, not a physical test. The PL calculation methodology using MTTFd, DCavg, and CCF per ISO 13849-1 is the accepted verification method for Machinery Directive 2006/42/EC compliance. Analysis is the correct verification type for this standards-based calculation.
Analysis session-562, validation, machine-safety, en-iso-13849, idempotency:session562-ver-sys016-iso13849-pl
VER-REQ-060 The verification activity for the OEE tracking requirement (SYS-REQ-017) SHALL run the system for 24 hours of simulated production with known availability events (3 unplanned stops of known duration), known speed losses (2 hours at 80 percent rated speed), and known quality losses (5 percent rejected tablets), compute the expected OEE from these inputs, and confirm the system-calculated OEE is within plus or minus 2 percent of the expected value. Pass criterion: OEE calculation accuracy within tolerance and alert generated when subsystem OEE drops below 75 percent.
Rationale: OEE calculation accuracy cannot be confirmed by inspection of the calculation algorithm alone — it requires end-to-end verification that data collection from all subsystems feeds the OEE calculation correctly. The plus or minus 2 percent tolerance is within measurement uncertainty for a 24-hour production window.
Test session-562, validation, oee, idempotency:session562-ver-sys017-oee
VER-REQ-061 The verification activity for the PAT qualification enforcement requirement (SYS-REQ-018) SHALL set one PAT instrument's calibration status to expired in the MES, attempt to initiate real-time release for a batch, and confirm: (a) the MES blocks real-time release initiation with an explicit error message citing the out-of-calibration instrument; (b) the block is not bypassable without QA Manager role credentials; and (c) the calibration status and block event are recorded in the EBR. Pass criterion: all three confirmations met.
Rationale: SYS-REQ-018 is a SIL-3 requirement addressing H-004 OOS product release. The enforcement of PAT calibration as a real-time release gate must be verified by Test — it cannot be confirmed by inspection because the block depends on runtime status flag evaluation in the MES workflow engine.
Test session-562, validation, pat, calibration, sil-3, h-004, idempotency:session562-ver-sys018-pat-calibration-block
VER-REQ-062 The verification activity for the PAT power supply requirement SHALL simulate a mains power failure by switching off the PAT subsystem UPS input, confirm: (a) the PAT subsystem continues operating without interruption for a minimum of 4 hours on battery; (b) a power failure alarm is transmitted to the MES within 10 seconds of mains loss; (c) battery state-of-charge is displayed on the SCADA operator dashboard throughout the test. Pass criterion: 4-hour autonomous operation and MES alarm within 10 seconds confirmed.
Rationale: SUB-REQ for PAT power supply directly supports SIL-3 hazard H-004 mitigation. The 4-hour UPS runtime must be verified by actual battery discharge test — design specifications for UPS capacity cannot substitute for a live runtime test under actual load conditions.
Test session-562, validation, pat, power, sil-3, idempotency:session562-ver-pat-power-ups-runtime
VER-REQ-063 The verification activity for the PAT manual override requirement SHALL log in as QC Analyst role in the MES test environment, trigger a CQA limit violation, activate the manual override function, confirm: (a) the override is accepted and recorded in the EBR within 60 seconds with operator ID and justification text; (b) attempting the same override with Operator role (below QC Analyst) is rejected; and (c) the override event is flagged in the batch audit trail for QA Manager review. Pass criterion: all three confirmations met.
Rationale: The manual override is a SIL-3 safety function — it must be restricted to qualified personnel and fully audit-trailed. Test verification is required because role-based access control enforcement depends on runtime identity and authorisation logic that cannot be confirmed by inspection of configuration settings alone.
Test session-562, validation, pat, override, sil-3, h-004, idempotency:session562-ver-pat-override-rbac
VER-REQ-064 The verification activity for the MES watchdog timer requirement SHALL stop the EBR processing heartbeat in the test environment, wait 95 seconds (3 consecutive missed heartbeats at 30-second interval), and confirm: (a) a system health alert is logged to the CMMS within 100 seconds; (b) the SCADA operator display changes to system-unavailable state within 100 seconds; (c) a new batch record initiation attempt fails with an explicit system-unavailable error. Pass criterion: all three confirmations met.
Rationale: The MES watchdog is a SIL-2 autonomous system safety control. Test verification is required because watchdog timer logic depends on actual heartbeat timing and state machine transitions — design documentation review cannot confirm the watchdog fires correctly under real failure conditions.
Test session-562, validation, mes, watchdog, sil-2, h-006, idempotency:session562-ver-mes-watchdog-test
VER-REQ-065 The verification activity for the Emergency Stop recovery requirement SHALL trigger a simulated containment breach alarm, confirm the system enters Emergency Stop mode, then attempt re-energisation without QA Manager sign-off and confirm rejection, then wait 30 minutes, perform QA Manager EBR sign-off, and confirm production equipment is permitted to restart. Pass criterion: unauthorised re-energisation blocked and authorised re-energisation permitted after sign-off and clearance period.
Rationale: Emergency Stop mode exit is a SIL-2 safety gate for H-001 and H-007 hazards. Test verification of the QA sign-off enforcement is mandatory — the effectiveness of an access control gate cannot be demonstrated by inspection of the workflow configuration. The 30-minute clearance period and QA sign-off requirement are both testable pass/fail criteria.
Test session-564, validation, emergency-stop, mode-coverage, sil-2, h-001, ambiguity-fixed
VER-REQ-066 The verification activity for the Maintenance LOTO display requirement SHALL apply a LOTO lock to the rotary tablet press via the MES LOTO registry, attempt to power on the press via all three command interfaces (operator HMI, PLC direct command, and MES remote command), confirm all three are rejected, and confirm the LOTO status (locked, applied-by, time-applied) is displayed on the MES operator HMI. Pass criterion: all three command rejections confirmed and LOTO status correctly displayed.
Rationale: The LOTO display and enforcement during Maintenance mode is a SIL-2 safety requirement for H-007 prevention. OSHA 29 CFR 1910.147 requires energy control procedures to be verified — inspection of LOTO registry configuration alone cannot demonstrate that all three command paths are blocked. Testing all three command paths is critical because single-channel protection is insufficient for SIL-2.
Test session-562, validation, maintenance, loto, sil-2, h-007, idempotency:session562-ver-maintenance-loto-display
VER-REQ-067 The verification activity for the Degraded Production mode real-time release block requirement SHALL activate degraded production mode in the MES test environment, produce a test batch, and confirm: (a) real-time release initiation is blocked with an explicit degraded-mode error message within 2 seconds of initiation attempt; (b) the batch is placed in quarantine status automatically within 60 seconds of batch completion; (c) QA Manager EBR sign-off is required before the batch is permitted to advance from quarantine. Pass criterion: all three confirmations met in 3 consecutive test runs; zero false-pass events (real-time release must never succeed in degraded mode).
Rationale: Blocking real-time release in degraded mode is an H-004 mitigation. The 2-second block response time and 60-second quarantine automation deadline are the minimum performance criteria required for this test to be meaningful. Zero false-pass events (real-time release succeeding in degraded mode) is the absolute safety criterion. Three consecutive runs confirm the control is not intermittent. Numeric criteria added per validation session 566.
Test session-564, validation, degraded, sil-3, h-004, rtrt, ambiguity-fixed
VER-REQ-068 The verification activity for the Tablet Compression Subsystem power supply requirement SHALL measure the main drive de-energisation time from EPO activation using a current clamp and oscilloscope, confirm de-energisation within 200ms across 5 test actuations, and confirm the MES LOTO registry logs the EPO event with a timestamp within 1 second of actuation. Pass criterion: all 5 actuations within 200ms and MES log entry confirmed.
Rationale: The 200ms EPO response is a direct contributor to H-007 safe state (equipment de-energised). Measurement of actual de-energisation time by oscilloscope is required because design specifications for contactor response times have manufacturing tolerances that may result in slower actual response. The MES LOTO log entry is required for 21 CFR Part 11 audit completeness.
Test session-562, validation, tablet-compression, power, h-007, idempotency:session562-ver-tc-epo-timing
VER-REQ-069 The verification activity for the Granulation and Blending Subsystem power supply requirement SHALL measure supply voltage at the HSG and FBD main distribution boards during a nominal production cycle, confirm voltage remains within plus or minus 10 percent of 400V nominal, inject a simulated voltage deviation beyond 10 percent, and confirm an MES alarm is generated within 60 seconds. Pass criterion: voltage within tolerance during production and alarm within 60 seconds of simulated deviation.
Rationale: Power supply voltage deviation affects both the HSG impeller speed (granule endpoint CQA) and FBD heating performance (LOD CQA). Test verification requires actual voltage measurement at distribution boards — design specifications cannot account for cable voltage drops and transformer loading effects in the installed facility.
Test session-562, validation, granulation-blending, power, idempotency:session562-ver-gb-power-voltage
VER-REQ-070 The verification activity for the Film Coating Subsystem power supply requirement SHALL run a complete simulated coating batch cycle, log MES power consumption data for the cycle, confirm power consumption per batch is within plus or minus 15 percent of the design specification value, and confirm the EPO de-energises all drives within 500ms across 5 test actuations. Pass criterion: power consumption within tolerance and EPO timing confirmed.
Rationale: Film coating power consumption logging is required for OEE calculation accuracy. The 15 percent tolerance accounts for coating load variability across batches. EPO test is required for H-001 safe state confirmation during coating of potent compounds.
Test session-562, validation, film-coating, power, idempotency:session562-ver-fc-power-consumption
VER-REQ-071 The verification activity for the Containment and Environmental Control Subsystem UPS requirement SHALL disconnect mains power from the containment subsystem UPS, confirm all monitoring and alarm functions remain operational for a minimum of 2 hours, confirm HVAC dampers remain in exhaust position throughout the test (fail-secure), and confirm UPS battery state-of-charge is displayed on the SCADA operator dashboard throughout. Pass criterion: 2-hour continuous operation and fail-secure exhaust position confirmed.
Rationale: The containment UPS runtime is a SIL-2 safety function for H-001 mitigation during power failure. Battery runtime must be verified by actual discharge test — manufacturer UPS capacity ratings do not account for actual connected load and battery ageing in the installed system.
Test session-562, validation, containment, power, sil-2, h-001, idempotency:session562-ver-cec-ups-runtime
VER-REQ-072 The verification activity for the MES server hardware requirement SHALL inspect the server room physical configuration and confirm by visual inspection: (a) dual redundant PSUs installed in each server with both connected to independent circuits; (b) server room door equipped with badge access reader with logged access events; (c) server room access log retrievable from CMMS for the previous 90 days. Pass criterion: all three items confirmed by inspection.
Rationale: Physical installation and access control measures for the MES server are verifiable by Inspection — they are observable physical characteristics that do not require functional testing. The 90-day access log retention directly supports 21 CFR Part 11 audit trail requirements for the physical location housing the EBR system.
Inspection session-562, validation, mes, hardware, 21cfr11, idempotency:session562-ver-mes-server-inspection
VER-REQ-073 The verification activity for the Startup mode entry criteria requirement SHALL configure the MES test environment with one equipment qualification record expired, one PAT system suitability check failed, and one open deviation from a prior campaign, then attempt to initiate a new batch record, and confirm the MES blocks batch record initiation with an error identifying all three blocking conditions. Pass criterion: batch record initiation blocked and all three blocking conditions clearly identified in the error message.
Rationale: Startup mode entry gate enforcement is a quality assurance control preventing production on unqualified equipment. Test verification requires injecting each blocking condition individually and in combination to confirm the MES enforcement logic is comprehensive. Inspection of workflow configuration alone cannot confirm all conditions are evaluated.
Test session-562, validation, startup, mode-coverage, mes, idempotency:session562-ver-startup-entry-gate
VER-REQ-074 The verification activity for the Degraded Production mode quarantine requirement SHALL complete a production run in degraded mode, confirm: (a) the batch is automatically placed in MES quarantine status within 60 seconds of batch completion without operator action; (b) an attempt to advance the batch to released status without QA Manager sign-off is rejected within 2 seconds with an explicit error message; (c) QA Manager sign-off (electronic signature) permits batch advancement. Pass criterion: automatic quarantine within 60 seconds confirmed, QA sign-off gate enforced with zero bypass events, all three test runs pass.
Rationale: The Degraded mode quarantine gate is an H-004 mitigation control. The 60-second automated quarantine deadline and the 2-second reject response for unauthorised release attempts are the quantified performance criteria required to confirm the control works under operational timing conditions. Zero bypass events is the absolute criterion — the sign-off gate must never fail. Numeric thresholds added per validation session 566 to resolve ambiguousReqs blocker.
Test session-564, validation, degraded, mode-coverage, h-004, ambiguity-fixed
VER-REQ-075 The verification activity for SUB-REQ-048 SHALL inject a simulated airborne concentration at 85 percent of OEL into the continuous monitoring system, confirm: (a) Emergency Stop activates within 5 seconds; (b) all material transfer valves close within 5 seconds as confirmed by position feedback; (c) HVAC switches to 100 percent exhaust within 15 seconds; (d) evacuation alarm sounds at minimum 85 dB at 1 metre. Pass criterion: all 4 criteria met in 3 test runs.
Rationale: H-001 is a SIL-2 hazard. Test verification with timing measurements is required for all four automated responses. Design analysis alone cannot confirm actual pneumatic valve actuation and HVAC damper response times match specified values.
Test session-562, validation, containment, sil-2, h-001, idempotency:session562-ver-sub048-breach-autoresponse
VER-REQ-076 The verification activity for SUB-REQ-049 SHALL configure the test environment to log air monitoring data for 24 hours, confirm that a minimum of 1 sample per 60 seconds per monitoring point is recorded in the EBR log, export the 24-hour record in CSV and PDF formats, and confirm file format validity. Pass criterion: sampling frequency confirmed at 1 per 60 seconds or higher and both export formats valid.
Rationale: Air monitoring frequency and data export format compliance cannot be confirmed by inspection of system configuration alone — actual data logging rate must be measured across a 24-hour period to confirm no gaps. Export format validation ensures regulatory inspection accessibility.
Test session-562, validation, containment, monitoring, h-001, idempotency:session562-ver-sub049-air-monitoring-freq
VER-REQ-077 The verification activity for SUB-REQ-050 SHALL inject a cleaning validation failure result (location 7 swab result exceeding acceptance limit) into the MES test environment, confirm: (a) next batch associated with that equipment is automatically placed in quarantine; (b) QA Manager receives SCADA notification and email alert within 5 minutes; (c) batch release is blocked until QA Manager sign-off. Pass criterion: all 3 confirmations met.
Rationale: Automatic quarantine on cleaning validation failure is a H-002 SIL-3 mitigation. Test verification is required to confirm the automatic quarantine trigger and dual notification path are both functional — inspection of workflow configuration cannot confirm the actual message routing and quarantine state enforcement.
Test session-562, validation, mes, changeover, sil-3, h-002, idempotency:session562-ver-sub050-cleaning-quarantine
VER-REQ-078 The verification activity for SUB-REQ-051 SHALL attempt to advance an API dispensing step in the MES test environment with only one operator confirmation, confirm the step advancement is blocked, then provide both operator confirmations and confirm the step advances. Repeat with a simulated second operator confirmation from an unauthorised role and confirm rejection. Pass criterion: single-confirmation advance blocked and dual authorised-role confirmation accepted.
Rationale: Two-person API dispensing verification is a 21 CFR Part 211 critical step control for H-002. Test verification must confirm both the enforcement of two distinct operator identities and the role authorisation requirement. These are runtime EBR workflow controls that cannot be verified by inspection.
Test session-562, validation, material-handling, sil-3, h-002, idempotency:session562-ver-sub051-two-person-api
VER-REQ-079 The verification activity for SUB-REQ-052 SHALL run the tablet compression line with the metal detection system active, inject 5 known metallic particles of 0.5mm diameter into the tablet stream at known positions, confirm: (a) all 5 particles are detected; (b) rejection mechanism activates and diverts the 10 tablets before and 10 after each detected particle; (c) a critical alarm is generated in the MES for each detection. Pass criterion: 100 percent detection rate and correct rejection window confirmed.
Rationale: Metal detection performance cannot be verified by equipment specification review alone — actual detection sensitivity depends on tablet mass, line speed, and detector calibration. Testing with 0.5mm particles at known positions confirms the worst-case detection scenario for the punch-tip fragment size most likely to result from tooling breakage.
Test session-562, validation, tablet-compression, metal-detection, idempotency:session562-ver-sub052-metal-detection
VER-REQ-080 The verification activity for SUB-REQ-053 SHALL connect a calibrated dust concentration monitor to the FBD exhaust duct, inject a dust aerosol to reach 30 percent of LEL, confirm: (a) the system detects concentration above 25 percent LEL threshold; (b) nitrogen inerting activates within 10 seconds; (c) FBD airflow reduces to minimum circulation rate within 10 seconds; (d) SIL-2 alarm is generated in MES within 10 seconds. Pass criterion: all 4 criteria met.
Rationale: H-003 dust explosion prevention is a SIL-2 safety function. Test verification with a calibrated dust monitor and timed response measurement is required. The 25 percent LEL detection threshold and 10-second response time must be confirmed under actual process conditions — design specifications for sensor sensitivity and pneumatic valve response times may differ from installed performance.
Test session-562, validation, granulation-blending, dust-explosion, sil-2, h-003, idempotency:session562-ver-sub053-dust-lel
VER-REQ-081 The verification activity for SUB-REQ-054 SHALL run 500 blister packs through the packaging vision inspection system, introduce 10 packs with deliberate defects (5 absent tablets, 3 broken tablets, 2 foreign particle simulants) at known positions, confirm: (a) all 10 defective packs are rejected; (b) no non-defective packs are rejected; (c) all rejected pack IDs and rejection reasons are logged in the EBR. Pass criterion: 100 percent defect detection with zero false rejects and complete EBR logging.
Rationale: Vision inspection at 100 percent confidence is a final critical quality gate before product release. Test verification with known defect types and zero false-reject tolerance is required because vision system performance depends on lighting, tablet colour, and line speed factors that vary with product. The EBR logging requirement ensures rejected pack traceability for batch disposition.
Test session-562, validation, packaging, vision-inspection, idempotency:session562-ver-sub054-vision-inspection
VER-REQ-082 The verification activity for SUB-REQ-055 SHALL register a time-critical sample request in the MES, confirm the LIMS receives the request within 30 seconds, enter the result in LIMS, and confirm the MES displays the result within 5 minutes of LIMS entry. Also confirm that a rejected result is retained with rejection reason in both systems. Pass criterion: both latency SLAs met and rejected result retained in both audit trails.
Rationale: LIMS-MES integration latency determines real-time release cycle time. The 30-second receipt and 5-minute result return SLAs must be verified by end-to-end integration test — interface configuration review cannot confirm actual network latency and system processing time under production load conditions.
Test session-562, validation, lims, mes, idempotency:session562-ver-sub055-lims-mes
VER-REQ-083 The verification activity for SUB-REQ-056 SHALL complete a simulated batch, confirm the MES generates a PDF/A batch review report within 15 minutes of batch completion, verify the report contains all required sections (CPP trends, IPC results, deviation summary, compliance checklist), and confirm the PDF/A format is valid per ISO 19005 using a PDF/A validator. Pass criterion: report generated within 15 minutes and PDF/A format confirmed valid.
Rationale: Batch review report SLA and PDF/A format compliance must be verified by a functional end-to-end test. The 15-minute SLA is a business process requirement for same-shift review. PDF/A validity requires format-level testing with a standards-compliant validator — design review cannot confirm PDF/A compliance in the generated output.
Test session-562, validation, mes, batch-review, idempotency:session562-ver-sub056-batch-report
VER-REQ-084 The verification activity for SUB-REQ-057 SHALL operate the PAT subsystem for 31 days in the test environment, query the audit log for day 1 entries and confirm they are present and unmodified, attempt to modify a log entry and confirm rejection, and export the full 30-day record in CSV format and confirm all entries are present. Pass criterion: 30-day retention confirmed, tamper evidence confirmed, and export validated.
Rationale: The 30-day PAT audit log retention is a SIL-3 H-004 data integrity control. Tamper-evidence verification requires attempting a modification and confirming it is rejected — inspection of technical controls alone cannot confirm tamper-evidence effectiveness. The CSV export confirmation is required for regulatory inspection accessibility.
Test session-562, validation, pat, audit-log, sil-3, h-004, idempotency:session562-ver-sub057-pat-audit-log
VER-REQ-085 The verification activity for the auto-deviation record requirement (SYS-REQ-019) SHALL inject a CPP limit exceedance into the test system, confirm a deviation record is created in the EBR within 10 minutes linking all required data fields (batch ID, measurement value, subsystem, timestamp), and confirm the deviation is visible to QA Manager in the SCADA review queue within the same window. Pass criterion: complete deviation record within 10 minutes.
Rationale: Deviation record generation latency must be confirmed by functional test because it depends on real-time EBR write performance under production load. The 10-minute SLA is a patient safety and regulatory compliance requirement under ICH Q10.
Test session-562, validation, mes, deviation, idempotency:session562-ver-sys019-auto-deviation
VER-REQ-086 The verification activity for the cleaning status registry requirement (SYS-REQ-020) SHALL set equipment item A's cleaning status to expired in the MES test environment, attempt to assign equipment A to a new batch record, confirm the assignment is blocked with an explicit status reason, then complete a cleaning record for equipment A, confirm the status updates to confirmed clean, and confirm the assignment now succeeds. Pass criterion: block enforced on expired status and unblocked after cleaning confirmation.
Rationale: Cleaning registry enforcement is a SIL-3 H-002 mitigation. Test verification confirms the enforcement gate is functional across the full status lifecycle (expired, cleaning in progress, confirmed clean). Runtime state evaluation cannot be confirmed by inspection of database schema design.
Test session-562, validation, changeover, sil-3, h-002, idempotency:session562-ver-sys020-cleaning-registry
VER-REQ-087 The verification activity for the shift handover requirement (SYS-REQ-021) SHALL simulate a shift end with 1 open deviation and 1 in-progress batch, confirm the outgoing supervisor electronically signs the handover record with all required data fields, attempt to start a new production operation without incoming supervisor acknowledgement and confirm rejection, then complete incoming supervisor acknowledgement and confirm the operation is permitted to proceed. Pass criterion: operation rejection confirmed before acknowledgement and permitted after.
Rationale: Shift handover enforcement is a 21 CFR Part 11 process control. Test verification confirms the MES workflow gate is enforced correctly for the specific scenarios where handover is most critical — active deviations and in-progress batches. Design review of workflow configuration cannot confirm runtime gate enforcement.
Test session-564, validation, mes, handover, ambiguity-fixed
VER-REQ-088 The verification activity for the system-level OEE tracking (SYS-REQ-017) SHALL confirm the OEE dashboard is accessible from the SCADA operator display, that all three OEE components (Availability, Performance, Quality) are displayed with the contributing subsystem breakdown, and that an alert is generated and visible on the dashboard when a subsystem OEE drops below 75 percent for more than one production shift. Pass criterion: dashboard accessible, all components displayed, and alert confirmed.
Rationale: OEE dashboard accessibility and display correctness is confirmed by Demonstration — a functional walkthrough of the dashboard with known input values. This complements VER-REQ-069 (OEE calculation accuracy test) by confirming the display layer and alerting logic are functional.
Demonstration session-562, validation, oee, idempotency:session562-ver-oee-dashboard-demo
VER-REQ-089 The verification activity for the batch genealogy system-level requirement (SYS-REQ-007) SHALL execute a complete production campaign (materials → packaging) for a single batch, perform a genealogy query for the finished product lot number, and confirm the returned record includes: (a) all raw material lot numbers and supplier certificates; (b) all in-process test results with subsystem IDs; (c) all deviation records and their dispositions; (d) the complete serialisation range. Pass criterion: all four genealogy components present and traceable to source records.
Rationale: SYS-REQ-007 system-level batch genealogy is a 21 CFR Part 211 and EU GMP Annex 15 requirement. Test verification of end-to-end genealogy requires an actual production campaign to confirm all data linkages are created correctly across all subsystem interfaces. Design review of database schema cannot confirm that all subsystem integration points populate genealogy records.
Test session-562, validation, genealogy, 21cfr11, system-level, idempotency:session562-ver-sys007-genealogy-system
VER-REQ-090 The verification activity for SYS-REQ-003 SHALL inject 50 pre-characterised CQA test spectra spanning 10 nominal, 10 OOS-API, 10 OOS-dissolution, 10 sensor-degraded, and 10 boundary-condition samples into the system at the PAT DAC Workstation, and confirm: (a) each spectrum is evaluated within 5 seconds; (b) OOS classification triggers automatic diversion valve actuation within 2 seconds; (c) sensor-degraded samples trigger a health alert within 15 seconds. Pass criterion: 50/50 correct decisions with all timing bounds met.
Rationale: SYS-REQ-003 is the system-level PAT/CQA requirement covering the safety-critical chain from spectrum acquisition through diversion actuation, addressing SIL-3 H-004. A system-level test with representative sample types is required because individual subsystem tests do not confirm the integrated acquisition-evaluation-actuation chain behaves correctly end-to-end.
Test session-564, validation, pat, sil-3, h-004, sys-level, ambiguity-fixed, idempotency:session564-ver-sys003-pat-system-level
VER-REQ-091 The verification activity for SYS-REQ-004 SHALL install calibrated airflow velocity probes at all access point openings of a qualified potent compound enclosure, operate the system under production conditions, inject a tracer aerosol in the enclosure headspace, and confirm: (a) inward airflow velocity is at least 0.5 m/s at all open access points; (b) continuous airborne particle monitor generates an alarm when concentration exceeds 20 percent of OEL; (c) automatic enclosure lockdown activates within 10 seconds of alarm. Pass criterion: all three measurements confirmed.
Rationale: SYS-REQ-004 is a SIL-2 H-001 safety requirement. Test verification with physical airflow measurement is required by COSHH regulations to confirm the negative pressure isolation is effective under actual production conditions. Design analysis of HVAC specifications cannot confirm in-situ airflow velocities with production equipment in place.
Test session-564, validation, containment, sil-2, h-001, sys-level, idempotency:session564-ver-sys004-containment-system-level
VER-REQ-092 The verification activity for SYS-REQ-011 SHALL register an active LOTO lockout device in the MES for three separate equipment types (tablet press, granulator, packaging line), attempt restart commands for each via operator HMI, supervisor override, and programmatic API, and confirm all nine restart attempts are rejected with LOTO interlock alarm while the lockout is active; remove each lockout device and confirm equipment restart is then permitted. Pass criterion: all 9 blocking attempts rejected and all 3 restart permits granted after LOTO removal.
Rationale: SYS-REQ-011 is a SIL-2 H-007 safety requirement — preventing energisation of equipment during maintenance. Test verification with three equipment types and three restart methods confirms the LOTO interlock is implemented uniformly across the system, not just for the specific configurations tested at subsystem level (VER-REQ-007, VER-REQ-037, VER-REQ-066).
Test session-564, validation, loto, sil-2, h-007, sys-level, idempotency:session564-ver-sys011-loto-system-level
VER-REQ-093 The verification activity for SYS-REQ-001 SHALL execute a continuous 12-hour simulated production run at the nominal recipe setpoint for a representative product, log the MES production counter at the start and end of each unit operation, and confirm: (a) cumulative tablet output at end of shift is at least 300,000 tablets; (b) MES OEE report is updated at least once per hour; (c) OEE is calculated and displayed for the shift. Pass criterion: throughput target met and hourly OEE reporting confirmed.
Rationale: SYS-REQ-001 is the primary production capacity requirement derived from STK-REQ-001. Test verification requires a full-shift production run to confirm all subsystem throughput contributions combine to meet the system-level target; static analysis of individual subsystem rates cannot confirm dynamic bottlenecks are absent.
Test session-564, validation, throughput, oee, sys-level, idempotency:session564-ver-sys001-throughput-system-level
VER-REQ-094 The verification activity for SYS-REQ-002 SHALL execute a complete batch lifecycle in the MES test environment: create an EBR, execute all lifecycle steps with electronic signatures, perform an audit trail review, confirm backup occurs within 15 minutes by checking backup timestamps, then tamper with one EBR record directly and confirm the cryptographic hash integrity check detects the alteration within 60 seconds. Pass criterion: all lifecycle operations succeed with electronic signatures, backup interval confirmed, and tamper detection triggered.
Rationale: SYS-REQ-002 covers EBR data integrity and electronic signature enforcement under 21 CFR Part 11 and EU GMP Annex 11. The original Inspection method is insufficient for a SIL-2 H-006 data integrity requirement — Test is required to confirm the hash chain, access controls, and backup intervals function correctly under actual system load.
Test session-564, validation, ebr, 21cfr11, sil-2, h-006, sys-level, idempotency:session564-ver-sys002-ebr-system-level
VER-REQ-095 The verification activity for SYS-REQ-009 SHALL induce PAT sensor-degraded mode in a running production simulation, and confirm: (a) the system switches to manual in-process testing mode within 30 seconds with a 15-minute sampling schedule; (b) production throughput is maintained at 50 percent of nominal or above for the next 30 minutes; (c) Production Supervisor receives a prominent EBR annotation within 30 seconds. Pass criterion: all three confirmations met across 3 test runs.
Rationale: SYS-REQ-009 implements the PAT Sensor Drift ConOps scenario — degraded mode must maintain minimum throughput while protecting product quality. Test verification confirms the mode transition, throughput floor, and supervisor notification all occur within the required time bounds under actual system load.
Test session-564, validation, degraded-mode, pat, sys-level, pat-sensor-drift-scenario, idempotency:session564-ver-sys009-degraded-mode-system-level
VER-REQ-096 The verification activity for SYS-REQ-010 SHALL run a packaging line production of 500 saleable units, confirm 100 percent of units receive a 2D DataMatrix barcode encoding serial number, GTIN, lot number, and expiry date, measure the barcode verification reject rate over the run and confirm it is below 0.5 percent, then confirm aggregation data for the lot is uploaded to the external serialisation system within 2 hours of line completion. Pass criterion: 100 percent barcode application, reject rate below 0.5 percent, and upload confirmed.
Rationale: SYS-REQ-010 implements EU FMD and DSCSA serialisation requirements at system level. Test verification requires a production-representative run because barcode reject rate is a statistical metric that cannot be confirmed by inspection of the print-and-verify station in isolation from the full packaging line.
Test session-564, validation, serialisation, eu-fmd, sys-level, idempotency:session564-ver-sys010-serialisation-system-level
VER-REQ-097 The verification activity for SYS-REQ-012 SHALL run the tablet press at nominal speed with IPC system active, inject 10 tablets per rejection criterion (10 overweight, 10 underweight, 10 hard, 10 soft, 10 thick, 10 thin) into the press feed, confirm all 60 out-of-specification tablets are rejected at the IPC station, then inject a sequence exceeding the L1 AV threshold of 15.0 and confirm the entire production segment is rejected. Pass criterion: 60/60 individual rejections and segment rejection confirmed.
Rationale: SYS-REQ-012 defines the system-level tablet quality rejection criteria. Test verification with deliberate OOS samples per acceptance criterion confirms the rejection logic is implemented for all specified parameters, not just the ones tested at subsystem level. The L1 AV segment rejection is an additional system-level control not covered by individual tablet rejection tests.
Test session-564, validation, product-quality, ipc, sys-level, idempotency:session564-ver-sys012-product-quality-system-level
VER-REQ-098 The verification activity for SUB-REQ-058 SHALL log in as QC Analyst in the MES test environment, trigger a CQA limit violation, activate the manual override function and confirm: (a) EBR electronic signature is required before override activates; (b) override expires automatically after 60 minutes and autonomous CQA evaluation resumes; (c) attempted override without electronic signature is rejected. Pass criterion: all three confirmations met.
Rationale: SUB-REQ-058 is a SIL-3 H-004 safety constraint on the PAT autonomous diversion function. Test is required to confirm the signature gate, duration limit, and automatic restoration all function correctly under operational conditions.
Test session-564, validation, pat, sil-3, h-004, override, functional-autonomy, idempotency:session564-ver-sub058-pat-override-test
VER-REQ-099 The verification activity for SUB-REQ-059 SHALL conduct a physical inspection of the Granulation and Blending Subsystem installation during commissioning: confirm the equipment bay is classified ISO 8 (Grade D) by environmental monitoring certificate, confirm all product-contact surfaces are 316L stainless steel by material certification, and confirm all IBC transfer connections are documented as ANSI/ISPE OEB 4-compatible by supplier certificate. Pass criterion: all three material and classification certificates present and signed by QA.
Rationale: SUB-REQ-059 is SIL-2 tagged (G&B containment subsystem contributes to H-002 cross-contamination mitigation via OEB 4 transfer connection integrity). IEC 61508 SIL-2 requires Test verification for safety-critical installation requirements — Inspection alone cannot confirm that the sealed IBC transfer connections withstand operating pressures and do not leak fine powder. The Test method adds: (d) pneumatic pressure integrity test of each ANSI/ISPE OEB 4-compatible transfer connection at 0.7 bar dry-air for 30 seconds with zero detectable powder leakage (leak detector ≤1×10⁻⁶ mbar·L/s). Inspection checks (material certificates, environmental certificate, sensor heights) are retained as Pass criteria (a)-(c) within the same Test protocol.
Test session-565, validation, granulation, installation, sil-2, idempotency:session565-ver-subreq059-granulation-install
VER-REQ-100 The verification activity for SUB-REQ-060 SHALL measure PCS power consumption at full PLC chassis load using a calibrated power analyser (confirm ≤ 500 W per chassis), then disconnect utility mains and confirm: (a) UPS sustains all PLC and HMI functions for a minimum of 30 minutes; (b) a power failure alarm appears on the SCADA operator screen within 2 seconds of mains loss; (c) supply voltage remains within 23.0–25.0 VDC throughout the test. Pass criterion: all three checks confirmed in a single test run.
Rationale: SUB-REQ-060 specifies the PCS power integrity constraints that protect batch execution during utility interruptions. Test verification with physical mains disconnection is the only method that can confirm the 30-minute autonomy period, the 2-second alarm response, and the voltage regulation simultaneously — these are measurable performance parameters that cannot be confirmed by Inspection or Analysis alone. PCS power continuity is an enabler for the MES heartbeat (SUB-REQ-061) and the safe-state transition sequence.
Test session-565, validation, pcs, power, ups, idempotency:session565-ver-subreq060-pcs-power
VER-REQ-101 The verification activity for SUB-REQ-061 SHALL: (a) Watchdog test — suspend the MES heartbeat signal in a test environment and confirm the watchdog triggers a controlled safe-state transition within 30 seconds: batch execution suspended, HVAC failsafe command issued (confirmed at HVAC controller), and an operator alert generated; (b) E-STOP test — activate the dedicated physical E-STOP button at each operator workstation in sequence and confirm all MES-controlled automated functions halt within 10 seconds per activation; (c) Confirm all watchdog and E-STOP events are recorded in the EBR with timestamp and operator station ID. Pass criterion: all activations meet timing criteria and EBR records are present.
Rationale: SUB-REQ-061 is a SIL-tagged safety requirement covering the MES watchdog timer and operator E-STOP — both are safety-critical functions for the Emergency Stop operating mode. IEC 61511 (Functional Safety — Safety Instrumented Systems for the Process Industry Sector) requires Test verification for SIL-rated functions; Analysis or Inspection alone cannot demonstrate that the actual hardware/software combination meets the 30-second watchdog timeout and 10-second E-STOP response. The HVAC failsafe confirmation is critical because HVAC exhaust mode is the H-001 containment breach safe state.
Test session-565, validation, mes, watchdog, estop, sil-2, safety-critical, idempotency:session565-ver-subreq061-mes-watchdog
VER-REQ-102 The verification activity for SUB-REQ-062 SHALL conduct a commissioning inspection of all environmental monitoring sensor installations: (a) verify differential pressure transmitters are present at each of the three controlled cleanroom boundaries by physical walkthrough against installation drawing; (b) confirm temperature and humidity sensor mounting heights are within 0.8–1.2 m above finished floor level using calibrated measuring tape at each classified bay; (c) verify 316L stainless steel construction for all sensor housings by material certification; (d) confirm ISO 8 installation certificate signed by QA for each bay. Pass criterion: all four checks confirmed at all locations.
Rationale: SUB-REQ-062 governs physical sensor placement and material certification — Inspection is the correct method as the requirement is verified by physical presence, position measurement, and certificate review, not by dynamic testing. The commissioning inspection is conducted against installation drawings and GMP qualification records and forms part of the Installation Qualification (IQ) package per ISPE Baseline Guide Volume 5 (Commissioning and Qualification).
Inspection session-565, validation, environmental-control, sensor-installation, idempotency:session565-ver-subreq062-sensor-install
VER-REQ-103 The verification activity for SYS-REQ-026 SHALL install reference traceable standards at three cleanroom monitoring points, confirm each differential pressure transmitter reads within ±1 Pa of the reference standard at 0, 50, and 100 Pa calibration points; each temperature transmitter reads within ±0.3°C at 15°C, 22°C, and 30°C; each RH transmitter reads within ±2% RH at 30%, 50%, and 70% RH. Pass criterion: all calibration points within stated tolerances for all installed sensors, confirmed against ISO 17025-accredited calibration records.
Rationale: SYS-REQ-026 specifies sensor accuracy requirements (±1 Pa, ±0.3°C, ±2% RH) and calibration intervals. These tolerances must be demonstrated by calibration test against traceable reference standards — instrument specification alone does not demonstrate field accuracy after installation. ISO 17025-accredited calibration records provide the regulatory evidence required for GMP instrument qualification.
Test session-566, validation, cleanroom, environmental, physical-embodiment, idempotency:ses566-ver-sys026-cleanroom-sensors
VER-REQ-104 The verification activity for SYS-REQ-027 SHALL confirm: (a) with PLC in RUN mode, pressing the manual override pushbutton at each equipment panel de-energises the target actuator within 250 ms (measured via oscilloscope on the actuator power circuit); (b) initiating an Emergency Stop via a hardwired safety relay input (bypassing software) de-energises all drives within 250 ms; (c) the override actions do not require any software acknowledgement and are effective regardless of recipe or interlock state. Pass criterion: all actuators de-energised within 250 ms on every test, 100% success rate across 10 consecutive tests per actuator type.
Rationale: SYS-REQ-027 specifies hardware-enforced overrides and 250ms E-stop response. The 250ms timing must be measured with an oscilloscope on the power circuit — software timing logs are insufficient because software failure is the scenario being mitigated. Testing with PLC in RUN mode confirms override works under normal software conditions; hardware bypass test (direct relay input) confirms override is independent of software state. EN ISO 13849-1 requires demonstrated performance level for safety-related control functions.
Test session-566, validation, process-control-system, safety-override, sil-2, idempotency:ses566-ver-sys027-pcs-override
VER-REQ-105 The verification activity for SYS-REQ-023 SHALL: (a) log in as a qualified Production Supervisor in the MES test environment; (b) trigger a PAT-induced automated batch diversion; (c) invoke the operator override function and confirm the system requests 21 CFR Part 11 electronic signature before accepting the override; (d) confirm the diversion is suspended and the override timer starts; (e) confirm the system automatically restores automated diversion control after 60 minutes without operator action; (f) confirm the audit trail records operator identity, override reason, start time, and duration. Pass criteria: 21 CFR Part 11 e-sig enforced on all override invocations; auto-restore within 60 minutes (±30 seconds); all 5 audit trail fields populated.
Rationale: SYS-REQ-023 (operator override capability, 21 CFR Part 11, 60-minute auto-restore) was identified as having no VER trace in the validation session. The override function is safety-relevant because suspension of automated diversion without audit trail creates H-004 (OOS product release) risk. Test verification is required to confirm: (1) electronic signature cannot be bypassed, (2) auto-restore timeout functions correctly, and (3) audit trail is complete per 21 CFR Part 11 requirements.
Test session-567, validation, override, normal-production, 21-cfr-part-11, sys-023, idempotency:session567-ver-sys023-operator-override
VER-REQ-106 The verification activity for SYS-REQ-022 SHALL conduct a commissioning inspection of the manufacturing facility against the approved GMP facility layout drawing: (a) confirm presence of at least four classified cleanrooms (weigh booth, granulation/compression, coating/packaging, and materials corridor) by physical walkthrough; (b) confirm ISO 7/Grade C classification certificate for the weigh booth and ISO 8/Grade D classification for remaining production bays by review of environmental monitoring qualification certificates; (c) confirm positive pressure cascade from cleanest to less-clean zones via magnehelic gauge readings at each boundary; (d) confirm dedicated access airlocks at each classified zone boundary. Pass criterion: all four zone certificates present, signed by QA; pressure cascade confirmed in the correct direction at all boundaries.
Rationale: SYS-REQ-022 is a facility layout inspection requirement (ISO 7/Grade C cleanrooms). Inspection is the appropriate verification method since compliance is demonstrated by facility qualification certificates and physical walkthrough, not by instrument test. EU GMP Annex 1 requires documented environmental classification for each cleanroom zone.
Inspection session-567, validation, facility, cleanroom, sys-022, idempotency:session567-ver-sys022-facility-layout
VER-REQ-107 The verification activity for SYS-REQ-025 SHALL inspect the installed environmental monitoring sensor positions in each classified bay: (a) measure mounting height of temperature and humidity sensors at each of the three classified bays with a calibrated measuring tape and confirm all sensors are within 0.8 to 1.2 m above finished floor level; (b) confirm differential pressure transmitters are positioned at each of three controlled cleanroom boundaries; (c) confirm all sensor cables route to the EMS rack and that the EMS controller is within the classified area. Pass criterion: all sensor positions within specified height range; differential pressure taps at all three boundaries; EMS rack location confirmed.
Rationale: SYS-REQ-025 specifies physical sensor mounting positions (0.8-1.2m height, three DP boundaries). Inspection is appropriate as sensor placement is verified by physical measurement during commissioning. No VER trace existed prior to this session.
Inspection session-567, validation, sensors, physical-embodiment, sys-025, idempotency:session567-ver-sys025-sensor-placement
VER-REQ-108 The verification activity for SYS-REQ-028 SHALL perform a physical commissioning inspection of the GMP equipment rack housing the EMS controller, PCS I/O modules, and 4-20mA signal conditioning hardware: (a) confirm the enclosure IP rating is IP54 or better by inspection of the manufacturer certificate; (b) confirm stainless steel construction by visual inspection and material certificate; (c) confirm the rack is installed within the manufacturing line classified area by physical location check against the approved facility layout drawing; (d) confirm connection to the clean power UPS supply by following the UPS output cable to the rack power inlet and verifying the UPS label matches SYS-REQ-007 specification; (e) confirm at least three 4-20mA input channels are wired to differential pressure transmitters at the three cleanroom boundaries. Pass criterion: all five checks confirmed and documented in the commissioning inspection record.
Rationale: SYS-REQ-028 specifies the physical attributes of the environmental monitoring rack (IP54, stainless steel, location in classified area, UPS connection, 4-20mA channels). Inspection is the appropriate verification method: physical attributes are confirmed by inspection and review of material certificates rather than by instrument testing. The inspection record provides the documentary evidence required for GMP facility qualification.
Inspection session-568, validation, normal-production, physical-embodiment, mes, sys-028, idempotency:session568-ver-sys028-rack-inspection
VER-REQ-115 Verify SYS-REQ-030: Inspect PCS network architecture documentation to confirm firewall or unidirectional gateway separates PCS from enterprise IT network. Review network topology diagram and firewall ruleset. Verify IEC 62443-3-3 Security Level 2 compliance assessment is documented. Test access control by attempting HMI login with invalid credentials and verify lockout occurs. Review user access matrix to confirm individual authentication is in place.
Rationale: Network isolation and access control for safety-critical OT systems cannot be fully tested at the system level without risk of disrupting live production. Inspection of documented architecture and security assessment, combined with targeted authentication testing, provides the required verification for a safety-functional cybersecurity requirement.
Inspection session-549, qc, cybersecurity, pcs, verification, idempotency:ver-sys-req-030-pcs-cyber-session-549

Traceability Matrix — Verification

RequirementVerified ByDescription
VER-REQ-024 SUB-REQ-027 VER-REQ-024 verifies tablet press guard interlock and LOTO restart prevention SUB-REQ-027
VER-109 SUB-REQ-065 SUB-REQ-065 safe state transition → VER-109 30-second response test
VER-108 SUB-REQ-063 SUB-REQ-063 HVAC cleanroom conditions → VER-108 FAT acceptance test
VER-114 SUB-REQ-064 SUB-REQ-064 pressure cascade → VER door disturbance test
VER-REQ-001 SUB-REQ-003 CQA model evaluation timing test
VER-REQ-002 SUB-REQ-004 Diversion valve actuation time and fail-safe test
VER-REQ-003 SUB-REQ-005 Sensor degradation detection test
VER-REQ-006 SUB-REQ-008 21 CFR Part 11 e-signature enforcement test
VER-REQ-007 SUB-REQ-011 LOTO restart prevention test
VER-REQ-008 SUB-REQ-010 SHA-256 hash chain tamper detection test
VER-REQ-010 SUB-REQ-002 Raman spectrometer OQ performance test
VER-REQ-011 SUB-REQ-007 Laser diffraction OQ particle size accuracy test
VER-REQ-012 SUB-REQ-015 Paper backup fallback demonstration on integrity failure
VER-REQ-015 SUB-REQ-016 End-to-end G&B cycle test verifies HSG endpoint detection as first criterion
VER-REQ-015 SUB-REQ-017 End-to-end G&B cycle test verifies FBD LOD drying endpoint
VER-REQ-019 SUB-REQ-009 VER-REQ-019 verifies MES tamper-evident audit trail
VER-REQ-020 SUB-REQ-020 VER-REQ-020 verifies IBC Blender blend uniformity RSD criterion
VER-REQ-021 SUB-REQ-001 VER-REQ-021 verifies NIR spectrometer spectral acquisition parameters
VER-REQ-023 SUB-REQ-024 VER-REQ-023 verifies quantified PAT sensor-degraded performance floor
VER-REQ-023 SUB-REQ-006 PAT channel-degraded CQA suspension verified by induced degradation test
VER-REQ-007 SUB-REQ-012 LOTO event logging verified as part of LOTO registry and restart-prevention test
VER-REQ-016 SUB-REQ-013 MES batch genealogy recording verified by end-of-cycle genealogy record inspection
VER-REQ-012 SUB-REQ-014 EBR backup and recovery capability verified as part of data integrity failure simulation
VER-REQ-015 SUB-REQ-018 FBD temperature control tolerance verified within end-to-end G&B cycle test
VER-REQ-015 SUB-REQ-019 Granule sizing D90 limit verified within end-to-end G&B cycle IPC measurements
VER-REQ-016 SUB-REQ-021 G&B step-mass recording verified by post-cycle batch genealogy record inspection
VER-REQ-022 SUB-REQ-022 PAT NIR blend-endpoint unavailability fallback verified by degraded-mode transition test
VER-REQ-015 SUB-REQ-023 G&B containment under OEB 3 potency conditions verified within end-to-end cycle test
VER-REQ-024 SUB-REQ-027 Guard door LOTO interlock test verifies SUB-REQ-027
VER-REQ-025 SUB-REQ-028 Containment pressure test verifies SUB-REQ-028
VER-REQ-102 SUB-REQ-062 Inspection protocol for environmental sensor installation commissioning
VER-REQ-101 SUB-REQ-061 Test verification of MES watchdog timer and E-STOP safety functions
VER-REQ-100 SUB-REQ-060 Test verification of PCS power supply and UPS performance
VER-REQ-099 SUB-REQ-059 Inspection verification of granulation bay installation standards
VER-REQ-098 SUB-REQ-058 PAT autonomy override mechanism Test (IEC 61508 Functional Autonomy Safety Constraint)
VER-REQ-083 SUB-REQ-056 MES batch review package and QA sign-off workflow
VER-REQ-082 SUB-REQ-055 LIMS sample request receipt within MES 30-minute SLA
VER-REQ-081 SUB-REQ-054 Packaging vision inspection 100 percent coverage
VER-REQ-079 SUB-REQ-052 Tablet Compression metal detection per-tablet check
VER-REQ-076 SUB-REQ-049 CEC continuous air monitoring frequency and data logging
VER-REQ-074 SUB-REQ-047 Degraded Production mode batch quarantine and QA release gate
VER-REQ-073 SUB-REQ-044 Startup mode entry criteria and production mode gate
VER-REQ-072 SUB-REQ-043 MES server hardware rack and environmental controls
VER-REQ-070 SUB-REQ-041 Film Coating Subsystem 400V power supply
VER-REQ-069 SUB-REQ-040 Granulation and Blending Subsystem 400V power supply
VER-REQ-068 SUB-REQ-039 Tablet Compression Subsystem EPO power interruption response
VER-REQ-055 SUB-REQ-026 Tablet IPC system sampling rate at nominal press speed
VER-REQ-049 SUB-REQ-013 MES batch genealogy and material lineage tracking
VER-REQ-048 SUB-REQ-006 PAT subsystem degraded-mode NIR channel failure alert
VER-REQ-080 SUB-REQ-053 Dust explosion inerting and LEL monitoring (SIL-2 H-003)
VER-REQ-075 SUB-REQ-048 CEC airborne API concentration breach auto-response (SIL-2 H-001)
VER-REQ-071 SUB-REQ-042 CEC subsystem UPS power supply (SIL-2 H-001)
VER-REQ-066 SUB-REQ-046 Maintenance LOTO MES display enforcement (SIL-2 H-007)
VER-REQ-065 SUB-REQ-045 Emergency Stop mode exit criteria (SIL-2 H-001)
VER-REQ-064 SUB-REQ-038 MES watchdog timer EBR processing (SIL-2 H-006)
VER-REQ-054 SUB-REQ-023 OEB-3 containment during G+B operations (SIL-2 H-001)
VER-REQ-053 SUB-REQ-021 G+B mass balance recording (SIL-2 data integrity)
VER-REQ-052 SUB-REQ-019 Granule sizing mill PSD requirement (SIL-2)
VER-REQ-051 SUB-REQ-018 FBD inlet air temperature control (SIL-2)
VER-REQ-050 SUB-REQ-017 FBD LOD drying target (SIL-2 product quality)
VER-REQ-084 SUB-REQ-057 VER-REQ-084 verifies PAT audit log 30-day rolling archive integrity requirement (SIL-3 H-004)
VER-REQ-078 SUB-REQ-051 VER-REQ-078 verifies two-person independent verification for API dispensing (SIL-3 H-002)
VER-REQ-077 SUB-REQ-050 VER-REQ-077 verifies MES cleaning validation failure quarantine enforcement (SIL-3 H-002)
VER-REQ-067 SUB-REQ-047 VER-REQ-067 verifies the Degraded Production mode real-time release block (SIL-3 H-004)
VER-REQ-063 SUB-REQ-037 VER-REQ-063 verifies the PAT manual CQA override access control requirement (SIL-3)
VER-REQ-062 SUB-REQ-036 VER-REQ-062 verifies the PAT subsystem dedicated UPS power supply requirement (SIL-3 H-004)
VER-REQ-047 SUB-REQ-031 VER-REQ-047 verifies the SIL-3 HFT≥1 architectural redundancy requirement for PAT CQA evaluation
VER-REQ-015 SUB-REQ-016 VER-REQ-015 verifies complete G&B cycle from API charge to IBC seal meeting all CQA specifications
VER-REQ-025 SUB-REQ-028 VER-REQ-025 verifies tablet compression containment pressure differential and alarm response SUB-REQ-028
VER-REQ-037 SUB-REQ-012 VER-037 verifies SUB-012 LOTO event logging completeness
VER-REQ-038 SUB-REQ-014 VER-038 verifies SUB-014 EBR backup interval and restore time
VER-REQ-039 SUB-REQ-016 VER-039 verifies SUB-016 HSG endpoint response timing
VER-REQ-040 SUB-REQ-022 VER-040 verifies SUB-022 PAT-unavailable degraded blend safety gate
VER-REQ-041 SUB-REQ-025 VER-041 verifies SUB-025 compression force rejection gate and timing
VER-REQ-042 SUB-REQ-029 VER-042 verifies SUB-029 RFID tooling lifecycle gate and read-failure block
VER-REQ-043 SUB-REQ-030 VER-043 verifies SUB-030 IPC degraded mode response across all three channel failures
VER-REQ-001 SUB-REQ-003 VER-REQ-001 verifies NIR model evaluation latency requirement SUB-REQ-003
VER-REQ-002 SUB-REQ-004 VER-REQ-002 verifies diversion valve actuation time requirement SUB-REQ-004
VER-REQ-003 SUB-REQ-005 VER-REQ-003 verifies sensor degradation detection requirement SUB-REQ-005
VER-REQ-006 SUB-REQ-008 VER-REQ-006 verifies 21 CFR Part 11 authentication enforcement on EBR critical actions
VER-REQ-007 SUB-REQ-011 VER-REQ-007 verifies MES LOTO restart prevention requirement SUB-REQ-011
VER-REQ-008 SUB-REQ-010 VER-REQ-008 verifies EBR hash chain integrity detection SUB-REQ-010
VER-REQ-010 SUB-REQ-002 VER-REQ-010 verifies Raman spectrometer spectral range and resolution SUB-REQ-002
VER-REQ-011 SUB-REQ-007 VER-REQ-011 verifies laser diffraction analyser accuracy and repeatability SUB-REQ-007
VER-REQ-012 SUB-REQ-015 VER-REQ-012 verifies MES paper backup mode switchover on data integrity failure SUB-REQ-015
VER-REQ-019 SUB-REQ-009 VER-REQ-019 verifies EBR tamper detection via direct DB modification SUB-REQ-009
VER-REQ-020 SUB-REQ-020 VER-REQ-020 verifies IBC blend uniformity acceptance criterion SUB-REQ-020
VER-REQ-021 SUB-REQ-001 VER-REQ-021 verifies NIR spectrometer spectral range and SNR in production simulation SUB-REQ-001
VER-REQ-023 SUB-REQ-024 VER-REQ-023 verifies PAT channel degradation response timing and two-sensor safe state SUB-REQ-024
VER-110 IFC-021 IFC-021 EMS-MES OPC UA → VER-110 integration latency test
VER-111 IFC-022 IFC-022 hardwired safety bus → VER-111 fail-safe disconnection test
VER-113 IFC-023 IFC-023 dP Controller-HVAC 4-20mA interface → VER PID response test
VER-REQ-004 IFC-REQ-001 CQA alarm delivery and soak test
VER-REQ-005 IFC-REQ-003 Diversion acknowledgment delivery test
VER-REQ-013 IFC-REQ-006 Integration test for G&B-to-PAT NIR interface latency
VER-REQ-014 IFC-REQ-007 Integration test for MES-to-G&B recipe delivery and EBR feedback
VER-REQ-016 IFC-REQ-008 Inspection test for G&B-to-Compression sealed IBC handoff
VER-REQ-017 IFC-REQ-002 VER-REQ-017 verifies PAT sensor health status publishing via OPC UA
VER-REQ-018 IFC-REQ-004 VER-REQ-018 verifies CQA measurement stream latency and diversion trigger
VER-REQ-022 IFC-REQ-009 VER-REQ-022 verifies quantified degraded mode MES-PAT interface
VER-REQ-005 IFC-REQ-005 MES diversion command transmission latency verified by CQA alarm-to-acknowledgment timing test
VER-REQ-026 IFC-REQ-010 OPC-UA data stream test verifies IFC-REQ-010
VER-REQ-027 IFC-REQ-011 MES EBR write test verifies IFC-REQ-011
VER-REQ-009 IFC-REQ-001 VER-REQ-009 verifies the end-to-end PAT-to-diversion chain cumulative latency
VER-REQ-027 IFC-REQ-011 VER-REQ-027 verifies rejection events and state transitions are written to MES EBR within latency bound
VER-REQ-026 IFC-REQ-010 VER-REQ-026 verifies IPC OPC-UA data stream rate, timestamp accuracy, and channel completeness
VER-REQ-022 IFC-REQ-009 VER-REQ-022 verifies degraded-mode transition latency and CQA continuity on IFC-REQ-009
VER-REQ-018 IFC-REQ-004 VER-REQ-018 verifies real-time CQA measurement stream latency on PAT-to-MES interface IFC-REQ-004
VER-REQ-017 IFC-REQ-002 VER-REQ-017 verifies PAT-to-MES sensor health status OPC-UA update IFC-REQ-002
VER-REQ-016 IFC-REQ-008 VER-REQ-016 verifies IBC handoff seal inspection and batch genealogy record IFC-REQ-008
VER-REQ-014 IFC-REQ-007 VER-REQ-014 verifies MES-to-G&B recipe delivery and EBR feedback latency IFC-REQ-007
VER-REQ-013 IFC-REQ-006 VER-REQ-013 verifies G&B-to-PAT NIR interface data integrity and latency IFC-REQ-006
VER-REQ-005 IFC-REQ-003 VER-REQ-005 verifies MES diversion acknowledgment latency on IFC-REQ-003
VER-REQ-004 IFC-REQ-001 VER-REQ-004 verifies CQA alarm transit time and loss rate on PAT-MES OPC-UA interface
VER-REQ-036 IFC-REQ-020 VER-036 verifies IFC-020 LIMS batch release interface
VER-REQ-035 IFC-REQ-019 VER-035 verifies IFC-019 ERP production order interface
VER-REQ-034 IFC-REQ-018 VER-034 verifies IFC-018 material identity gate
VER-REQ-033 IFC-REQ-017 VER-033 verifies IFC-017 dispensing interface
VER-REQ-032 IFC-REQ-016 VER-032 verifies IFC-016 containment halt timing
VER-REQ-031 IFC-REQ-015 VER-031 verifies IFC-015 coating release gate
VER-REQ-030 IFC-REQ-014 VER-030 verifies IFC-014 packaging serialisation
VER-REQ-029 IFC-REQ-013 VER-029 verifies IFC-013 transfer gate
VER-REQ-028 IFC-REQ-012 VER-028 verifies IFC-012 Film Coating MES timing
VER-REQ-115 SYS-REQ-030 VER-REQ-115 verifies SYS-REQ-030 PCS cybersecurity
VER-112 SYS-REQ-013 SYS-REQ-013 OEL containment → VER-112 end-to-end safety chain test
REQ-SEPHARMAMANUFACTURING-026 SYS-REQ-028 Rack inspection VER → SYS-REQ-028 physical rack embodiment
VER-REQ-107 SYS-REQ-025 VER-107 → SYS-025 environmental sensor placement inspection
VER-REQ-106 SYS-REQ-022 VER-106 → SYS-022 facility layout inspection
VER-REQ-105 SYS-REQ-023 VER-105 → SYS-023 operator override test
VER-REQ-009 REQ-SEPHARMAMANUFACTURING-016 System-level PAT diversion chain integration test
VER-REQ-104 SYS-REQ-027 Hardware override test verifies PCS manual override and E-stop timing
VER-REQ-103 SYS-REQ-026 Calibration test verifies cleanroom sensor accuracy
VER-REQ-094 REQ-SEPHARMAMANUFACTURING-015 EBR lifecycle test verifies system EBR integrity requirement
VER-REQ-097 REQ-SEPHARMAMANUFACTURING-025 System-level IPC automated rejection verification
VER-REQ-096 REQ-SEPHARMAMANUFACTURING-023 System-level packaging serialisation and aggregation verification
VER-REQ-095 REQ-SEPHARMAMANUFACTURING-022 System-level PAT degraded-mode transition and manual sampling frequency verification
VER-REQ-094 REQ-SEPHARMAMANUFACTURING-015 System-level EBR lifecycle and 21 CFR Part 11 compliance verification
VER-REQ-093 REQ-SEPHARMAMANUFACTURING-014 System-level throughput and OEE verification via continuous production run
VER-REQ-092 REQ-SEPHARMAMANUFACTURING-024 System-level LOTO electronic lockout enforcement verification
VER-REQ-091 REQ-SEPHARMAMANUFACTURING-017 System-level containment negative pressure and HVAC verification
VER-REQ-090 REQ-SEPHARMAMANUFACTURING-016 System-level PAT CQA model accuracy verification
VER-REQ-089 REQ-SEPHARMAMANUFACTURING-020 End-to-end batch genealogy verification (SYS-REQ-007)
VER-REQ-088 SYS-REQ-017 OEE dashboard update latency confirmation
VER-REQ-087 SYS-REQ-021 Shift handover supervisor capability and pending action transfer
VER-REQ-060 SYS-REQ-017 OEE tracking per SEMI E10 equipment availability standard
VER-REQ-058 SYS-REQ-015 EU FMD serialisation and unit-level 2D code generation
VER-REQ-057 SYS-REQ-014 ICH Q8/Q11 process validation data recording
VER-REQ-085 SYS-REQ-019 Automatic deviation record on CPP exceedance (SIL-2)
VER-REQ-059 SYS-REQ-016 EN ISO 13849-1 machine safety PLd/PLe (SIL-2 H-007)
VER-REQ-056 SYS-REQ-013 OEL containment system requirement (SIL-2 H-001)
VER-REQ-086 SYS-REQ-020 VER-REQ-086 verifies the cleaning status registry system requirement (SIL-3 H-002)
VER-REQ-061 SYS-REQ-018 VER-REQ-061 verifies the SIL-3 PAT qualification enforcement system requirement
VER-REQ-046 REQ-SEPHARMAMANUFACTURING-021 VER-REQ-046 verifies MES-guided changeover workflow and electronic release gate
VER-REQ-045 REQ-SEPHARMAMANUFACTURING-019 VER-REQ-045 verifies system-level cleanroom environmental alarm and halt response times
VER-REQ-044 REQ-SEPHARMAMANUFACTURING-018 VER-REQ-044 verifies system-level emergency stop timing across all three activation paths

Orphan Requirements (no trace links)

RefDocumentRequirement
STK-REQ-001 stakeholder-requirements The manufacturing line SHALL achieve a minimum Overall Equipment Effectiveness (OEE) of 75% during Normal Production mod...
STK-REQ-002 stakeholder-requirements The manufacturing line SHALL maintain electronic batch records (EBRs) that fully comply with FDA 21 CFR Part 11 and EU A...
STK-REQ-003 stakeholder-requirements The manufacturing line SHALL perform continuous real-time in-process quality monitoring using Process Analytical Technol...
STK-REQ-004 stakeholder-requirements The manufacturing line SHALL maintain containment integrity for potent compounds with Occupational Exposure Limit (OEL) ...
STK-REQ-005 stakeholder-requirements When an emergency condition is detected, the manufacturing line SHALL achieve a full controlled stop of all process equi...
STK-REQ-006 stakeholder-requirements The manufacturing line SHALL comply with EU GMP Annex 1 (for sterile areas if applicable), EU GMP Annex 15 (validation),...
STK-REQ-007 stakeholder-requirements The manufacturing line SHALL support validated product changeover procedures that achieve cross-contamination residue le...
STK-REQ-008 stakeholder-requirements The manufacturing line SHALL integrate with the external drug serialisation system to apply unique identifiers to 100% o...
STK-REQ-009 stakeholder-requirements When a non-critical equipment fault or PAT sensor degradation is detected, the manufacturing line SHALL maintain product...
STK-REQ-010 stakeholder-requirements The manufacturing line SHALL maintain bidirectional traceability of all raw materials, intermediates, and finished produ...
STK-REQ-011 stakeholder-requirements While operating in Normal Production mode, the manufacturing line SHALL maintain cleanroom conditions at ISO Class 7 (EU...
STK-REQ-012 stakeholder-requirements The manufacturing line SHALL provide documented lockout/tagout (LOTO) procedures and physical isolation points for all e...
STK-REQ-013 stakeholder-requirements The manufacturing line SHALL produce finished drug products that comply with pharmacopoeial specifications for tablet ha...
SYS-REQ-001 system-requirements The system SHALL operate the production sequence — from raw material dispense through granulation, blending, compression...
SYS-REQ-002 system-requirements The system SHALL generate, execute, and archive electronic batch records (EBRs) with electronic signatures, access contr...
SYS-REQ-003 system-requirements The system SHALL acquire PAT sensor data (NIR, Raman, laser diffraction) at a minimum sample interval of 30 seconds, eva...
SYS-REQ-004 system-requirements The system SHALL maintain negative pressure isolation in potent compound processing enclosures (OEB 4/5 compounds, OEL <...
SYS-REQ-005 system-requirements When an emergency stop is triggered (by operator actuator, interlock, or automatic safety function), the system SHALL de...
SYS-REQ-006 system-requirements While in Normal Production mode, the system SHALL continuously monitor cleanroom differential pressure, temperature (20±...
SYS-REQ-007 system-requirements The system SHALL record and maintain a full batch genealogy database linking every finished product unit to its input ra...
SYS-REQ-008 system-requirements The system SHALL guide operators through validated cleaning procedures during product changeover, verify cleaning comple...
SYS-REQ-009 system-requirements When the PAT subsystem enters sensor-degraded mode, the system SHALL automatically switch to manual in-process testing m...
SYS-REQ-010 system-requirements The system SHALL apply 2D DataMatrix barcodes encoding a unique serial number, GTIN, lot number, and expiry date to 100%...
SYS-REQ-011 system-requirements The system SHALL enforce electronic lockout verification for maintenance activities, preventing equipment restart while ...
SYS-REQ-012 system-requirements The system SHALL enforce an automated in-process rejection of any tablet with weight outside ±5% of target, hardness out...
VER-REQ-108 verification-plan The verification activity for SYS-REQ-028 SHALL perform a physical commissioning inspection of the GMP equipment rack ho...